Motor Protection Circuit Breakers
Motor Protection Circuit Breakers
Protection
Circuit
Breakers
About us
1
Product Range
L&T introduces complete range of Supernova product covering Motor Protection Circuit Breakers,
Contactors / Thermal Overload Relays & Motors.
The latest range of Contactors The unique range of 3 Phase Inverter Duty Motors
& Thermal Overload relays, (LTI Series) operate at desirable base speed, reducing
rated from 9A to 110A. the cost of switchgear, cable & inverter. These motors
can operate from its rated speed to 10% of rated
speed without any reduction in torque. They are
suitable for lower speed or lower frequency operation.
They can be offered for constant power application in
field weakening mode.
2
Motor Protection Circuit Breakers
Functions
Moulded Case Circuit Breaker and Thermal Overload Relay functions integrated
into a highly compact unit known as Motor Protection Circuit Breaker.
}
Short circuit protection
l
Overcurrent protection
l
MPCB-Advantages
Line protection
l
Compactness
l
Overload protection
l Reduction in wiring work
l
Select the branch circuit cable & confirm the control panel specifications
Adjustable thermal magnetic trip type MPCB Instantaneous trip type MPCB
3
Typical Problem in the Conventional System
and their Solution by using MPCB
When numerous small and medium motor loads exist in a circuit requiring
high breaking capacity, there is no high breaking capacity circuit breaker
with a small rated current for a short circuit protection.
The MPCB can be used in 100kA short circuit current circuits for three-phase,
240V motors with rated capacity upto 15kW, and in 50kA short circuit current circuits
for three phase, 415V motors with rated capacity up to 30kW.
Despite their compact size, the MPCB provide high-performance short-circuit current
breaking. They eliminate the need for an upstream circuit breaker for back-up use.
Overload Protection
The compact size of the MPCB, including overload relay functions, enables a smaller
installation area with less wiring space, for a reduction in panel size.
4
Ordering Information
Thermal & Magnetic Trip - Rocker Type
Frame Rating Motor Rating at Type Thermal Release Breaking
size (mm) (A) 415V, 50Hz (kW) Designation Cat Nos.
Range (A) Capacity
0.16A - 0.1-0.16A ST41889OOOO
0.25A 0.16 0.16-0.25A ST41890OOOO
0.4A 0.09 0.25-0.4A ST41891OOOO
0.63A 0.12 0.4-0.63A ST41892OOOO
1.0A 0.25 0.63-1.0A ST41893OOOO
45 mm 1.6A 0.55 MOG-S1 1.0-1.6A ST41894OOOO 100kA
2.5A 0.75 1.6-2.5A ST41895OOOO
4A 1.50 2.5-4A ST41896OOOO
6.3A 2.20 4.0-6.3A ST41897OOOO
10.0A 4.00 6.3-10.0A ST41898OOOO
13.0A 5.40 9.0-13.0A ST41899OOOO 50kA
5
Accessories
A wide variety of accessories enables a flexible response to change in specifications. Snap-on fittings speed up mounting.
9mm external device Internal device 9mm external device 18mm external device
Left-side mounting Front mounting MPCB Right-side mounting Right-side mounting
Undervoltage
trip device
Auxiliary alarm
contact blocks
Short-cirucuit alarm
contact block Shunt trip device
Short-circuit alarm
55mm
contact block
6
Technical Specifications
Number of poles 3 3
Maximum motor capacity AC3 7.5 kW (at 200-240V), 15 kW (at 380-440V) 7.5 kW (at 200-240V), 15 kW (at 380-440V)
AC3 Electrical/Mechanical endurance 100000 (32A:70000)/100000 (32A:70000), (25cycles/hour) 100000 (32A:70000)/100000 (32A:70000), (25cycles/hour)
Overload, Phase loss protection yes (according to IEC60947-4-1) yes (according to IEC60947-4-1)
Dimensions (mm) W x H x D 45 x 90 x 66 45 x 90 x 66
Relative humidity 45 ~ 85%RH No dew formation or freezing due 45 ~ 85%RH No dew formation or freezing due
Standard Operation altitude Up to 2000m to rapid temperature change allowed Up to 2000m to rapid temperature change allowed
service
condition Atmosphere having no excess Vapour, Steam, Dust, Atmosphere having no excess Vapour, Steam, Dust,
Atmosphere
Corrosive gas, Salt, Flammable gas Corrosive gas, Salt, Flammable gas
7
MOG-H2 MOG-H1M MOG-H2M
3 3 3
15 kW (at 200-240V), 30 kW (at 380-440V) 7.5 kW (at 200-240V), 15 kW (at 380-440V) 15 kW (at 200-240V), 30 kW (at 380-440V)
55 x 110 x 96 45 x 90 x 79 55 x 110 x 96
45 ~ 85%RH No dew formation or freezing due 45 ~ 85%RH No dew formation or freezing due 45 ~ 85%RH No dew formation or freezing due
Up to 2000m to rapid temperature change allowed 2000m to rapid temperature change allowed Up to 2000m to rapid temperature change allowed
Atmosphere having no excess Vapour, Steam, Dust, Atmosphere having no excess Vapour, Steam, Dust, Atmosphere having no excess Vapour, Steam, Dust,
Corrosive gas, Salt, Flammable gas Corrosive gas, Salt, Flammable gas Corrosive gas, Salt, Flammable gas
8
Breaking Capacity at Different Voltages
MOG-S1
AC240V AC415V AC460V AC690V
AC500V
AC230V AC400V AC440V AC600V
Rating Ie (A)
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
0016 0.1-0.16 100 100 100 100 100 100 100 100 100 100
0025 0.16-0.25 100 100 100 100 100 100 100 100 100 100
0040 0.25-0.4 100 100 100 100 100 100 100 100 100 100
0063 0.4-0.63 100 100 100 100 100 100 100 100 100 100
0100 0.63-1 100 100 100 100 100 100 100 100 100 100
0160 1-1.6 100 100 100 100 100 100 100 100 100 100
0250 1.6-2.5 100 100 100 100 100 100 100 100 3 2
0400 2.5-4 100 100 100 100 100 100 100 100 3 2
0630 4-6.3 100 100 100 100 50 38 50 38 3 2
1000 6.3-10 100 100 100 100 15 11 10 8 3 2
1300 9-13 100 100 50 38 10 8 6 5 3 2
MOG-H1
AC240V AC415V AC460V AC690V
AC500V
AC230V AC400V AC440V AC600V
Rating Ie (A)
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
0016 0.1-0.16 100 100 100 100 100 100 100 100 100 100
0025 0.16-0.25 100 100 100 100 100 100 100 100 100 100
0040 0.25-0.4 100 100 100 100 100 100 100 100 100 100
0063 0.4-0.63 100 100 100 100 100 100 100 100 100 100
0100 0.63-1 100 100 100 100 100 100 100 100 100 100
0160 1-1.6 100 100 100 100 100 100 100 100 100 100
0250 1.6-2.5 100 100 100 100 100 100 100 100 8 6
0400 2.5-4 100 100 100 100 100 100 100 100 8 6
0630 4-6.3 100 100 100 100 100 100 100 100 6 5
1000 6.3-10 100 100 100 100 50 38 50 38 6 5
1300 9-13 100 100 100 100 50 38 42 32 6 5
1600 11-16 100 100 50 38 35 27 10 8 4 3
2000 14-20 100 100 50 38 35 27 10 8 4 3
2500 19-25 100 100 50 38 35 27 10 8 4 3
3200 24-32 100 100 50 38 35 27 10 8 4 3
MOG-H2
AC240V AC415V AC460V AC690V
AC500V
AC230V AC400V AC440V AC600V
Rating Ie (A)
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
3200 24-32 100 100 50 38 35 27 10 8 5 4
4000 28-40 100 100 50 38 35 27 10 8 5 4
5000 35-50 100 100 50 38 35 27 10 8 5 4
6300 45-63 100 100 50 38 35 27 10 8 5 4
9
MOG-H1M
AC240V AC415V AC460V AC690V
AC500V
AC230V AC400V AC440V AC600V
Rating In (A)
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
0016 0.16 100 100 100 100 100 100 100 100 100 100
0025 0.25 100 100 100 100 100 100 100 100 100 100
0040 0.4 100 100 100 100 100 100 100 100 100 100
0063 0.63 100 100 100 100 100 100 100 100 100 100
0100 1 100 100 100 100 100 100 100 100 100 100
0160 1.6 100 100 100 100 100 100 100 100 100 100
0250 2.5 100 100 100 100 100 100 100 100 8 6
0400 4 100 100 100 100 100 100 100 100 8 6
0630 6.3 100 100 100 100 100 100 100 100 6 5
1000 10 100 100 100 100 50 38 50 38 6 5
1300 13 100 100 100 100 50 38 42 32 6 5
1600 16 100 100 50 38 35 27 10 8 4 3
2000 20 100 100 50 38 35 27 10 8 4 3
2500 25 100 100 50 38 35 27 10 8 4 3
3200 32 100 100 50 38 35 27 10 8 4 3
MOG-H2M
AC240V AC415V AC460V AC690V
AC500V
AC230V AC400V AC440V AC600V
Rating In (A)
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
3200 32 100 100 50 38 35 27 10 8 5 4
4000 40 100 100 50 38 35 27 10 8 5 4
5000 50 100 100 50 38 35 27 10 8 5 4
6300 63 100 100 50 38 35 27 10 8 5 4
10
Selection Chart : Fuseless Protection for
DOL starter feeders with MPCB
The selection
l is valid only for complete L&T combinations i.e. MPCB + Relay + Contactor
In any
l case if this combination is changed to accommodate another brand / rating of MPCB etc.
it shall be the responsibility of the person making such a change to assure type 2 performance
Selection is for normal starting conditions with starting time
l
Motor Rating: 3φ
, 415V, 50Hz Contactor Overload Relay MPCB (Only Magnetic)
Sr No.
hp kW IL Type Type Range (A) Type Rating IM (A)
11
IT Characteristics
1000
1000
3-poles from
cold state 3-poles from
cold state
100
100
2-poles from
Average Tripping Time (s)
10
10
Instantaneous tripping
characteristic is set at Instantaneous tripping
1300% of the maximum characteristic is set at
current setting 1300% of the maximum
3-poles from current setting
1 hot state 3-poles from
1 hot state
0.1
0.1
0.01
0.01
0.001
1 10 100 0.001
1 10 100
Multiples of current setting x Ie[A]
Multiples of current setting x Ie[A]
1000
3-poles from
cold state
100
2-poles from
Average Tripping Time (s)
cold state
10
Instantaneous tripping
characteristic is set at
1300% of the maximum
current setting
3-poles from
1 hot state
0.1
0.01
0.001
1 10 100
Multiples of current setting x Ie[A]
12
IT Characteristics
1000
100
Tripping Time (s)
10
Instabtabeous tripping
characteristic is set at
1100 ~ 1560% of the
rated current
0.1
0.01
0.001
1 10 100
Multiples of rated current x In[A]
1000
100
Tripping Time (s)
10
Instabtabeous tripping
characteristic is set at
1100 ~ 1560% of the
rated current
0.1
0.01
0.001
1 10 100
Multiples of rated current x In[A]
13
Overall Dimensions
Type MOG-S1
45
Ø 4.6
14.3 14.3 2- 71 2-M4
1 L1 3 L2 3 L3 6-M4
1- 1- 2- 2-
27
27
6
24
32 28
13.5
13
105
105
116
90
95
45
75
27
5.5
2 T1 4 T2 6 T3
10 45
14.3 62.3 3.7 14.3
Type MOG-H1
45
.6 2-M4
14.3 14.3 Ø4 91
2-
1 L1 3 L2 5 L3
1- 1- 2- 2- 6-M4
27
24
3.3
32 28
105
105
116
75
90
45
95
27
5.5
2 T1 4 T2 6 T3
45
10
14.3 75.3 3.7 14.3
Type MOG-H2
107.8
55 92.3
16.5 16.5 88.3
4.5
1 L1 3 L2 5 L3 6 - M6
1- 1- 2- 2-
33.8
5.5
45
63 55
16.3
45
110
110
120
19
66
84
33.8
2 T1 4 T2 6 T3
5
4.2 42
42
14
Overall Dimensions
Type MOG-H1M
45
1 L1 3 L2 5 L3
1- 1- 2- 2- 6-M4
27
3.3
105
105
116
90
75
45
95
27
5.5
2 T1 4 T2 6 T3
45
10
14.3 75.3 3.7 14.3
Type MOG-H2M
107.8
55 92.3
16.5 16.5 88.3
4.5
1 L1 3 L2 5 L3 6 - M6
1- 1- 2- 2-
33.8
5.5
16.3
45
110
110
120
19
66
84
33.8
2 T1 4 T2 6 T3
5
4.2 42
42
15
Overall Dimensions
21.5 10.5
MOG-TAFINO
27
16.7
5.8 28
I>
38.8
MOG-TAFINC
25
1.5
26
3.5
48.7
35.7
9 2.8
18.7
Trip indication
2.3
(reset by hand)
M3.5
5.2
MOG-FALICO
87
85
47.2
53.6
11.8
14.8
70.4
45
90
86
88
I>
6
3.4
16
Overall Dimensions
66
MMS A 66~216
T IP ON
SE TR
RE 4-Ø3.5
66
3.3
MMS 8
O FF
ø2
52.6±0.2
MMS
(16)
3.7 52.6±0.2
45
5.5 1
1.5~5 X 2
4.2
OFF
(Ø4~Ø8) 3
68
75
21.5
MOG-AXFINO
10.5
13(23)
16.7
5.8 14(24)
I>
38.8
MOG-AXFINC
11(21)
1
12(22)
18.9 8.5
I>
17
Overall Dimensions
66
48.7
9 2.8 35.7
M3.5 18.7
2.3
Indication window
5.2
1
MOG-KTL2NO
73
47.2
53.6
11.8
14.8
70.4
77
45
90
78
I 74
3.4
66
48.7
35.7
9 2.8
18.7
M3.5 Left side Right side
2.3
47.2
14.8
53.6
11.8
70.4
45
90
1
5.2
3.4
18
Electrical Standard Products (ESP) Branch Offices:
REGISTERED OFFICE AND L&T House, Group MIG - 5 Plot No. 518
HEAD OFFICE Padmanabhpur 4th Main Road
L&T House, Ballard Estate Durg 491 001 K. K. Nagar
P. O. Box 278 Tel: 0788-2213833 / 14 / 28 / 29 Madurai 625 020
Mumbai 400 001 Fax: 0788-2213820 Tel: 0452-2537404, 2521068
Tel: 022-6752 5656 Fax: 0452-2537552
Fax: 022-6752 5858 A1/11, Astronauts Avenue e-mail: [email protected]
Website: www.Larsentoubro.com Bidhan Nagar
Durgapur 713 212 EBG North Wing Office - 2
Tel: 0343-2536891 / 8952 / 7844 Powai Campus
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 0343-2536493 Mumbai 400 072
501, Sakar Complex I e-mail: [email protected] Tel: 022-67052874 / 2737 / 1156
Opp. Gandhigram Rly. Station Fax: 022-67051112
Ashram Road Milanpur Road, Bamuni Maidan e-mail: [email protected]
Ahmedabad 380 009 Guwahati 781 021
Tel: 079-66304007-11 Tel: 0361-2651297 #12, Shivaji Nagar
Fax: 079-26580491 / 66304025 Fax: 0361-2551308 North Ambazari Road
e-mail: [email protected] e-mail: [email protected] Nagpur 440 010
Tel: 0712- 2260012 / 3
38, Cubbon Road, Post Box 5098 II Floor, Vasantha Chambers Fax: 0712- 2260020 / 30
Bangalore 560 001 5-10- 173, Fateh Maidan Road e-mail: [email protected]
Tel: 080-25020100, 25593613 Hyderabad 500004
Fax: 080-25580525 Tel: 040-66720250 32, Shivaji Marg
e-mail: [email protected] Fax: 040-23296468 P. O. Box 6223
e-mail: [email protected] New Delhi 110 015
Tel: 011-41419514 / 5 / 6
131/1, Zone II
Fax: 011-41419600
Maharana Pratap Nagar D-24, Prithvi Raj Road, C-Scheme
e-mail: [email protected]
Bhopal 462 011 Jaipur 302 001
Tel: 0755-4098706 / 7 / 8 / 9 Tel: 0141-2385916 / 8
L&T House
Fax: 0755-2769264 Fax: 0141-2373280 P. O. Box 119
e-mail: [email protected] e-mail: [email protected] 191/1, Dhole Patil Road
Pune 411 001
Plot No. 559, Annapurna Complex Akashdeep Plaza, 2nd Floor Tel: 020-26135048
Lewis Road P. O. Golmuri Fax: 020-26124910, 26135048
Bhubaneswar 751 014 Jamshedpur 831 003 e-mail: [email protected]
Tel: 0674-6451342, 2436696 Jharkhand
Fax: 0674-2537309 Tel: 0657-2340864 / 387 3rd Floor
e-mail: [email protected] Fax: 0657-2341250 Vishwakarma Chambers
e-mail: [email protected] Majura Gate, Ring Road
SCO 32, Sector 26-D Surat 395 002
Madhya Marg, P. O. Box 14 Skybright Bldg. M. G. Road Tel: 0261-2473726
Chandigarh 160 026 Ravipuram Junction, Ernakulam Fax: 0261-2477078
Tel: 0172-4646841 to 7 Kochi 682 016 e-mail: [email protected]
Fax: 0172-4646802 Tel: 0484-4409420 / 4 / 5 / 7
e-mail: [email protected] Fax: 0484-4409426 Radhadaya Complex
e-mail: [email protected] Old Padra Road
10, Club House Road Near Charotar Society
Chennai 600 002 3-B, Shakespeare Sarani Vadodara 390 015
Tel: 044-28462072 / 4 / 5 / 2109 Kolkata 700 071 Tel: 0265- 2311744 / 6613610 / 1 / 2
Fax: 044-28462102 / 3 Tel: 033-44002572 / 3 / 4 Fax: 0265-2336184
e-mail: [email protected] Fax: 033-22822589 e-mail: [email protected]
e-mail: [email protected]
67, Appuswamy Road 48-8-16, Dwarakanagar
Post Bag 7156 A28,Indira Nagar, Faizabad Road Visakhapatnam 530 016
Opp. Nirmala College Uttar Pradesh, Tel: 0891-6620411-2 / 3
Coimbatore 641 045 Lucknow 226 016 Fax: 0891-6620416
Tel: 0422-2588120 / 1 / 5 Tel: 0522-2312904 / 5 / 6 e-mail: [email protected]
Fax: 0422-2588148 Fax: 0522-2311671
e-mail: [email protected] e-mail: [email protected]
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
SP 50455 R1 110210