Building Fire Alarm System
Building Fire Alarm System
Revision 1
Applicability All
Document Type Guidelines
Debkumar
Lahiri / Nitin Haresh
1 30-Dec-2013 Revised to incorporate LL points Nitin De
Dighe / Sharma
S.Gurumurthy
Debkumar
Yashwant Lahiri / Nitin Haresh
0 18-Dec-2011 Original issue
Sonar Dighe / Sharma
S.Gurumurthy
Page 1 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
CONTENTS
2.0 SCOPE............................................................................................ 3
3.2 Acronyms........................................................................................... 3
9.0 APPENDICES....................................................................................16
Page 2 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
1.0 PURPOSE
The purpose of this design guide is to outline minimum requirements that need to be
considered for developing the specification and evaluating the offers for Fire and Gas
Detection System for Buildings considered in EPC onshore oil & gas projects. A typical
content list is presented in this document. Detailed description of each section is not
provided in this document. Document in reference list should be referred as a detailed
guide on relevant sections of the Philosophy.
2.0 SCOPE
This design guide applies to all Petrofac onshore oil & gas projects for preparing
specifications and for the technical evaluation of Fire and Gas Detection System for
Buildings. This design guide is to be adopted for EPC projects in absence of any project
specific philosophy. The recommended contents of this document may be suitably
modified as per project requirement.
This specification defines the minimum requirements for the design, engineering,
installation and commissioning of UL/ FM/ VDs approved Fire & Gas Detection System for
buildings used in onshore hydrocarbon plants.
This specification describes the field detection and actuating equipment for the Fire & Gas
Detection system, and the functionality of the system as a whole. The fire detection and
alarm system covered here shall facilitate early warning alarm to alert the Fire stations/
Local Control Room of the plant/ workshop complex about the out-break of fire so that a
timely action is initiated to prevent/mitigate loss of life and property.
Approval date
3.0 DEFINITIONS
3.1 Definition
Not applicable
3.2 Acronyms
Page 3 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
4.0 REFERENCES
This design guide has been constructed by referencing experience on various projects in
which such Systems have been implemented.
The system and its components shall conform to the latest editions of the UL/FM/VdS
standards and relevant stipulations of NFPA & IS Codes as applicable. Installation shall be
done as per relevant NFPA standards.
Not applicable
6.0 DESCRIPTION
A brief and structured guide line is presented below which addresses features of F&G
Detection system along with the inert gas flooding and with suitable interface to DCS /PLC
and PAGA system and Fire Station.
In hydrocarbon industries, the buildings are exposed to internal and external hazards risks.
The building fire alarm system is required to address the risk associated
Page 4 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
with imminent or established fire and leakage of combustible/ toxic gas. The F&G system
is meant for early detection of fire or gas leakage. In event of early detection, some time
is made available for automatically initiating actions to prevent outbreak of fire.
In most of the buildings, the Fire protections are provided against electrical fire likely to
occur due to short circuit in electrical systems or cable fault/fire. Most of the cable fires
are usually associated with the large generation of smoke. Hence sensing smoke at early
stage can prevent fire from occurring. To sense smoke, the smoke detectors are provided
in cable ducts, false flooring and false ceiling of the control buildings. For reliable
detection, the two types of detectors such as ionization type (suitable for incipient stage
of fire) and optical type (suitable for smoldering stage of fire) are employed in cross zone.
To check presence of actual flame (suitable for third stage of fire when ignition
temperature has reached), the flame detectors such as UV/IR or IR type or Multi-spectrum
IR type are employed.
To check the rise in temperature (suitable for last & fourth stage of fire when heat is
released) in surrounding area, rate of rise type (bimetallic or thermo-electric sensors) or
absolute fixed type (bimetallic or fusible link devices) thermal detectors are employed.
The hydrocarbon or toxic gas detectors are employed in buildings for protection of assets
and human beings. The detectors are installed in inlet of Air handling unit. In event of
high level of hydrocarbon or toxic gases, the inlet dampers are closed automatically with
suitable pre-warning. In event of presence of toxic gases, separate purifying unit, if
installed at the inlet, may be started for reducing the toxic content.
Hydrogen detectors are usually used in the electrical battery room to detect any leakage
of hydrogen gas from the batteries.
If inert gas flooding is used for fire suppression, then oxygen monitors are employed inside
the building to detect the presence of sufficient oxygen for operators to enter the building
again after release of inert gas.
Page 5 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
These items are used at pre-fixed locations and at predefined intervals as per the
applicable codes and standards. An observer can initiate fire/gas alarm and executive
actions by initiating a command through BGU/MCP contact input.
Addressable detectors allow automatic identification of the detector that has initiated the
action, and in-turn allows automatic diagnostic alarms and online replacement of
detectors.
Such detectors are connected to controller unit through redundant bus or through ring
network. Only after confirmation of through voting logic, the alarm or any executive
action is initiated.
This kind of system is expandable and it is possible to add additional F&G zones, if
required.
The fault in a loop or a zone shall not affect the function of the other loops or detection
by other groups. Also, removal of detectors shall not break a loop.
The building shall be divided into separate zones and executive actions on HVAC and any
other device shall be accordingly segregated and designed.
The F&G systems are generally powered from redundant UPS supply. As per NFPA
guidelines, the F&G system is also powered from dedicated dual back-up batteries, which
will provide stable supply, allowing orderly shutdown and monitoring if power is lost. For
sizing of the batteries, consider requirement of installed spares & spare space in F&G
system 'Control Devices'. The back-up battery capacity allows continued monitoring by the
F&G system for a nominal period of not less than 24 hours. This period is to be confirmed
by the project requirements/applicable codes and standards followed for project risk
assessments. A common power supply fault alarm is provided for connection to DCS.
Contacts are generally volt free contacts.
6.1.9 Calibrators
Kits of Calibration gases in bottles, aerosols or cans, smoke detector test gas, Heat
detector tester etc. are required for commissioning of the system and for future
Page 6 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
maintenance. The number of bottles or cans is decided based on the actual number of
detectors and the calibration frequency as per the project requirements and the
applicable codes.
a) Interfaces to the actuating devices such as deluge valves, pneumatic solenoid and
pilot valves, extinguisher release.
b) Interfaces to other Systems of the plant such as HVAC System, Plant F&G System,
Plant ESD System, DCS, Package Equipment (such as Gas Turbines, Process gas
Compressors etc. which may be housed with noise-hood / enclosures) F&G
Detection System, PAGA System, Emergency Power Generator.
Automatic release of inert gas is initiated after confirmed fire detection. The choice of
inert gas depends upon type of assets to be protected and also on the project
requirement/site environmental policy on inert gas mixture. Most of the inert gas mixtures
work on principle of reducing oxygen in affected area and there by extinguishing fire.
Hence before release of the inert gas, the persons in the affected rooms are evacuated by
pre-warning through use of timer, signboards, and audio-visual alarms. Interlocks are
implemented with Security Access system to ensure that nobody is trapped inside the
building and gets suffocated during the release of the inert gas.
All detectors are located and spaced in accordance with NFPA Code 72 E/BS 5839/other
applicable Codes/Local regulations. The selection and combination of detectors is done on
the basis of overall safety and reliability of the system, keeping in view 100% coverage
area by each detector. Further, the selection of type of detectors and their locations and
mountings are based on their ability to ensure the earliest response to imminent or
established fire or leakage of hydrocarbon / toxic (H2S) gases, with consideration to the
following as a minimum:
Page 7 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
For the purpose of selecting gas detectors, following general factors are considered
Combustible Gas (HC) & Flammable gas (H2) Detectors shall be able to perform to
the temperature, humidity, air velocity and vibration specification prescribed in
ISA 12.13.01. Toxic Gas (H2S) Detectors shall be able to perform to the
specifications prescribed in ISA 92.0.01 Part I.
Temperature Effects: The detectors shall be calibrated at their mean operating
temperature. All components, including the sensor, shall be designed for operation
within the ambient temperature range for the location of the installation. Where
high temperatures are unavoidable, high-temperature rated detectors with remote
sensing heads shall be employed.
Effects of Humidity: The detector housing shall be suitable for corrosive
environment.
Air Velocity: Sensors shall be located away from prevailing winds, heating and
cooling system. Air circulation patterns and effects of other equipment that affect
circulation shall be taken into consideration while finalizing the location of the
detectors. Where widely varying wind direction changes are expected, multiple
detectors shall be installed to provide the required cover.
Vibration: Sensors shall be located away from vibration prone areas. If this is not
possible, the sensors shall be mounted on flexible mounts or flexible conduit.
Sensors shall be typically located approximately 1 m from the expected emission
point, and preferably in the direction of ignition sources and / or populated areas.
Special consideration shall be given to the properties of the process gas (refer
Process Design Criteria for properties of process fluids), specifically its vapor
density and predominant component. For lighter-than-air gases, the detectors shall
be placed above the probable leakage point. For heavier-than-air gases, the
detectors shall be placed 300-450 mm above the grade.
Detector locations shall take into account the possible flow pattern of the leaking
gas or vapor and ventilation system airflow.
The number of detectors shall be based on the number of potential leakage
sources.
Perimeter detection of leakages shall be considered in areas containing large
amounts of light hydrocarbons (e. g. process areas or pressure storage areas) to
alert operations to initiate a manual response or to actuate an automatic response
(e. g. unit shutdown or firewater spray system). These detectors shall be installed
along a unit boundary adjacent to an ignition source.
Page 8 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
Indoor or partially enclosed installations that may require gas detection (such as
turbine enclosures, compressor stations, etc.) shall be protected with open path or
point detection system.
The fire detection system comprises a variety of addressable fire detection devices and
sensors, including addressable Optical Flame Detectors, Smoke Detectors, Thermal
Detectors and Manual Call Points. These detectors are installed in combinations to
increase the reliability.
Optical flame detectors are the UV/IR or IR or Multi-spectrum/Triple IR type and make use
of such sensor, filters, and / or design to reject phenomena such as electric arcs, heaters,
artificial light sources, lightning and are completely "solar blind".
The detectors are able to detect all types of flaming fires. The flame detector shall be
selected taking in to consideration the fuel source and the cone of vision of the selected
detector to ensure adequate coverage of the potential hazard.
UV detectors may be used where they are not exposed to external UV rays, such as in
compressors and power generating enclosures. Detectors are powered from 24 VDC, with a
4-20 mA signal loop to cover the calibrated range. Detector faults are signaled by a 4 mA
signal. Sufficient margin are allowed between fault, normal and alarm levels to minimize
spurious alarms.
The system uses addressable type of UL/FM/VDS listed automatic wired Photoelectric &
Ionization Smoke detectors, which are installed in all the manned rooms and corridors,
including concealed floor and ceiling voids.
Addressable Ionization smoke detectors are used in general-purpose areas to provide early
response to smoldering or flaming fires in their incipient stages. A detector base is
provided for connecting the individual detectors to the F&G system so that detector can
be removed without removing any wiring.
Page 9 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
Addressable Photoelectric smoke detectors are used in electric equipment and control
room areas. It shall be possible to reset all detectors from panel after fault signal has
been indicated.
Two independent smoke detector loops are installed in each area where executive action
is required on detection of fire for reliability.
Detectors, which are not visible, such as in ceiling void or under floor, are provided with
remote LED's located in the room being monitored.
The smoke detectors incorporate an integral LED indicator for confirmation that the unit is
active. A detector base is provided for connecting the individual detectors to the F&G
system.
Smoke detectors remain in alarm state until reset by the F&G system. It is possible to
reset all detectors from panel after fault signal has been indicated.
Disconnection of one or more Smoke detectors in a transmission path shall not impair the
operation of the remaining Smoke detectors and the transmission path. Either wiring break
or short circuit is automatically indicated by audio-visual warning in the form of fault
alarm. Isolators are provided for protection against short circuits.
The sensitivity of the detector is not to vary with any change in ambient temperature,
humidity or voltage variations. The detectors will have in-built arrangement such that puff
of smoke or hot air pockets shall not trigger the alarm. The detector shall be able to sense
incipient fire by detecting the presence of visible and invisible products of combustion like
wood, paper, cloth, PVC, Bakelite nylon foam, acrylic thermocol, photo film, nylon,
polyester, painted sheets, Teflon leather etc. The detector performance shall not be
affected by an air current of 5 m/sec. Where air velocity is expected to be higher, smoke
guard/ baffle shall be used. The detector shall be protected against dust accumulation/
ingress.
Smoke detectors may require separate power supply (e.g. separate 24 V DC). In such a
case, the power distribution and power source for these detectors to be considered. Such
power supply shall be arranged from the power supply which feeds the building Fire and
Gas system so that it meets the uninterrupted power supply requirement.
Intrinsically Safe smoke detectors may be used for the battery room applications.
Sometimes project specification require smoke detector with in-built relay contacts. For
such cases IS certification for the ‘detector + base (relay)’ to be mandatorily verified
before procurement. Following shall be checked:
Page 10 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
ii. The certification is valid for the area where these detectors are intended to be
installed.
iii. System interface: If IS certified smoke detectors including base (relay)’ is not
available, addressable Intrinsically Safe certified smoke detectors can be used in
battery rooms, which can be interfaced with the Fire Alarm panel. This eliminates
the requirement of relay contacts in-built in the Smoke Detector base.
Thermal detectors are used in all indoor spaces including all rooms and equipment
enclosures, including concealed floor and ceiling voids.
Rate of rise thermal detectors are used where an early warning of smoldering fires is
required, such as storerooms and equipment rooms where air flow or high humidity may
inhibit the response of smoke detectors.
Fixed temperature or rate compensated type heat detectors shall be used within areas
unsuitable for smoke detection where a rapidly achieved high temperature can be
expected, such as machinery rooms or equipment enclosures. These are set at
approximately 12o C above maximum ambient temperature within the area.
Thermal detectors remain in alarm state until reset by the F&G system.
All visible detectors incorporate an LED indicator as an integral part of the detector head
or its mounting base. Concealed thermal detectors are provided with an LED "repeater"
that is located in a visible location. Normally, unmanned equipment rooms or offices have
indicators in the corridor. The detector circuitry cause the LED to remain illuminated
while the detector is in the alarm condition.
Manual Call Points are provided to alarm and initiate the F&G deluge. These are laid out
and segregated according to the fire zones. MCPs are installed at strategic locations all
over the building to initiate F&G actions and ESD.
MCP is provided with current limiting resistances permanently fitted inside the unit and
not wired on the terminals provided for field wiring.
All MCPs may require a double action to activate the alarm. They may be the break-glass,
pushbutton type with protection (lid/cover) for accidental actuation.
Each unit is surface mounted at a height of 1.4 meters and is provided with a striker
connected to the station by a chain.
Page 11 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
Each unit is wired to the F&G system in the Control Room. The MCP is provided with test
key to test functionality without breaking the glass.
The operation of MCP causes the change in the loop current to be detected by the F&G
system. All MCP are Epoxy Red in color. All MCP confirm to specifications and tests as
specified in BS 5839:Part-II
The Fire & Gas detection system panel is independent of DCS/Process PLC and constitutes
the following:
Gas detector Controller/Monitor Cards, Logic & auxiliary relays, power distribution
scheme, hooter mounted on a separate panel in safe area.
Hooter is provided for alarms only.
The front panel mounted Gas/Fire detection controllers/ monitors are installed in
mating cases or mounting bins recommended and supplied by the manufacturer for
panel mounting. All wiring to these controllers are terminated on terminal blocks
and/or multi-pin connectors provided as an integral part of the case. Routine
calibration adjustments are accessible from the front of the panel without having
to remove any wiring or causing loss of the instrument function. In addition, total
removal of the instrument and replacement with a spare is possible from the front
of the panel.
The modules are plug-in type permitting the removal of the modules without
disturbing the system wiring. Each module has a maximum of 4 channels (one
detector per channel) per modules. Gas/Fire circuit are so designed that any
channel can be put out of service for repair, without affecting the other.
Page 12 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
Besides PLC/Logic Processor related cabinets, other main components of Fire & Gas
Detection system panel shall be:
Critical Annunciator Panel: Annunciator Panel is provided for critical alarms. The
annunciation sequences are as per ISA-S18.1, 'Annunciator sequences and
specifications'. The annunciation lamps are capable of removal and replacement
from the panel front via individual snap out windows or a swing out hinged door on
which all windows are mounted. Minimum critical alarms to be provided are given
below:
a) Line monitoring fault
b) Gas detection malfunction
c) Fire detection malfunction
d) Fire Water Pump common alarm
e) Fire Water Pump - Start
f) Fire Water Pump - Failed to Start
g) Fire Water Pump - Shutdown
h) Fire Water Pump - on Manual
i) Fire water header Pressure- Low
j) Diesel Generator- Running
k) Diesel Generator- Fault
l) Gas Fault- Compressor
m) Instrument Air Pressure- Low Low
n) F&G System
o) ESD
p) Confirmed H2S detection
q) Confirmed HC-H2 detection
r) Confirmed Fire detection
Matrix Panel: Matrix panel provide graphic status of Fire & Gas Detection system &
Fire suppression system area-wise for the entire plant/building.
h) Heat
i) Smoke
j) Manual Alarm Call point- Fire Alarm
k) Extinguisher- Released
l) Deluge- Valve open
m) Deluge- Valve closed
n) Deluge- Pressure Low
o) System Fault
Fire & Gas detection system panel are interfaced with the following systems of the plant
to confirm to SAFE chart requirements:
The Cause and Effect diagrams are prepared as per standards mentioned together with the
project requirements of specification.
All shutdown interlock and alarm circuits are designed to operate in a fail-safe mode.
6.6.1 Alarms
In addition to signaling on the F&G matrix and alarm annunciator, fire and gas
detection shall result in separate and distinct audible and visual alarms at Control
room/equipment enclosure/field area.
Visual alarms shall be color coded to the project requirements to distinguish
between fire, combustible gas and toxic gas leakage.
For gas detection, distinct visual and audible alarms in the Control room shall be
provided for the two levels of detection.
Silencing of audible alarms shall not de-activate visual alarms until detection falls
below the alarm level.
Visual and audible alarms are different for each level of detection.
F&G Detection system are suitably interfaced with plant DCS. DCS have an over
view graphic for each F&G zone. The graphic displays individual detector analogue
value, alarm and fault status, and deluge valve and extinguisher release status. A
separate graphic displays the fire water pumps run and fault status and fire water
pressure.
6.6.2 Paging
Distinct plant audio-alarm is provided for confirmed HC-H2 gas leakage, confirmed H2S gas
leakage, confirmed fire through paging system. Dry volt free contacts shall be provided for
the input signals.
6.6.3 Actuation
7.0 RECORDS
Not applicable
Page 15 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014
Document Number Document Title Revision
8.0 FLOWCHART
Not applicable
9.0 APPENDICES
Not applicable
Page 16 of 16
This document is an uncontrolled copy when printed or saved. Viewed by:
Santhosh Chandrasekaran 03-Jul-2014