Generator Project Report
Generator Project Report
KADAPA DISTRICT-516312
CERTIFICATE
CHAPTER 1
Stator Frame
Stator Core
Stator Winding
Hydrogen Coolers
Rotor Shaft
Rotor Winding
Rotor Retaining Rings
Field Connections
Bearings
CHAPTER 2
2.1 Protective Relays
2.2 Nature of Faults in Generator
Effect of Faults
Causes of Faults
CHAPTER 3
Generator Protection
3.1 Voltage balance protection
3.2 Stator earth fault
3.3 Rotor earth fault
3.4 Negative phase sequence
3.5 Over voltage protection
3.6 Under voltage protection
3.7 Over frequency protection
3.8 Under frequency protection
3.9 loss of excitation
3.10 Pole slip relay
3.11 Failure of the prime mover
3.12 Over current protection
3.13 Over flux protection
3.14 Under flux protection
3.15 Reverse power protection
3.16 low forward power protection
3.17 Backup impedance protection
3.18 Differential Protection
3.19 Overall differential protection
CHAPTER 4
4.1 Relay Settings
CHAPTER 5
5.1 Excitation System
1.1 NEED FOR PROTECTION
A fault in power system is defined as a defect in its electrical
circuit due to which the flow of current is diverted from the intended path.
Breaking of conductors or failure of insulation causes faults. Fault impedance is
generally low and fault current is generally high. During the faults, the voltages of
the phases become unbalanced and the supply to the neighboring circuit is
affected .Fault currents being excessive they can damage not only the faulty
equipment, but also the installation through which the fault current is fed.
a. Stator frame:
b. Stator core:
Micalastic-High-Voltage Insulation:
To minimize corona discharges between the insulation and the slot wall, a
final coat of semi conducting varnish is applied to the surface of all bars within
the slot range.
In addition, all bars are provided with an end corona protection to
control the electric field at the transition from the slot to the end winding and to
prevent the termination of creep age spark concentrations.
The 210 mw turbo generator having cylindrical rotor two pole uses
direct hydrogen cooling for the rotor winding and indirect H2 cooling for the stator
winding. The hydrogen coolers are arranged horizontally inside the stator. The
heat losses arising in the generator are dissipated through hydrogen. The heat
dissipating capacity of hydrogen is eight times higher than that of air. The losses
in the generator components such as iron losses, friction losses and windage
and stray losses are also dissipated through hydrogen.
The hydrogen cooler is a shell and tube type heat exchanger which
cools the hydrogen gas in the generator. The heat removed from the hydrogen is
dissipated through the tubes, while the hydrogen is passed around the finned
tubes.
The hydrogen cooler is subdivided into sections which are
horizontally mounted in the stator frame. All parallel-connected water paths must
have equal flow resistances to ensure a uniform cooling water supply to the
cooler sections and equal cold gas temperature downstream of the individual
sections. The required cooling water volume flow is adjusted by control valves on
the hot water side. Controlling the cooling water volume flow on the outlet side
ensures an uninterrupted water flow through the cooler sections so that proper
cooler performance will not be impaired.
To maintain the cold gas temperature at an approximately constant
level under all operating conditions, a motor-operated control valve is arranged in
the common cooling water outlet line. The control valve is activated by
temperature transmitters located upstream and downstream of the cooler
sections.
a.Rotor shaft:
To ensure that only high-quality forgings are used, strength test, material
analysis and ultrasonic tests are performed during manufacture of the rotor. After
completion, the rotor is balanced in various planes at different speeds and then
subjected to an over speed test at 120% of rated speed for two minutes.
b.Rotor winding:
The rotor winding consists of several coils which are inserted into
the slots and series connected such that two coil groups form one pole. Each coil
consists of several series connected turns, each of which consists of two half
turns which are connected by brazing in the end section.
The rotor winding consists of silver-bearing de-oxidized copper hallow
conductors with two lateral cooling ducts. L-shaped strips of laminated epoxy
glass fiber fabric with Nomex filler are used for slot insulation. The slot wedges
are made of high-conductivity material and extend below the shrink seat of the
retaining ring. The seat of the retaining ring is silver-plated to ensure a good
electrical contact between the slot wedges and rotor retaining rings. This system
has long proved to be a good damper winding.
c. Retaining Rings:
d. Field connections:
3. BEARINGS:
The sleeve bearings are provided with hydraulic shaft during start up and
turning gear operation. To eliminate shaft currents, all bearings are insulated from
the stator and base plate respectively. The temperature of the bearings is stored
with thermocouples embedded in the lower bearing sleeve so that the measuring
points are located directly below the habits. The bearings have provisions for
fitting vibration pickups to monitor bearing vibrations.
FORMS OF PROTECTION:
The various forms of protection applied to generator units fall into one of the
following two categories:
i) Protective relay (or) device to detect faults occurring outside the
generator unit.
ii) Protective relay (or) device to detect faults occurring within the
generator unit and the associated connections
The protective relays could not in themselves prevent faults but can
only detect and minimize fault damage. However, as it is desirable to avoid any
undue stresses in the generator and transformer windings, it is usual practice to
install surge capacitors or divertors to reduce the effects of lightning and other
voltage surges on both the line side of the transformer and the machine
terminals.
A protective relay is a device that detects the fault and initiates the
operation of the circuit breaker to isolate the defective element from the rest of
the system.
The relays detect the abnormal conditions in the electrical circuits
by constantly measuring the electrical quantities which are different under normal
and fault conditions. The electrical quantities which may change under fault
conditions are voltage, current, frequency and phase angle. Through the
changes in one or more of these quantities, the faults signal their presence, type
and location to the protective relays. Having detected the fault, the relay operates
to close the trip circuit of the breaker. This results in the opening of the breaker
and disconnection of the faulty circuit.
BASIC RELAY CIRCUIT
2. Speed: The relay system should disconnect the faulty section as fast as
possible for the following reasons:
A. Electrical apparatus may be damaged if they are made to carry the fault
currents for a long time.
B. A failure on the system leads to a great reduction in the system voltage. If the
faulty section is not disconnected quickly, then the low voltage created by the
fault may shut down consumers’ motors and the generators on the system may
become unstable.
C. The high speed relay system decreases the possibility of development of one
type of fault into the other more severe type.
3. Sensitivity: It is the ability of the relay system to operate with low value of
actuating quantity.
4. Reliability: It is the ability of the relay system to operate under the pre-
determined conditions. Without reliability, the protection would be rendered
largely ineffective and could even become a liability.
5. Simplicity: The relaying system should be simple so that it can be easily
maintained. Reliability is closely related to simplicity. The simpler the protection
scheme, the greater will be its reliability.
2.2 NATURE OF FAULTS IN GENERATORS:
EFFECT OF FAULTS
The most dangerous type of fault is a short circuit as it may have the
following effects on a power system, if it remains uncleared.
1. Heavy short circuit current may cause damage to equipment or any other
element of the system due to overheating and high mechanical forces set up due
to heavy current
2. Arcs associated with short circuits may cause fire hazards. Such fires,
resulting from arcing, may destroy the faulty element of the system. There is also
a possibility of the fire spreading to other parts of the system if the fault is not
isolated quickly.
3. There may be reduction in the supply voltage of the healthy feeders, resulting
in the loss of industrial loads.
4. Short circuits may cause the unbalancing of supply voltages and currents,
thereby heating rotating machines.
5. There may be a loss of system stability. Individual generators in a power
station may lose synchronism, resulting in a complete shutdown of the system.
Loss of stability of interconnected systems may also result. Subsystems may
maintain supply for their
individual zones but load shedding would have to be resorted in the sub-system,
which was receiving power from the other subsystem before the occurrence of
the fault.
6. The above faults may cause an interruption of supply to consumers, thereby
causing a loss of revenue.
CAUSES OF FAULTS
Birds also may cause faults on overhead lines if their bodies touch one of
the phases and the earth wire ( or the metallic supporting structure which is at
earth potential) If the conductors are broken, there is a failure of the conducting
path and the conductor becomes open-circuited. If the broken conductor falls to
the ground, it results in a short circuit. Joint failures on cables or overhead lines
are also a cause of failure of the conducting path. The opening of one or two of
the three phases makes the system unbalanced. Unbalanced currents flowing in
rotating machines set up harmonics, thereby heating the machines in short
periods of time. Therefore, unbalancing of the lines is not allowed in the normal
operation of a power system. Other causes of faults on overhead lines are direct
lightning strokes aircraft, snakes, ice and snow loading abnormal loading, storms,
earthquakes, creepers etc. In the case of cables, transformers, generators and
other equipment, the causes of faults are: failure of the solid insulation due to
aging, heat, moisture or over voltage, mechanical damage, accidental contact
with earth or earthed screens, Flashover due to over voltages, etc.
CLASS-A:- This covers all electrical protections for faults with in the generating
unit in which generator field breaker, generator breaker and turbine should be
tripped.
CLASS-C:- This covers electrical protection for faults in the system in which
generator will be unloaded by tripping of generator breakers only. The unit will
come to house load operation and the UAT will be in service. Various protections
of this class are
i. 220 KV busbar protection
ii. Generator transformer HV side breaker pole discrepancy
iii. Generator negative phase sequence protection
iv. Generator transformer over current / earth fault protection
v. Reverse power protection without turbine trip.
3.1 GENERATOR VOLTAGE BALANCE PROTECTION
Application:
Normally generator circuits have more than one voltage
transformer,for protection, metering and for automatic voltage regulator(AVR).
These will be, In general Y/Y connected with primary and secondary neutrals
earthed.They will also have fuses both on primary and secondary sides.In
general,however,standard fuse failure relay schemes connected across
secondary fuses will not be adequate for monitoring the healthiness of such VTs
as these schemes cannot detect primary fuse failure. In such cases,the voltage
balance principle is used for detecting the failure of the VT due to either primary
or secondary fuse failure.
Relay Description:
Three attracted armature units are employed. Unit A is fed from a
resistance/capacitance network which under healty conditions with negligible
harmonics has zero output.An operationg voltage appears across the coil of unit
A when the secondary voltages become unbalanced due to loss of any one
primary or secondary fuse.
Unit B is normally energized via the normally closed contact on Unit A form two
phases of the supply.
Unit B has three changeover contacts and this unit drops off on operation of Unit
A,or on complete loss of supply,or on loss of two primary or secondary phases.
Unit C is a DC auxiliary unit energized by normally closed cantact of Unit B. The
Unit C has 30 to 40m.sec.time delay on pickup. Unit Chas 2 N/O+2 C/O output
contacts, which can be used to block protection trip and sound VT faulty alarm
when VT fault occurs.
Technical Data
Contacts Ratings :
AC Make and carry Make and carry Break
Continuously for 3secs
1250VA with 7500VA with 1250VA with
maxima of 5A maxima of 30A maxima of 5A
and 660V and 660V and 660V
F=B2A/8pi
Where, A=area
B=flux density
The attracting force is in consenence large on one pole but very weak on the
opposite one.
This result in an unbalanced forces and hence produced a violent vibration which
may damage bearing surpace or even.
Displace the rotor by an amount sufficient far cause it to found the stator.
METHODS:
Three methods are available to detect this type of faults.
i. Potentiometer method
ii. A.C.injection method
iii. D.C injection method.
i. POTENTIOMETER METHOD:
This scheme is simple no auxiliary supply is used.A blind spot exists at the centre
of field winding.This point being at a potential eveal to that of tapping point on the
potentiometer.
To check the blind spot the tapping point is varied by a push button or switch.
The generator grounding resistor normally limits the neutral voltage transmitted
from the high voltage side of the unit transformer in case of a ground fault on the
H.V. side to maximum 2 – 3% of rated generator phase voltage.
Short circuits between the stator winding in the slots and the stator core are the
most common electrical fault in Generators. Interturn faults, which normally are
difficult to detect, will quickly develop into a ground fault and will be tripped by the
stator ground fault protection.
95% Stator Ground fault Relay for Generator
For generators with unit transformer and with high impedance grounding of the
neutral, a neutral voltage relay with harmonic immunity and independent time
delay is used. The relay is normally set to operate at 5% of maximum neutral
voltage with a time delay of 0.3 – 0.5 second. With this voltage setting, it
protects approximately 95% of the Stator winding.
It also covers the generator bus, the low voltage winding of the unit transformer
and the high voltage winding of the unit aux. Transformer.
Relay details : 64 A/B – Neutral Displacement Relay having IDMT or definite time
characteristic.
Ground faults caused by mechanical damage may occur close to the generator
neutral. Today there is a distinct trend towards providing ground fault protection
for the entire stator winding (100% stator ground fault protection).
The 100% stator ground fault scheme includes a 95% unit (1), which covers the
stator winding from 5% of the neutral and 3 rd harmonic voltage measuring unit
(2) which protects the rest of the stator winding.
For generators with 3rd harmonic voltage less than 1%, a filter is available with a
damping factor of more than 100.
When the generator is running and there is no ground fault near the neutral, the
third harmonic voltage unit (2) and the voltage check unit (4) are both activated
and the relay contact used in alarm / trip circuit is open. If a ground fault occurs
close to the generator neutral, the third harmonic voltage unit will reset, operating
relay contact will close and alarm or tripping is obtained.
The voltage check unit is included to prevent faulty operation of the relay at
generator standstill or during the machine running up or running down period.
Generators which produce more than 1% third harmonic voltage under all service
conditions, can have the entire stator winding up to and including the neutral
point protected by the 100% stator ground fault relay.
3.4 NEGATIVE SEQUENCE AND UNBALANCE PROTECTION:
T = Time in seconds
Protects the rotor of a generator from damage resulting from the heating effects
of negative phase sequence currents.
Accurate over a wide system frequency range.
The protection must be timegraded to allow downstream protection to clear on
unbalance fault.
Can provide back up protection for uncleared asymmetric faults.
The alarm elements is commonly set to70% of the trip setting with a time delay
well above the time taken to clear any system faults.The alarm element functions
directly on the measured level of negative phase sequence current.
Measurement of Negative Sequence components:
The ‘A’ phase C.T is loaded with a resistance where as the ‘C’ phase C.T
energizes reactor and resistor in series.
The total power factor of the circuit is O.S i.e cos60
The ‘A’ phase voltage drop is in phase with a phase current.
The ‘C’ phase voltage drop, therefore leads the current by 60.
Vzc
With positive sequence currents, the A and C phase voltages are in opposition
IB
and so the resultant voltage is zero.
IC
Where as negative sequence currents produces resultant voltage across the
Vzc IC
relay.
If the current contained azero sequence component, this would also produce an
outputs.
Zero sequence current doesn’t cause heating of generator rotor.
So, this component is sometimes eliminated by a star-delta group of auxillary
transformers with in the relay.
The protection should have a time delay characteristic, which is as near as in
practice for the heating characteristics of the machine.
The relay contains alarm features which operates at a setting equal to (or)
slightly lower than tripping element.
Time calculations:
For stage-1
Only 1/3 rd injected current is negative sequence current
I2 (setting) = 7.5%
So ininjected current =3 * 7.5% * 5 * 2 = 2.25amps
( I2 )² t =K1 * K3
K1 = 2.25
K3=3.3
[(2*7.5% *5)/5]² t = 2.25 * 3.3
t = 330sec
Operates when the 3 phase voltages fall below the common set point.
Can be interlocked with field failure protection to prevents its operation during
stable power swings.
Can be detected failure of the AVR (or) system faults which have failed to be
cleared by other means.
Prevents damage to any connected loads which could occur during operation at
less than rated voltage.
The pick up level should be set to less than the voltage seen for a 3 phase fault
at the remote end of any connected feeder.
The time delay should be set to allow the appropriate feeder protection to
operate first to clear fault, and also to prevent operation of protection during
transient voltage dips.
Setting is 70% Vn.
Over current protection is that protection in which the relay picks up when the
magnitude of current exceeds the pickup level. The basic element in over current
protection is an over current relay.
The over current relays are connected to the system, normally by means
of CT's. Over current relaying has following types:
1. High speed over current protection.
2. Definite time over Current protection.
3. Inverse minimum time over Current protection.
4. Directional over current protection.
Over current protection includes the protection from overloads. This is most
widely used protection. Over loading of a machine or equipment means that
machine is taking more current than is rated Current. Hence over loading,
associated with temperature rise. The permissible temperature rise has limit
based on insulation class and material problems. Over current protection of over
loads is generally provided by thermal relays.
Operation:
Referring to fig shown the 3 current transformers and relay coils
connected in star, the star point is grounded. When short circuit occurs in
protected zone, the secondary current of CT increases. When current through
the relay exceeds its setting the disc unit operates and closes disc contacts to
complete the path for secondary winding. The auxiliary unit connected across the
rectifier goes path and one of its NO contacts reinforces the disc contacts. The
other NO contacts of auxiliary unit are available for tripping and for alarm
purposes. With suitable time delay of operation.
Application:
- Motor protection
- Transformer protection
- Line protection
- Protection of utility equipment
The normally closed contact of under currents relay is open during healthy c
condition.
On loss of field currents, it closes to energizetiming relay T1.This relay operates
instantly to energise timer T2,which has an adjustable time relay to pick up of 2-
10 seconds.
Relay T1 is time delayed on drop off to stabilize the scheme against slip
frequency effects.
Time relay in T2 to prevents spurious operation for external fault.
3.12 POLE SLIP RELAY:
The pole slipping relay is designed to protect synchronous generator’s against
the possibility of machine running unstable region of power angle curve which
would result in power oscillation and pole slip.
Pole slipping of generator with respect to the system leading to an increase in
rotor angular position beyond the generator transient stability limits.
Some of the causes for poleslipping are as follows.
Large network disturbance.
Faults on the network close to the generator.
Loss of generator field.
Operating the generator in excessive under excited mode.
Exciter
SETTING RECOMMENDATIONS:
If the source of oscillation lies between generator/transformer unit. The machine
has to be isolated from the network after the first slip.
Forward reach of the relay characteristics shall cover generator/generator
transformer.
Tripping in this zone shall be in the first pole slip.
The reach of this zone=0.7 Xd’
If the source oscillation lies outside the unit in the network the generator should
not be switched off until several pole slips have recurved.
3.13 FAILURE OF THE PRIME MOVER:
When a generator operating in parallel with others loses its driving force, it
remains in synchronism with system and continuous to run a s a synchronous
motor.
If draws sufficient power to drive the prime mover.
Synchronous machines can be used as an alternator when driven mechanically
(or) as motor when driven electrically.
This condition is not dangerous to generator but it is dangerous to turbine.
In a steam turbine under normal operation there is a continuous flow of steam
through the machine.
Any losses due to turbulence will be converted into heat, but this heat is
continuously carried away.
If the flow of steam causes while the set continues to run at full speed, the
turbulence losses in the trapped steam may then build up a high temperature
condition in the low pressure stages,leading to soft bearing and distortion of the
blades.
The wattmetric relay with directional characterstic is use.
Reverse power relay defects active power flow in to generator.
A high sensitivity current input is used to monitor the system power.This may be
connected to the main system protection C.T’s.
A Compensation angle setting is provided to conpensate for CT and VT phase
errors.
Reverse power relay setting =0.5% of rated active power..
Stage 1=with turbine trip, a time delay of 3 sec shall be adopted.
Stage2= with out turbine trip a time delay of 20 sec can be adopted to acoid
unnecessary tripping of unit during system disturbance causing sudden rise and
frequency or power swing condition.
3.14 BACK UP IMPEDANCE PROTECTION:
Application:
Back up impedance relay is a stand by relay. This relay can be operated to any
fault occurring in the generator in case only when the necessary relay fails to
operate.
Description:
This relay is a non-directional 3-phase impedance relay having circular
characteristics. The relay is generally applied for the back up protection of
generator/transformer units. In these applications it is possible that the sustained
short circuit current for a multi phase fault will be less than the load current. The
under impedance relay gets over this problem as its operation is a function of
voltage and current.
At rated voltage this relay operates as a definite time over current relay. When
the terminal voltage drops the relay operates at a lower current. A built in timer
with adjustable settings ensures that the relay operates only for faults, which are
not cleared by other protection.
When the relay is used for the protection of generators connected to generator
transformers it is necessary to use auxiliary voltage transformer connected is
delta/star so that the relay on the generator side measures the same impedance
for a phase-phase or 3 phase faults on the high voltage side of the step up
transformers. However when this requirement is not essential, the delta/star
interposing VTS can be omitted.
3.15 GENERATOR REVERSE POWER PROTECTION (32):
This is basically the protection provided for the prime mover i.e. turbine. If the
driving torque becomes less such as closure of main steam valves in case of
steam turbo generator, the generator starts to work as a synchronous
compensator, taking the necessary active power from the network. The
reduction of steam flow reduces the cooling effect on the turbine blades and
overheating may occur. The work done by the entrapped steam in the turbine s
then zero. As generator is not designed to run as a motor it should be
immediately tripped when the steam flow to the turbine is stopped and to avoid
damage to the turbine blades.
The relay contains directional current relay which measures the product IX cosǿ,
where ǿ is the angle between the polarizing voltage and the current to the relay.
The scale range used is 5 – 20 mA for 1A and 30-120 mA for 5A rated CT
secondary currents. Time delay of 2 seconds is provided
3.16 LOW FORWARD POWER PROTECTION:
Operates when the forward power falls below the set level.
Typical levels of motoring power and possible motoring damage that could occur
for various types of generating plant are given in table below.
The extent of the damage will depend upon the fault current level and the
duration of the fault.
Protection should be applied to limit the degree of damage in order to limit repair
costs.
For primary generating plant, high speed disconnection of the plant from the
power system may be necessary to maintain system stability.
This form of unit protection allows discriminative detection of winding faults, with
no intentional time delay, where a significant fault current arises.
The zone of protection ,defined by the location of the CT’s , should be arranged
to overlap protection for other items of plant ,such as a busbar or a step up
transformer.
The current flowing through the zone of protection will cause current to circulate
around the secondary wiring.
If the CT’s are of the same ratio and have identical secondary currents and
hence zero current will flow through the relay
As general low impedance biased differential relay, the MBCH may also be
regarded as an alternative to the high impedance type relay for the protection of
reactors, motors and generators.
The relay is externally stable during through faults, even when energized given
line current transformer of only moderate output. Immunity to fault tripping due to
large enrich currents on energization of the power transformers and also during
over fluxing conditions, is generated by the use of a novel feature not involving
harmonic filter circuits and their associated delay.
The type MBCH relay is high speed biased differential relay suitable for the
protection two or three winding power transformers, auto transformers or
generator transformer units. The differential protection measuring circuits is
based on well known Merz-Price circulating current principal. The outputs form
each bias restraint transformer T3 proportional to the appropriate primary line
currents, are rectified and summed to produce a bias resistant voltage. Any
resulting difference current is circulated through transformers T1 and T2.The
output form T1 is combined and rectified with the bias voltage to produce a signal
applied to the amplitude comparator. The comparator output pulses, which vary
in width depending on the amplitude of the combined bias and difference
voltages, are fed into a circuit which measures the time interval between pulses.
If the instantaneous value of the differential current exceeds the threshold level
set by the bias, timer is initiated when this time delay expires, the relay output
element is initiated to give a trip. However, if during this time delay period the
instantaneous value of the differential current faults below the threshold and
retains below for longer than a further present time, as it would during
transformer magnetizing inrush conditions, the initial timer is reset and operation
of the relay is blocked.
If the instantaneous value of the differential current exceeds the threshold level
set by the bias, timer is initiated when this time delay expires, the relay output
element is initiated to give a trip. However, if during this time delay period the
instantaneous value of the differential current further present time, as it would
during transformer magnetizing inrush conditions, the initial timer is reset and
operation of the relay is blocked.
BRUSHLESS SYSTEM
The brush less excitation system consists of an alternator, rectifier, main
exciter and a permanent magnet generator pilot exciter. Both the main and pilot
exciters and driven directly from the main shaft. The main exciter has a
stationary field and a rotating armature directly connected, through silicon
rectifiers, to the field of the main alternator. The pilot exciter is a shaft driven
permanent magnet generator having rotating permanent magnets attached to the
shaft and a 3-phase stationary armature, which feeds the main exciter’s field
through 3-phase full wave phased controlled thyristor bridges. This system
eliminates the use of commutator, collector and brusher and has a short time
constant and a response time of less than 0.1 second.
The 3-phase pilot excites in a six-pole revolving field unit. The frame
accommodates the laminated core with the three-phase winding. The rotor
consists of a shaft with mounted poles. Each pole consists of separate
permanent magnets.
2. AUTOMATIC VOLTAGE REGULATOR:
A voltage regulator is the heart of the excitation system. The output
voltage of the generator changes only when the voltage regulator instructs the
excitation system to do so irrespective of the speed of response of the exciter. A
regulator senses changes in the output voltage and / or current and causes
corrective action to take place. If the regulator is slow i.e., has dead band or
backlash or is otherwise insensitive, the system will be a poor one. By dead band
of a regulator is meant the time elapsing between the voltage deviation and the
return to the prescribed value due to slow action of the regulator.
The automatic voltage regulator performs the following functions-
1. Control of system voltage within prescribed limits.
2. Proper division of reactive power between the alternators operating in
parallel.
3. Prevention of dangerous over-voltages on the occurrences of sudden loss
of load on the system.
4. Increase of excitation under system fault conditions so that maximum
synchronizing power exists at the time of clearance of fault, to prevent
loss of synchronism.
4. RECTIFIER WHEELS:
The main components of the rectifier wheels are the silicon diodes,
which are arranged in the rectifier wheels in a three-phase bridge CKT. The
arrangement of the diode is such that this contact pressure in increased by the
centrifugal force during rotation.
BRUSHLESS EXCITATION SYSTEM ADVANTAGES:
1. Fast response.
2. CT slip rings and brushes for the same are completely eliminated.
3. No generator field breaker is possible exciter field breaker with its field
discharge is provided. Slow discharge of generator field Is accepted for
brush-less generator sets as internal faults with in the generator are rare.
4. Generally generator field volt meters and rotor temp recorder can’t be
provided due to absence of slip rings. In special cases telemetry systems
are developed by the manufacturer to provide these facilities.
5. Generator field current indication is possible by provision of quadrature
axis coil in brush-less exciter.
6. For TG units with single machine size of over 660 MVA and where
elimination of current collection slip rings and brushes is important this is
preferred.
CONCLUSION
BIBLIOGRAPHY
4. R.T.P.P. MATERIAL