Feed-Through Terminal Block - UT 4 - 3044102: Key Commercial Data
Feed-Through Terminal Block - UT 4 - 3044102: Key Commercial Data
com/pi/products/3044102
Feed-through terminal block, nom. voltage: 1000 V, nominal current: 32 A, connection method: Screw
connection, number of connections: 2, cross section: 0.14 mm² - 6 mm², AWG: 26 - 10, width: 6.2 mm, height:
46.9 mm, color: gray, mounting type: NS 35/7,5, NS 35/15
Your advantages
The large wiring space enables the connection of solid and stranded conductors without ferrules, even above the nominal cross section
As well as saving space, the compact design enables user-friendly wiring in a small amount of space
Optimum screwdriver guidance through closed screw shafts
Tested for railway applications
The cable entry funnel enables the use of conductors with ferrules and plastic collars within the nominal cross section
GTIN
GTIN 4017918960391
Weight per Piece (excluding packing) 8.900 g
Weight per piece (including packing) 9.282 g
Custom tariff number 85369010
Country of origin Germany
Technical data
General
Number of levels 1
Number of connections 2
Potentials 1
Nominal cross section 4 mm²
Color gray
Insulating material PA
Flammability rating according to UL 94 V0
03/13/2019 Page 1 / 5
https://www.phoenixcontact.com/pi/products/3044102
ASD level 2 2
1.857 (m/s ) /Hz
Acceleration 0,8 g
Test duration per axis 5h
Test directions X-, Y- and Z-axis
Shock test result Test passed
Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
Shock form Half-sine
Acceleration 5g
Shock duration 30 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE
125 °C
0304-21))
Static insulating material application in cold -60 °C
Behavior in fire for rail vehicles (DIN 5510-2) Test passed
Flame test method (DIN EN 60695-11-10) V0
Oxygen index (DIN EN ISO 4589-2) >32 %
NF F16-101, NF F10-102 Class I 2
NF F16-101, NF F10-102 Class F 2
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Dimensions
03/13/2019 Page 3 / 5
https://www.phoenixcontact.com/pi/products/3044102
Connection data
Connection method Screw connection
Connection in acc. with standard IEC 60947-7-1
Note: Product releases, connection cross sections and notes on
Note
connecting aluminum cables can be found in the download area.
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 10
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 6 mm²
Min. AWG conductor cross section, flexible 26
Max. AWG conductor cross section, flexible 10
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 4 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 4 mm²
2 conductors with same cross section, solid min. 0.14 mm²
2 conductors with same cross section, solid max. 1.5 mm²
2 conductors with same cross section, stranded min. 0.14 mm²
2 conductors with same cross section, stranded max. 1.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with
0.5 mm²
plastic sleeve, min.
2 conductors with same cross section, stranded, TWIN ferrules with
2.5 mm²
plastic sleeve, max.
2 conductors with same cross section, stranded, ferrules without plastic
0.14 mm²
sleeve, min.
2 conductors with same cross section, stranded, ferrules without plastic
1.5 mm²
sleeve, max.
Connection in acc. with standard IEC/EN 60079-7
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 10
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 4 mm²
03/13/2019 Page 4 / 5
https://www.phoenixcontact.com/pi/products/3044102
Drawings
Circuit diagram
03/13/2019 Page 5 / 5