DSE335 Operators Manual PDF
DSE335 Operators Manual PDF
057-233 ISSUE: 1
DSE335 Operator Manual
E-mail: [email protected]
Website: www.deepseaplc.com
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.
Amendments List
Minimum
Minimum Module
Issue Comments Configuration Suite
Version Required
Version Required
1 Initial release V4.2.22 2014.101 V1.212.3
2 Updates to Breaker Scheme C
Typeface: The typeface used in this document is Arial. Care must be taken not to mistake the upper
case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
TABLE OF CONTENTS
SECTION PAGE
1 INTRODUCTION .................................................................................................. 6
1.1 BIBLIOGRAPHY ................................................................................................................. 7
1.1.1 INSTALLATION INSTRUCTIONS ................................................................................. 7
1.1.2 TRAINING GUIDES...................................................................................................... 7
1.1.3 MANUALS .................................................................................................................... 7
1.1.4 THIRD PARTY DOCUMENTS ...................................................................................... 7
2 SPECIFICATIONS ............................................................................................... 8
2.1 SHORT NAMES .................................................................................................................. 8
2.2 REQUIREMENTS FOR UL CERTIFICATION ...................................................................... 8
2.3 TERMINAL SPECIFICATION .............................................................................................. 9
2.4 POWER SUPPLY REQUIREMENTS................................................................................... 9
2.4.1 MODULE SUPPLY INSTRUMENTATION DISPLAY ..................................................... 9
2.5 S1 & S2 VOLTAGE / FREQUENCY SENSING................................................................. 10
2.6 CURRENT SENSING ........................................................................................................ 10
2.6.1 V A RATING OF THE CTS ......................................................................................... 11
2.6.2 CT POLARITY ............................................................................................................ 12
2.6.3 CT PHASING ............................................................................................................. 12
2.6.4 CT CLASS.................................................................................................................. 12
2.7 INPUTS............................................................................................................................. 13
2.7.1 DIGITAL INPUTS ....................................................................................................... 13
2.8 OUTPUTS ......................................................................................................................... 13
2.8.1 CONFIGURABLE OUTPUTS A & E ............................................................................ 13
2.8.2 CONFIGURABLE OUTPUTS B & F ............................................................................ 13
2.8.3 CONFIGURABLE OUTPUTS C & D ........................................................................... 13
2.8.4 CONFIGURABLE OUTPUTS G, H, I, J, K & L............................................................. 13
2.9 COMMUNICATION PORTS .............................................................................................. 14
2.9.1 COMMUNICATION PORT USAGE ............................................................................ 15
2.9.1.1 USB CONNECTION ............................................................................................ 15
2.9.1.2 RS232 ................................................................................................................. 16
2.9.1.3 RECOMMENDED PC RS232 SERIAL PORT ADD-ONS ..................................... 16
2.9.1.4 RECOMMENDED EXTERNAL MODEMS ............................................................ 17
2.9.1.5 RS485 ................................................................................................................. 18
2.9.1.6 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS ..................................... 18
2.9.2 DSENET® FOR EXPANSION MODULES ................................................................. 19
2.10 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION ...................................... 19
2.11 DIMENSIONS AND MOUNTING .................................................................................... 20
2.11.1 DIMENSIONS............................................................................................................. 20
2.11.2 PANEL CUTOUT ........................................................................................................ 20
2.11.3 WEIGHT..................................................................................................................... 20
2.11.4 FIXING CLIPS ............................................................................................................ 21
2.11.5 CABLE TIE FIXING POINTS ...................................................................................... 22
2.11.6 SILICON SEALING GASKET...................................................................................... 22
2.11.8 APPLICABLE STANDARDS ....................................................................................... 23
2.11.9 ENCLOSURE CLASSIFICATIONS ............................................................................. 25
2.11.9.1 IP CLASSIFICATIONS......................................................................................... 25
2.11.9.2 NEMA CLASSIFICATIONS .................................................................................. 26
3 INSTALLATION ................................................................................................. 27
3.1 TERMINAL DESCRIPTION ............................................................................................... 27
3.1.1 DC SUPPLY, OUTPUTS G-L...................................................................................... 28
3.1.2 CONFIGURABLE DIGITAL INPUTS A-I...................................................................... 28
3.1.3 CONFIGURABLE DIGITAL INPUTS J-L, DSENET ..................................................... 29
3.1.4 CONFIGURABLE VOLT-FREE OUTPUTS E & F........................................................ 29
3.1.5 LOAD SWITCHING AND S2 VOLTAGE SENSING ..................................................... 29
3.1.6 S1 VOLTAGE SENSING ............................................................................................ 30
1 INTRODUCTION
This document details the installation and operation requirements of the DSE335 module version 4.2
and later, part of the DSEATS® range of products.
A separate document covers the DSE335 modules with firmware version prior to version 4.2.
The manual forms part of the product and must be kept for the entire life of the product. If the product
is passed or supplied to another party, ensure that this document is passed to them for reference
purposes.
This is not a controlled document. Updates are not automatically informed. Any future updates of this
document are included on the DSE website at www.deepseaplc.com
The module is designed to provide differing levels of functionality across a common platform. This
allows the OEM greater flexibility in the choice of controller to use for a specific application.
The module has been designed to allow the operator to control the transfer of the load from Source 1
(S1) to Source 2 (S2), typically the mains supply and a standby generator either manually (via fascia
mounted push-buttons) or automatically upon S1 failure. Additionally if configured too, the module
automatically starts and stops the generator set (S2) depending upon the status of S1.
The user also has the facility to view the system operating parameters via the LCD display to monitor
the supplies and indicating the operational status and fault conditions of the module.
The powerful ARM microprocessor contained within the module allows for incorporation of a range of
complex features:
Using a PC and the DSE Configuration Suite software allows alteration of selected operational
sequences, timers, alarms and operational sequences. Additionally, the module’s integral front panel
configuration editor allows adjustment of this information.
A robust plastic case designed for front panel mounting houses the module. Connections are via
locking plug and sockets.
Access to critical operational sequences and timers for use by qualified engineers, can be protected
by a security code. Module access can also be protected by PIN code. Selected parameters can be
changed from the module’s front panel.
The module is housed in a robust plastic case suitable for panel mounting. Connections to the module
are via locking plug and sockets.
1.1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications are obtained from the
DSE website: www.deepseaplc.com
Installation instructions are supplied with the product in the box and are intended as a ‘quick start’
guide only.
Training Guides are produced to give ‘handout’ sheets on specific subjects during training sessions.
1.1.3 MANUALS
Product manuals are are downloaded from the DSE website: www.deepseaplc.com.
Reference Description
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device
ISBN 1-55937-879-4 Function Numbers and Contact Designations. Institute of Electrical and
Electronics Engineers Inc
ISBN 0-7506-1147-2 Diesel generator handbook. L.L.J.Mahon
ISBN 0-9625949-3-8 On-Site Power Generation. EGSA Education Committee.
2 SPECIFICATIONS
2.1 SHORT NAMES
Short Name Description
DSE3xx All modules/controllers in the DSEATS range
DSE335 DSE335 module/controller
Description Specification
Screw Terminal
• 4.5 lb-in (0.5 Nm)
Tightening Torque
• Terminals suitable for connection of conductor size 12 AWG to 26 AWG
(0.5 mm² to 2.0 mm²).
• Conductor protection must be provided in accordance with NFPA 70,
Article 240
Conductors • Low voltage circuits (35 V or less) must be supplied from the engine
starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors
shall be separated and secured to maintain at least ¼ ” (6 mm) separation
from the generator and mains connected circuit conductors unless all
conductors are rated 600 V or greater.
• Must be connected through UL Listed or Recognized isolating current
Current Inputs
transformers with the secondary rating of 5 A maximum.
Communication
• Must be connected to communication circuits of UL Listed equipment
Circuits
Output Pilot Duty • 0.5 A
• Suitable for use in type 1 Enclosure Type rating with surrounding air
temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC)
• Suitable for pollution degree 3 environments when voltage sensing inputs
Mounting
do not exceed 300 V. When used to monitor voltages over 300 V, a
device is to be installed in an unventilated or filtered ventilation enclosure
to maintain a pollution degree 2 environment.
Operating
• -22 ºF to +158 ºF (-30 ºC to +70 ºC)
Temperature
Storage Temperature • -40 ºF to +176 ºF (-40 ºC to +80 ºC)
NOTE: For purchasing additional connector plugs from DSE, see the section entitled
Maintenance, Spares, Repair and Servicing elsewhere in this document.
Description Specification
Two part connector.
• Male part fitted to
module
Connection Type • Female part supplied in
module packing case -
Screw terminal, rising
clamp, no internal Example showing cable entry and screw
spring. terminals of a 10 way connector
Minimum Cable Size 0.5 mm² (AWG 24)
Maximum Cable Size 2.5 mm² (AWG 10)
Description Specification
0 V to 70 V DC
Range
Maximum continuous operating voltage of 35 V DC
Resolution 0.1 V
Accuracy 1% full scale (±0.7 V)
NOTE: Details for 4 mm² cables are shown for reference only. The connectors on the DSE
modules are only suitable for cables up to 2.5 mm².
The V A burden of the module on the CTs is 0.5 V A. However depending upon the type and length of
cabling between the CTs and the module, CTs with a greater V A rating than the module are required.
Example.
If 1.5 mm² cable is used and the
distance from the CT to the measuring
module is 20 m, then the burden of the
cable alone is approximately 15 V A.
As the burden of the DSE controller is
0.5 V A, then a CT with a rating of at
least 15 + 0.5 V = 15.5 V A must be
used.
If 2.5 mm² cables are used over the
same distance of 20 m, then the
burden of the cable on the CT is
approximately 7 V A. CT’s required in
this instance is at least 7.5 V A
(7 + 0.5).
2.6.2 CT POLARITY
NOTE: Take care to ensure correct polarity of the CT primary as shown above. If in doubt,
check with the CT supplier.
Take care to ensure the correct polarity of the CTs. Incorrect CT orientation leads to negative kW
readings when the set is supplying power. Take note that paper stick-on labels on CTs that show the
orientation are often incorrectly placed on the CT (!). It is more reliable to use the labelling in the case
moulding as an indicator to orientation (if available).
To test orientation, run the generator in island mode (not in parallel with any other supply) and load
the generator to around 10% of the set rating. Ensure the DSE module shows positive kW for all three
individual phase readings.
Labelled as Labelled as
p1, k or K p2, l or L
TO GENERATOR TO LIGHTS
POLARITY OF CT PRIMARY
2.6.3 CT PHASING
Take particular care that the CTs are connected to the correct phases. For instance, ensure that the
CT on phase 1 is connected to the terminal on the DSE module intended for connection to the CT for
phase 1.
Additionally ensure that the voltage sensing for phase 1 is actually connected to generator phase 1.
Incorrect connection of the phases as described above results in incorrect power factor (PF)
measurements, which in turn results in incorrect kW measurements.
One way to check for this is to make use of a single-phase load. Place the load on each phase in turn,
run the generator and ensure the kW value appears in the correct phase. For instance if the load is
connected to phase 3, ensure the kW figure appears in phase 3 display and not in the display for
phase 1 or 2.
2.6.4 CT CLASS
Ensure the correct CT type is chosen. For instance if the DSE module is providing overcurrent
protection, ensure the CT is capable of measuring the overload level required to be protected against,
and at the accuracy level required.
For instance, this may mean fitting a protection class CT (P10 type) to maintain high accuracy while
the CT is measuring overload currents.
Conversely, if the DSE module is using the CT for instrumentation only (current protection is disabled
or not fitted to the controller) then measurement class CTs can be used. Again, bear in mind the
accuracy required. The DSE module is accurate to better than 1% of the full-scale current reading. To
maintain this accuracy fit Class 0.5 or Class 1 CTs.
Check with the CT manufacturer for further advice on selecting the CTs.
2.7 INPUTS
Description Specification
12 Configurable negative or positive switching inputs in banks of 3
Number
through PC Software
Arrangement Contact between input terminal and the module’s plant supply
negative or positive terminal.
Low level threshold 3.2V minimum
High level threshold 8.1V maximum
Maximum input voltage +60V DC with respect to module’s plant supply negative terminal
Minimum input voltage -2V DC with respect to module’s plant supply negative terminal
Contact wetting current 7mA typical
Open circuit voltage 12V typical for negative activation.
0V typical for positive activation.
2.8 OUTPUTS
NOTE: Refer to Breaker Control Training Document (DSE part 056-022) for further details
on configuring and control different type of load switching devices.
Description Specification
Number 2
Type Fully configurable normally closed volt-free contacts.
Rating 8A resistive at 250V AC
Description Specification
Number 2
Type Fully configurable normally open volt-free contacts.
Rating 8A resistive at 250V AC
Description Specification
Number 2
Type Fully configurable volt-free changeover contacts.
Rating 8A resistive at 250V AC
Description Specification
Number 6
Type Fully configurable, supplied from DC positive terminal 2
Rating 2 A resistive continuous at 35 V
NOTE: The DC supply must be connected to the module for configuration by PC.
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Suite PC Software Manual.
The USB port is provided to give a simple means of connection between a PC and the controller.
Using the DSE Configuration Suite Software, the operator is then able to control the module, starting
or stopping the generator, selecting operating modes, etc.
Additionally, the various operating parameters (such as output volts, oil pressure, etc.) of the remote
generator are available to be viewed or changed.
• DSE335 Controller
2.9.1.2 RS232
The RS232 port on the controller supports the Modbus RTU protocol.
The Gencomm register table for the controller is available upon request from the DSE Technical
Support Department.
RS232 is for short distance communication (max 15m) and is typically used to connect the controller
to a telephone or GSM modem for more remote communications.
Many PCs are not fitted with an internal RS232 serial port. DSE DOES NOT recommend the use of
USB to RS232 convertors but can recommend PC add-ons to provide the computer with an RS232
port.
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
• Brainboxes VX-001 Express Card RS232 (for laptops and nettops PCs)
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: [email protected]
NB DSE Have no business tie to Brainboxes. Over many years, our own engineers have used these
products and are happy to recommend them.
NOTE: For GSM modems a SIM card is required, supplied by your GSM network
provider
• Sierra Fastrak Xtend GSM modem kit (PSU, Antenna and modem)*
DSE Part number 0830-001-01
• For SMS only, a ‘normal’ voice SIM card is required. This enables the controller to send SMS
messages to designated mobile phones upon status and alarm conditions.
• For a data connection to a PC running the DSE Configuration Suite software, a ‘special’ CSD
(Circuit Switched Data) SIM card is required in order for the modem to answer an incoming
data call. Many ‘pay as you go’ services do not provide a CSD (Circuit Switched Data) SIM
card.
2.9.1.5 RS485
NOTE: For a single module to PC connection and distances up to 6m (8yds) the USB
connection method is more suitable and provides for a lower cost alternative to RS485 (which
is more suited to longer distance connections).
The RS485 port on the series controller supports the Modbus RTU protocol.
The DSE Gencomm register table for the controller is available upon request from the DSE Technical
Support Department.
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices) and
allows for connection to PCs, PLCs and Building Management Systems (to name just a few devices).
One advantage of the RS485 interface is the large distance specification (1.2km when using Belden
9841 (or equivalent) cable. This allows for a large distance between the module and a PC running the
DSE Configuration Suite software. The operator is then able to control the module, selecting operating
modes, etc.
The various operating parameters (such as output volts, currents, etc.) of the remote ATS can be
viewed or changed.
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: [email protected]
NB DSE have no business tie to Brainboxes. Over many years,our own engineers have used these
products and are happy to recommend them.
NOTE: As a termination resistor is internally fitted to the host controller, the host
controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to the
‘last’ unit on the DSENet®. For connection details, you are referred to the section entitled
‘typical wiring diagram’ elsewhere in this document.
DSENet® is the interconnection cable between the host controller and the expansion module(s) and
must not be connect to any device other than DSE equipment designed for connection to the
DSENet®
Description Specification
Cable type Two core screened twisted pair
Cable characteristic 120Ω
impedance
Recommended cable Belden 9841
Belden 9271
Maximum cable length 1200m (¾ mile) when using Belden 9841 or direct equivalent.
600m (666 yds) when using Belden 9271 or direct equivalent.
DSENet® topology “Daisy Chain” Bus with no stubs (spurs)
DSENet® termination 120Ω. Fitted internally to host controller. Must be fitted externally to the
‘last’ expansion module by the customer.
Maximum expansion Total 6 devices made up of DSE2130 (up to 2), DSE2157 (up to 2),
modules DSE2548 (up to 2)
Example of configuration to achieve external sounder with external alarm mute button:
2.11.1 DIMENSIONS
220 mm x 160 mm
(8.7 ” x 6.3 ”)
2.11.3 WEIGHT
0.7 kg
(1.4 lb)
The module is held into the panel fascia using the supplied fixing clips.
• Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from
the clip.
• Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
• Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of
the clip are inside their allotted slots.
• Turn the fixing clip screws clockwise until they make contact with the panel fascia.
• Turn the screws a little more to secure the module into the panel fascia. Care must be taken
not to over tighten the fixing clip screws.
Fixing clip
Integral cable tie fixing points are included on the rear of the module’s case to aid wiring. This
additionally provides strain relief to the cable loom by removing the weight of the loom from the screw
connectors, thus reducing the chance of future connection failures.
Care is to be taken not to over tighten the cable tie (for instance with cable tie tools) to prevent the risk
of damage to the module case.
The supplied silicon gasket provides improved sealing between module and the panel fascia.
The gasket is fitted to the module before installation into the panel fascia.
Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal.
Sealing gasket
Gasket fitted
to module
Standard Description
BS 4884-1 This document conforms to BS4884-1 1992 Specification for presentation
of essential information.
BS 4884-2 This document conforms to BS4884-2 1993 Guide to content
BS 4884-3 This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068-2-1
-30 °C (-22 °F)
(Minimum temperature)
BS EN 60068-2-2
(Maximum temperature) +70 °C (158 °F)
BS EN 60950 Safety of information technology equipment, including electrical business
equipment
BS EN 61000-6-2 EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4 EMC Generic Emission Standard (Industrial)
BS EN 60529 IP65 (front of module when installed into the control panel with the
(Degrees of protection optional sealing gasket)
provided by enclosures) IP42 (front of module when installed into the control panel WITHOUT
being sealed to the panel)
UL508 12 (Front of module when installed into the control panel with the
NEMA rating supplied sealing gasket).
(Approximate) 2 (Front of module when installed into the control panel WITHOUT being
sealed to the panel)
IEEE C37.2 Under the scope of IEEE 37.2, function numbers can also be used to
(Standard Electrical represent functions in microprocessor devices and software programs.
Power System Device The controller is device number 11L-8000 (Multifunction device
Function Numbers and protecting Line (generator) –module).
Contact Designations)
As the module is configurable by the generator OEM, the functions
covered by the module vary. Under the module’s factory configuration,
the device numbers included within the module are :
Continued overleaf...
Standard Description
IEEE C37.2 Continued…
(Standard Electrical
Power System Device 49 – Machine Or Transformer Thermal Relay (USING EXPANSION
Function Numbers and MODULE)
Contact Designations) 50 – Instantaneous Overcurrent Relay
52 – AC Circuit Breaker
55 – Power Factor Relay (USING INTERNAL PLC EDITOR)
59AC – AC Overvoltage Relay
59DC – DC Overvoltage Relay
62 – Time Delay Stopping Or Opening Relay
63 – Pressure Switch
71 – Level Switch
74 – Alarm Relay
78 – Phase-angle measuring relay
79 – Reclosing relay (USING INTERNAL PLC EDITOR)
81 – Frequency Relay
83 – Automatic Selective Control Or Transfer Relay
86 – Lockout Relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
2.11.9.1 IP CLASSIFICATIONS
IP65 (Front of module when module is installed into the control panel with the optional sealing
gasket).
IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the
panel)
12 (Front of module when module is installed into the control panel with the optional sealing gasket).
2 (front of module when module is installed into the control panel WITHOUT being sealed to the
panel)
NOTE: There is no direct equivalence between IP / NEMA ratings. IP figures shown are
approximate only.
1 Provides a degree of protection against contact with the enclosure equipment and against a
limited amount of falling dirt.
IP30
2 Provides a degree of protection against limited amounts of falling water and dirt.
IP31
3 Provides a degree of protection against windblown dust, rain and sleet; undamaged by the
formation of ice on the enclosure.
IP64
3R Provides a degree of protection against rain and sleet:; undamaged by the formation of ice
on the enclosure.
IP32
4 (X) Provides a degree of protection against splashing water, windblown dust and rain, hose
directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion).
IP66
12/12K Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.
IP65
13 Provides a degree of protection against dust and spraying of water, oil and non corrosive
coolants.
IP65
3 INSTALLATION
The module is designed to be mounted on the panel fascia. For dimension and mounting details, see
the section entitled Specification, Dimension and mounting elsewhere in this document.
NOTE: Availability of some terminals depends upon module version. Full details are given
in the section entitled Terminal Description elsewhere in this manual.
Terminals 30-37 Serial and Terminals 38-41 Terminals 42-47 Terminals 48-53
part
number
label
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
Pin Cable
Description Notes
No Size
DC Plant Supply Input 2.5 mm²
1
(Negative) AWG 13
DC Plant Supply Input 2.5 mm²
2 Supplies the module and DC Outputs A, B, C, D, E & F
(Positive) AWG 13
1.0 mm²
3 Output relay G Plant Supply Positive from terminal 2. 2 Amp rated.
AWG 18
1.0 mm²
4 Output relay H Plant Supply Positive from terminal 2. 2 Amp rated.
AWG 18
1.0 mm²
5 Output relay I Plant Supply Positive from terminal 2. 2 Amp rated.
AWG 18
1.0 mm²
6 Output relay J Plant Supply Positive from terminal 2. 2 Amp rated.
AWG 18
1.0 mm²
7 Output relay K Plant Supply Positive from terminal 2. 2 Amp rated.
AWG 18
1.0 mm²
8 Output relay L Plant Supply Positive from terminal 2. 2 Amp rated.
AWG 18
Pin Cable
Description Notes
No Size
0.5 mm²
9 Configurable digital input A Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
10 Configurable digital input B Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
11 Configurable digital input C Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
12 Configurable digital input D Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
13 Configurable digital input E Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
14 Configurable digital input F Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
15 Configurable digital input G Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
16 Configurable digital input H Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
17 Configurable digital input I Switch to negative or positive depending on configuration
AWG 20
Pin Cable
Description Notes
No Size
0.5 mm²
18 Configurable digital input J Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
19 Configurable digital input K Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
20 Configurable digital input L Switch to negative or positive depending on configuration
AWG 20
0.5 mm²
21 DSENet expansion B (+) Use only 120 Ω RS485 approved cable
AWG 20
0.5 mm²
22 DSENet expansion A (-) Use only 120 Ω RS485 approved cable
AWG 20
0.5 mm²
23 DSENet expansion SCR Use only 120 Ω RS485 approved cable
AWG 20
Pin Cable
Description Notes
No. Size
1.0 mm² Normally closed volt-free relay user configured (8 A
25 Output relay E
AWG 18 resistive at 250 V AC rated)
1.0 mm² Normally closed volt-free relay user configured (8 A
26 Output relay E
AWG 18 resistive at 250 V AC rated)
1.0 mm² Normally open volt-free relay user configured (8 A
28 Output relay F
AWG 18 resistive at 250 V AC rated)
1.0 mm² Normally open volt-free relay user configured (8 A
29 Output relay F
AWG 18 resistive at 250 V AC rated)
NOTE: The above table describes connections to a three phase, four wire alternator. For
alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this
manual.
Pin Cable
Description Notes
No. Size
1.0 mm² Normally configured to control S1 contactor coil
30 Output relay A
AWG 18 (Recommend 10A fuse)
1.0 mm²
31 Output relay A Normally configured to control S1contactor coil
AWG 18
1.0 mm² Normally configured to control S2 contactor coil
32 Output relay B
AWG 18 (Recommend 10A fuse)
1.0 mm²
33 Output relay B Normally configured to control S2 contactor coil
AWG 18
1.0 mm² Connect to S2 L1 (U) output (AC)
34 S2 L1 (U) voltage monitoring
AWG 18 (Recommend 2A fuse)
1.0 mm² Connect to S2 L2 (V) output (AC)
35 S2 L2 (V) voltage monitoring input
AWG 18 (Recommend 2A fuse)
1.0 mm² Connect to S2 L3 (W) output (AC)
36 S2 L3 (W) voltage monitoring input
AWG 18 (Recommend 2A fuse)
1.0 mm²
37 S2 Neutral (N) input Connect to S2 Neutral terminal (AC)
AWG 18
NOTE: The above table describes connections to a three phase, four wire alternator. For
alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this
manual.
Pin Cable
Description Notes
No. Size
1.0 mm² Connect to S1 L1 (R) incoming supply (AC)
38 S1 L1 (R) voltage monitoring
AWG 18 (Recommend 2A fuse)
1.0 mm² Connect to S1 L1 (S) incoming supply (AC)
39 S1 L2 (S) voltage monitoring
AWG 18 (Recommend 2A fuse)
1.0 mm² Connect to S1 L1 (T) incoming supply (AC)
40 S1 L3 (T) voltage monitoring
AWG 18 (Recommend 2A fuse)
1.0 mm²
41 S1 Neutral (N) input Connect to S1 N incoming supply (AC)
AWG 18
WARNING!: Do not disconnect this plug when the CTs are carrying current.
Disconnection does open circuit the secondary of the C.T.’s and dangerous voltages may then
develop. Always ensure the CTs are not carrying current and the CTs are short circuit
connected before making or breaking connections to the module.
NOTE: The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the burden
of the controller, the cable length being used and any other equipment sharing the CT. If in
doubt, consult your CT supplier.
Pin Cable
Description Notes
No. Size
2.5 mm²
42 CT Secondary for Load L1 Connect to s1 secondary of L1 monitoring CT
AWG 13
2.5 mm²
43 CT Secondary for Load L2 Connect to s1 secondary of L2 monitoring CT
AWG 13
2.5 mm²
44 CT Secondary for Load L3 Connect to s1 secondary of L3 monitoring CT
AWG 13
N/A
45 Not Used
2.5 mm²
46 CT Common Connect to s2 secondary of all CT’s
AWG 13
3.1.7.1 CT CONNECTIONS
s1 is the secondary of the CT that connects to the DSE Module’s input for the CT measuring
s2 is the secondary of the CT that must be commoned with the s2 connections of all the other CTs
and connected to the CT common terminal of the module.
Labelled as Labelled as
p1, k or K p2, l or L
TO SUPPLY TO LOAD
POLARITY OF CT PRIMARY
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
Pin Cable
Description Notes
No. Size
1.0 mm²
48 Output C Normally Open
AWG 18
1.0 mm² Volts free relay change-over relay user configured (8A resistive
49 Output C Common
AWG 18 at 250V AC rated)
1.0 mm²
50 Output C Normally Closed
AWG 18
1.0 mm²
51 Output D Normally Open
AWG 18
1.0 mm² Volts free relay change-over relay user configured (8A resistive
52 Output D Common
AWG 18 at 250V AC rated)
1.0 mm²
53 Output D Normally Closed
AWG 18
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
NOTE: The USB connection cable between the PC and the module must not be extended
beyond 6 m (20 feet). For distances over 6 m, it is possible to use a third party USB extender.
Typically, they extend USB up to 50 m (55 yards). The supply and support of this type of
equipment is outside the scope of Deep Sea Electronics PLC.
CAUTION!: Care must be taken not to overload the PCs USB system by connecting more
than the recommended number of USB devices to the PC. For further information, consult the
PC supplier.
Cable
Description Notes
Size
Socket for connection to PC with DSE 0.5 mm² This is a standard USB
Configuration Suite Software AWG 20 type A to type B connector.
Location of RS232
connector
3.1.11 RS232 CONNECTOR
Genset manufacturers and panel builders may use these diagrams as a starting point; however, refer
to the completed system diagram provided by the system manufacturer for complete wiring detail.
Further wiring suggestions are available in the following DSE publications, available at
www.deepseaplc.com.
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
The controller is factory configured to connect to a 3 phase, 4 wire Star connected alternator. This
section details connections for alternative AC topologies. Ensure to configure the controller to suit the
required topology.
The typical wiring diagrams located within this document show connections for a negative earth
system (the battery negative connects to Earth)
When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the
following points must be followed:
• Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
• All points shown as Earth on the typical wiring diagram must connect to BATTERY
NEGATIVE (not earth).
Where neither the battery positive nor battery negative terminals are connected to earth the following
points must to be followed
• Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
• All points shown as Earth on the typical wiring diagram must connect to BATTERY
NEGATIVE (not earth).
For part numbers of the expansion modules and their documentation, see section entitled DSENet
Expansion Modules elsewhere in this manual.
4 DESCRIPTION OF CONTROLS
NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to the configuration source for the exact
sequences and timers observed by any particular module in the field.
CAUTION: The module may instruct an engine start event due to external influences.
Therefore, it is possible for the engine to start at any time without warning. Prior to performing
any maintenance on the system, it is recommended that steps are taken to remove the battery
and isolate supplies.
Control of the module is via push buttons mounted on the front of the module with
Start Inhibit/Reset , Manual , Auto , Mode , Alarm Mute , Latest Transfer
Information , Close/Open S1 and Close/Open S2 functions. For normal operation, these
are the only controls which need to be operated. Details of their operation are provided later in this
document.
Open/Close S2
Open/Close S1 (manual mode only)
(manual mode only)
Latest Transfer
Select Stop Information (Info)
mode
S1 status LED.
Illuminated when S1
is supplying the load.
S2 status LED.
Illuminated when S2
is supplying the load.
Manual
This button places the module into its Manual mode to allow manual control of
the ATS functions. This starts S2 when configured as a generator, and runs it off
load.
For further details, please see the more detailed description of ‘Manual operation’
elsewhere in this document.
Auto
This button places the module into its Auto mode. This mode allows the
module to control the function of S1 and S2 automatically. The module monitors
the remote start input and S1 supply status and once a start request is made, a
start request is given to S2 if configured to a generator and once available, placed
on load.
Upon removal of the starting signal, the module automatically transfers the load
from S2 and remove the start signal to the generator observing the return delay
timer and cooling timer as necessary. The module then awaits for the next start
event.
For further details, please see the more detailed description of ‘Auto operation’
elsewhere in this manual.
Mode
This button allows the user to cycle through different operating Mode and
press the Tick to accept the mode change.
The modes available are:
Test On Load: This mode allows the module to start and load S2 for test purposes.
Test Off Load: This mode allows the module to start S2 and leave off load for test
purposes.
Prohibit Return: This mode is used to prevent the module from returning load the
S1 until instructed.
For further details, please see the more detailed description of ‘Mode operation’
elsewhere in this manual.
Icon Description
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the
LEDs as a lamp test feature.
Whilst pressing this button, the module displays the reason, time, date and
duration for the latest transfer that occurred, holding this button cycles between the
last S1 transfer and the last S2 transfer.
For further details, please see the more detailed description of ‘Viewing Latest
Transfer Information Page’ elsewhere in this manual.
Close / Open to S1
Pressing the Close / Open S1 button when S1 is on load, opens the S1 load
switch.
Pressing the Close / Open S1 button when S2 is on load and S1 is healthy, the
S2 load switch opens, wait for the duration of the transfer delay, then closes the S1
load switch.
For further details, please see the more detailed description of ‘Manual operation’
elsewhere in this document.
Close/Open to S2
Pressing the Close / Open S2 button when S2 is on load, opens the S2 load
switch.
Pressing the Close / Open S2 button when S1 is on load and S2 is healthy, the
S1 load switch opens, wait for the duration of the transfer delay, then closes the S2
load switch.
For further details, please see the more detailed description of ‘Manual operation’
elsewhere in this document.
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items
elsewhere in this manual.
The complete order and contents of each information page are given in the following sections
Once selected the page remains on the LCD display until the user selects a different page, or after an
extended period of inactivity (LCD Page Timer), the module reverts to the status display.
If no buttons are pressed upon entering an instrumentation page, the instruments are displayed
automatically subject to the setting of the LCD Scroll Timer.
The LCD Page and LCD Scroll timers are configurable using the DSE Configuration Suite Software or
by using the Front Panel Editor.
Alternatively, to scroll manually through all instruments on the currently selected page, press the scroll
To re-enable ‘autoscroll’ press the scroll buttons to scroll to the ‘title’ of the instrumentation
page (ie S1). A short time later (the duration of the LCD Scroll Timer), the instrumentation display
begins to autoscroll.
When scrolling manually, the display automatically returns to the Status page if no buttons are
pressed for the duration of the configurable LCD Page Timer.
If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw
the operator’s attention to the alarm condition.
4.2.1 STATUS
This is the ‘home’ page, which is displayed when no other page has been selected, and the page that
is automatically displayed after a period of inactivity (LCD Page Timer) of the module control buttons.
Contains summary information of both supplies along with different module status display.
This page changes with the action of the controller, when S1 is on load, S1 parameters are seen and
when changing to S2 on load, the S2 parameters are shown.
No Start Request Example of the first status screen showing no start request to S2 and
S1 Closed S1 closed supplying the load…
L-N 230V 40A
L-L 400V 50.0Hz
4.2.2 S1
Contains electrical values of S1 measured or derived from the module’s voltage and current inputs.
• S1 Configuration
• S1 State
• S1 Summary
• S1 Voltage (ph-N)
• S1 Voltage (ph-ph)
• S1 Frequency
• S1 Current
• S1 Earth Current
• S1 Load (ph-N kW)
• S1 Load (Total kW)
• S1 Load (ph-N kV A)
• S1 Load (Total kV A)
• S1 Power Factor
• S1 Power Factor Average
• S1 Load (ph-N kvar)
• S1 Load (Total kvar)
• S1 Load (kW h, kV A h, kvar h)
4.2.3 S2
Contains electrical values of S2 measured or derived from the module’s voltage and current inputs.
• S2 Configuration
• S2 State
• S2 Summary
• S2 Voltage (ph-N)
• S2 Voltage (ph-ph)
• S2 Frequency
• S2 Current
• S2 Earth Current
• S2 Load (ph-N kW)
• S2 Load (Total kW)
• S2 Load (ph-N kV A)
• S2 Load (Total kV A)
• S2 Power Factor
• S2 Power Factor Average
• S2 Load (ph-N kvar)
• S2 Load (Total kvar)
• S2 Load (kW h, kV A h, kvar h)
• Load Control
4.2.4 MODULE
• S1 Configuration
• S2 Configuration
• Date and Time
• Battery Voltage
4.2.5 EXPANSION
Contains the measured value of the expansion module’s analogue inputs, this is pressure, percentage
or temperature for example ‘Bulk Fuel Level’.
4.2.6 ALARMS
Contains the alarms currently active on the module. For more information please see the section
entitled ‘Protections’ else where in this manual.
The module maintains a log of past alarms and/or selected status changes.
At the time of writing, the modules log is capable of storing the last 250 log entries.
Under default factory settings, the event log only includes electrical trip alarms (The event log does
not contain Warning alarms); however, this is configurable by the system designer using the DSE
Configuration Suite software.
Once the log is full, any subsequent shutdown alarms overwrites the oldest entry in the log.
Hence, the log always contains the most recent alarms.
The module logs the alarm, along with the date and time of the event (or engine running hours if
configured to do so).
If the module is configured and connected to send SMS text
To view the event log, repeatedly press the next page button until the LCD screen displays the
Event log :
1 Event log
S1 Failure This is event 1.
Warning
23 Mar 2014, 08:25:46
Continuing to press down cycles through the past alarms after which the display shows the
most recent alarm and the cycle begins again.
To exit the event log and return to viewing the instruments, press the next page button to
select the next instrumentation page.
NOTE: Factory Default settings are for the RS232 port to be enabled with no modem
connected, operating at 19200 baud, Modbus slave address 10.
This section is included to give information about the RS232 serial port and external modem (if
connected).
The items displayed on this page change depending upon configuration of the module. Refer to the
system supplier for further details.
NOTE: Not all alarms generate a dial out command; this is dependant upon module
configuration of the event log. Any event configured to be recorded in the event log causes the
modem to dial out to a PC.
When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the
modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the
Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is
dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is
established, all data is passed between the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out
whenever an alarm is generated.
NOTE: Not all alarms generate a dial out command; this is dependant upon module
configuration of the event log. Any event configured to be recorded in the event log causes the
modem to dial out to a PC.
NOTE: In the case of GSM modems, it is important that a DATA ENABLED SIM is used.
This is often a different number than the ‘voice number’ and is often called Circuit Switched
Data (CSD) by the SIM provider.
When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the
modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the
Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is
dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is
established, all data is passed between the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out
whenever an alarm is generated.
Many GSM modems are fitted with a status LED to show operator cell status and ringing indicator.
These are a useful troubleshooting tool.
In the case of GSM connection problems, try calling the DATA number of the SIMCARD with an
ordinary telephone. After two rings, the modem answers the call and then starts ‘squealing’. If this
does not happen, check all modem connections and double check with the SIM provider that it is a
DATA SIM and can operate as a data modem. DATA is NOT the same as FAX or GPRS and is often
called Circuit Switched Data (CSD) by the SIM provider.
If the GSM modem is not purchased from DSE, ensure that it has been correctly set to operate at
9600 baud.
3) In case of communication failure between the modem and module, the modem is automatically
reset and initialisation is attempted once more:
In the case of a module that is unable to communicate with the modem, the display continuously
cycles between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and
attempts to communicate with it again, this continues until correct communication is established
with the modem. In this instance, check connections and verify the modem operation.
Modem diagnostic screens are included; press the Scroll Down button when viewing the
RS232 Serial Port instruments to cycle to the available screens. If modem communication problems
are experiencied, this information aids troubleshooting.
Line Description
RTS Request to Send Flow Control
CTS Clear to Send Flow Control
DSR Data Set Ready Ready to Communicate
DTR Data Terminal Ready Ready to Communicate
DCD Data Carrier Detect Modem is Connected
Modem Commands
Rx: OK Shows the last command sent to the
Tx: AT+IPR=9600 modem and the result of the command.
Rx: OK
The modules operate as a modbus RTU slave device. In a modbus system, there is only one Master,
typically a PLC, HMI system or PC SCADA system.
This master requests for information from the modbus slave (The module) and may (in control
systems) also send request to change operating modes etc. Unless the Master makes a request, the
slave is ‘quiet’ on the data link.
The DSE MODBUS document containing register mappings inside the DSE module is available upon
request from [email protected]. Email the request along with the serial number of the DSE
module to ensure the correct information is sent.
NOTE: Factory Default settings are for the RS485 port to operate at 19200 baud, modbus
slave address 10.
This section is included to give information about the currently selected serial port
The items displayed on this pagel change depending upon configuration of the module. Refer to the
system supplier for further details.
The DSE MODBUS document containing register mappings inside the DSE module is available upon
request from [email protected]. Email the request along with the serial number of the DSE
module to ensure the correct information is sent.
Shutdown=(ReadRegister(10,0306,1) >> 12) & 1): reads (hex) 0306 and looks at bit 13
(shutdown alarm present)
Warning=(ReadRegister(10,0306,1) >> 11) & 1): reads (hex) 0306 and looks at bit 12 (Warning
alarm present)
ControlledShutdown=(ReadRegister(10,0306,1) >> 10) & 1): reads (hex) 0306 and looks at
bit 11 (Controlled Shutdown alarm present)
4.2.9 SCHEDULER
2/3 Schedule 10:39 Example of the 3rd scheduled operation in bank 2 for S2.
Off Load Week 3
On 12:00 Run Time 00:30
M T W T F S S
4.2.10 ABOUT
Contains important information about the module and the firmware versions. This information may be
asked for when contacting DSE Technical Support Department for advice.
About
Bootloader V1.3.4 • Bootloader - Firmware Update bootloader software
version
Analogue V2.0.0 •
S1 Latest Transfer 16:53 Example of the Latest Transfer page which shows that there
S2 Under Voltage was a transfer cause by an S1 Under Voltage failure which
22 Oct 2014
2014, 12:59:47 lasted for 27 minutes and 13 seconds.
00:27:13
• Indications - Monitoring of a digital input and indicating associated functioning user’s equipment -
Such as Battery Charger On or Louvres Open, etc.
• Warning & Electrical Trips - Specific indication of a particular warning or electrical trip condition,
backed up by LCD indication - Such as S2 Under Voltage Trip, Transformer Over Temperature, etc.
• Status Indications - Indication of specific functions or sequences derived from the modules
operating state - Such as, Panel Locked, S2 Available, etc.
4.5 OPERATION
NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to the configuration source for the exact
sequences and timers observed by any particular module in the field.
NOTE: For comprehensive detail of the load switching functionality of each Breaker
Scheme, refer to DSE Publication: 057-237 DSE335 Configuration Suite PC Software Manual.
The load switching functionality of the DSE335 is dependant on which Breaker Scheme the module is
currently configured to adhere to. A brief description of the operation of each scheme is detailed
below:
NOTE: S1 Closed Auxiliary and S2 Closed Auxiliary inputs do not affect the operation of
the load switching in Breaker Scheme A
Breaker Scheme A has been designed for use with contactors or ACB’s. When this scheme is
selected the DSE335 will always perfrom an open transition, with a pre-configured transfer delay
between opening one load switch, and closing the other. Breaker Scheme A is suitable for load
switching devices that require either pulsed or continuous close / open commands.
Breaker Scheme B has been designed primarily for use with rotary transfer switches with a very fast
changeover time. When this scheme is selected the DSE335 may be configured to perfrom either a
normal open transition, with a pre-configured transfer delay between opening one load switch, and
closing the other, or an open transition with Check Sync, in which the open and close commands are
sent to each load switch simultaneously. For the latter option, Check Sync must be enabled within the
DSE335. The module then proceeds to compare the phase angle and frequency difference between
the two supplies. A transfer is then only allowed when these values are within pre-defined limits.
Breaker Scheme B is suitable for a limited amount of load switching devices, all of which must be able
to accept pulse signal for opening and closing.
Breaker Scheme C has been designed for use with contactors or ACB’s. This scheme can be used for
open transition, open transition with Check Sync, or closed transition with Check Sync. The open
transition functionality of Breaker Scheme C is identical to that of Breaker Scheme A. The open
transition with Check Sync functionality is similar to that of Breaker Scheme B, but additionally
supports continuous signal open and close commands, and so is compatible with contactors and
ACB’s. The closed transition with Check Sync functionality allows for both load switching devices to
be closed, and thus both supplies in parallel, for the preconfigured Parallel Time. As soon as the
DSE335 detects the load switching device of the supply the load is being transferred to has closed,
the Parallel Time timer begins. Once this timer has expired, the DSE335 opens the load switching
device of the supply the load has been transferred from. If at any time during this process a load
switching device is detected to have not opened or closed as instructed, one or multiple alarms are
generated. At this point the DSE335 configures the load switching devices to ensure continued supply
of the site load where possible. Following such instances, load switch alarms may be cleared without
putting the DSE335 into Stop mode by pressing and holding the Mute button on the front of the
module for 5 seconds, or enabling a module input configured as Reset Breaker Alarms. Doing so only
resets these alarms, leaving any other latched or active alarms still present. Pressing the Stop button
when in Stop mode also clears the load switch alarms, along with any others present.
4.6.1 STARTING S2
4.6.2 STOPPING S2
Select Stop/Reset
mode. S2 breaker is
opened and the start
request is removed.
4.7 STOP/RESET
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
In Stop mode , the module removes S2 from load (if necessary) and removes the start signal
given to the generator controller (if S2 is configured as a generator and it is running).
If S2 is configured as a generator and it does not stop after the cooling down time, the Fail To Stop
alarm is activated (subject to if the Fail To Stop timer is enabled and its duration). To detect the
generator (S2) is at rest the following must occur:
Any latched alarms that have been cleared are reset when Stop mode is entered.
S2 is not placed on load (or started if configured as a generator) when in Stop mode . If remote
start signals are given, the input is ignored until Auto mode is entered.
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
In Manual mode, the module actives an output to give a start signal to an external generator
controller (if S2 is configured as a generator supply), and if required, change the state of the load
switching devices. An LED indicator beside the button confirms this action.
As soon as the Manual mode button is pressed, the output to give a start signal to an external
generator controller is activated (if S2 is configured as a generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved loading voltage and frequency (if configured as a generator).
4.8.2 S2 AVAILABLE
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
In Manual mode, the load is not transferred to S2 unless a ‘loading request’ is made and the S2
supply is within limits (if configured as a mains supply) or achieve Loading Voltage and Loading
Frequency (if configured as a generator).
A loading request can come from a number of sources.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
Once the load has been transferred to S2, it is not automatically transferred back to the S1 supply. To
manually transfer the load back to the mains either:
For further details of breaker control, see the section entitled “controls and indications” elsewhere in
this manual.
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
In Auto mode, the module operates fully automatically, changing between the two supplies in
case of failure without user intervention. An LED indicator beside the button confirms this action.
To allow for ‘false’ start/load requests such as S1 brownouts, the Start Delay timer begins. There are
individual start delay timers for each of the different start/load request types.
When all start/load requests are removed during the Start Delay timer, the unit returns to a stand-by
state.
If a start/load request is still present at the end of the Start Delay timer, an output to give a start signal
to an external generator controller is activated (if S2 is configured as a generator).
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
If a start/load request is present but the starting sequence has not begun, an input configured to ‘Auto
Start Inhibit’ could be active.
4.9.3 S2 AVAILABLE
In Auto mode, the load is automatically transferred to S2 when it is within limits (if configured as a
mains supply) or achieve loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’
could be active.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
The Return Delay timer operates to ensure that the start/load request has been permanently removed
and isn’t just a short term removal. In case another start request is made during the Return Delay (or
cooling down period when S2 is configured as a generator), the set returns on load.
If there are no starting requests at the end of the Return Delay timer, the load is transferred back from
the S2 to the S1 supply and the Cooling timer is initiated (when S2 is configured as a generator).
The Cooling timer allows S2 (when configured as a generator) to run off load and cool sufficiently
before the start signal to the external generator control unit is removed. This is particularly important
where turbo chargers are fitted to the engine.
After the Cooling timer has expired, the start signal given to the external generator controller is
removed..
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Pressing the Mode button sets which of the three modes below to leave the controller in.
Activate by pressing the Mode button repeatedly until Test on Load is shown on the display, then
press the Tick button to confirm the change. An LED indicator beside the button confirms this
action.
The Test on Load mode starts S2 (if configured as a generator) and transfers the load to S2.
As soon as the Mode is selected and confirmed by pressing the Tick button is pressed, the
output to give a start signal to an external generator controller is activated (if S2 is configured as a
generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
4.10.1.2 S2 AVAILABLE
In Test on Load mode, the load is automatically transferred to S2 when it is within limits (if configured
as a mains supply) or had achieved loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’
could be active.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
Activate by pressing the Mode button repeatedly until Test off Load is shown on the display, then
press the Tick button to confirm the change. An LED indicator beside the button confirms this
action.
The Test off Load mode only starts S2 (if configured as a generator) and leave it off load.
As soon as the Mode is selected and confirmed by pressing the Tick button is pressed, the
output to give a start signal to an external generator controller is activated (if S2 is configured as a
generator)
If the generator fails to start during the S2 Fail Delay timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
4.10.2.2 S2 AVAILABLE
In Test Off Load mode, the load is not transferred to S2 unless a ‘loading request’ is made and the S2
supply is within limits (if configured as a mains supply) or has achieved loading voltage and frequency
(if configured as a generator).
A loading request can come from a number of sources.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
Activate by pressing the Mode button repeatedly until Prohibit Return is shown on the display,
then press the Tick button to confirm the change. An LED indicator beside the button confirms
this action.
The Prohibit Return mode prevents the load being transfer back to the S1 from the S2 supply until the
module is instructed to do so.
To allow for ‘false’ start/load requests such as S1 brownouts, the Start Delay timer begins. There are
individual Start Delay timers for each of the different start/load request types.
When all start/load requests are removed during the Start Delay timer, the unit returns to a stand-by
state.
If a start/load request is still present at the end of the Start Delay timer, an output to give a start signal
to an external generator controller is activated (if S2 is configured as a generator).
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
If a start/load request is present but the starting sequence has not begun, an input configured to ‘Auto
Start Inhibit’ could be active.
4.10.3.3 S2 AVAILABLE
In Prohibit Return mode, the load is automatically transferred to S2 when it is within limits (if
configured as a mains supply) or has achieved Loading Voltage and Loading Frequency (if configured
as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’
could be active.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
In Return Inhibit mode, S2 continues to run on load even if S1 has return until either:
4.11 SCHEDULER
The controller contains an inbuilt exercise run scheduler, capable of automatically starting and
stopping the set. Up to 16 scheduled start/stop sequences can be configured in banks of 8 to either
repeat on a 7-day or 28-day cycle.
Scheduled runs may be on load or off load depending upon module configuration.
Example
• Scheduled runs operate ONLY if the module is in Auto mode with no Electrical Trip alarm
present.
• If the module is in Stop or Manual mode when a scheduled run begins, S2 is not
started (if configured as generator). However, if the module is moved into Auto mode
during a scheduled run, S2 is called to start.
• Depending upon configuration by the system designer, an external input can be used to
inhibit a scheduled run.
• If S2 is Off Load in Auto mode and a scheduled run configured to ‘Transfer to S2’ begins,
S2 is placed On Load for the duration of the Schedule.
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
The Load Shedding Control feature (if enabled) allows for a maximum of five load shedding steps.
When S2 is about to take load, the configured number of Load Shedding Control Outputs at Startup
energises. This configurable setting allows (for instance) certain loads to be removed from S2 prior to
the set’s load switch being closed. This can be used to ensure the initial loading of the set is kept to a
minimum, below the Load Acceptance specification of S2.
If at any time the load falls back below the Load Shedding Return level, the Return Time starts. If the
load remains below the return level when the timer has expired the ‘highest’ Load Shedding Control
output that has been energised is de-energised. This process continues until all outputs have been
de-energised.
When the set enters a stopping sequence for any reason the Load Shedding control’ outputs are de-
energised at the same time as the S2 load switch is signalled to open.
5 PROTECTIONS
When an alarm is present, the Audible Alarm sounds and the Common alarm LED if configured
illuminates.
The audible alarm can be silenced by pressing the Alarm Mute
The LCD display jumps from the ‘Information page’ to display the Alarm Page
The LCD displays multiple alarms E.g. “S1 Failure Warning”, “Fail to Stop Warning” and “Digital Input
A Electrical Trip”. These automatically scroll in the order that they occurred.
In the event of a warning alarm, the LCD displays the appropriate text. If an electrical trip then occurs,
the module again displays the appropriate text.
Example:-
Alarm 1/2
Fail to Stop
Unlatched
Warning
Alarm 2/2
Digital Input A
Unlatched
Electrical Trip
5.1 INDICATIONS
Indications are non-critical and often status conditions. They do not appear on the LCD of the module
as a text message. However, an output or LED indicator can be configured to draw the operator’s
attention to the event.
Example
• Sample showing
operation of the LED.
5.2 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the system, they serve to
draw the operators attention to an undesirable condition.
Example
1/2 Alarm
S1 Failure
Latched
Warning
In the event of an alarm the LCD jumps to the alarms page, and scroll through all active warnings and
shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However some
warning alarms are latched and need to be reset manually.
Display Reason
Auxiliary Inputs If an auxiliary input has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
Battery Under Voltage The DC supply has fallen below the low volts setting level for the
duration of the low battery volts timer
Battery Over Voltage The DC supply has risen above the high volts setting level for the
duration of the high battery volts timer
Calibration Lost The module has lost its calibration settings and must be sent back to
DSE to be re-calibrated.
Expansion Inputs If an expansion input has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
Fail To Start S2 has not reached the configured limits or loading voltage and
frequency before the S2 Fail Delay timer has expired.
Fail To Stop The module has detected a condition that indicates that S2 is present
when it has been instructed to stop.
Loading Voltage Not Indicates that the S2 voltage is not above the configured loading
Reached voltage. S2 does not take load when the alarm is present after the
safety timer.
Display Reason
PLC Functions If a PLC Function has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
S1 Breaker Auxiliary Fail Indicates that the S1 Closed Auxiliary input has not activated along with
the Close S1 Output or Open S1 Output, or the input has activated
when the output was not energised.
S1 Failure Unlatched The module has detected that S1 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S1 returning to an available state.
S1 Phase Rotation The module has detected a wrong phase sequence for S1.
S2 Breaker Auxiliary Fail Indicates that the S2 Closed Auxiliary input has not activated along with
the Close S2 Output or Open S2 Output, or the input has activated
when the output was not energised.
S2 Failure Unlatched The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S2 returning to an available state.
S2 Phase Rotation The module has detected a wrong phase sequence for S2.
Example
1/2 Alarm
Digital Input A
Latched
Electrical Trip
Electrical trips are latching alarms and unload and stop S2 (if configured as a generator). To clear
these alarms the STOP button is pressed
Display Reason
Auxiliary Inputs If an auxiliary input has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates.
Expansion Inputs If an expansion input has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates.
PLC Functions If a PLC Function has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates.
S1 Breaker Auxiliary Fail Indicates that the S1 Closed Auxiliary input has not activated along with
the Close S1 Output or Open S1 Output, or the input has activated
when the output was not energised.
S1 Phase Rotation The module has detected a wrong phase sequence for S1.
S2 Failure Unlatched The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S2 returning to an available state.
S2 Phase Rotation The module has detected a wrong phase sequence for S2.
Use the module’s navigation buttons to traverse the menu and make value changes to the
parameters:
Previous page
Press and hold the Stop and Tick buttons simultaneously to Editor
enter the editor.
If a module security PIN has been set, the PIN number request is then ####
shown :
Press the Tick button, the first ‘#’ changes to ‘0’. Press (up or down) to adjust it to the correct
value.
Press (right) when the first digit is correctly entered. The digit entered is now shown as ‘#’ for
security.
Repeat this process for the other digits of the PIN number. Press (left) to move back and adjust
one of the previous digits.
When the Tick button is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not Editor - Display
been enabled), the editor is displayed :
Contrast
54 %
NOTE: The PIN number is not set by DSE when the module leaves the factory. If the
module has a PIN code set, this has been affected by the ATS supplier who must be contacted
if the code is required. If the code has been ‘lost’ or ‘forgotten’, the module must be returned
to the DSE factory to have the module’s code removed. A charge is applied for this procedure.
NB - This procedure cannot be performed away from the DSE factory.
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details on
configuring, monitoring and control.
Press the (up or down) buttons to select the parameter to view/change within the currently
selected section.
To edit the parameter, press the Tick button to enter edit mode. The parameter begins to flash to
indicate that value is being edited.
Press the (up or down) buttons to change the parameter to the required value.
Press the Tick button to save the value. The parameter ceases flashing to indicate that it has been
saved.
To exit the editor at any time, press and hold the Tick button.
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
7 COMMISSIONING
Before the system is started, it is recommended that the following checks are made:-
• The unit is adequately cooled and all the wiring to the module is of a standard and rating
compatible with the system. Check all mechanical parts are fitted correctly and that all electrical
connections (including earths) are sound.
• The unit DC supply is fused and connected to the battery and that it is of the correct polarity.
• To check the start cycle operation, take appropriate measures to prevent S2 from starting (if
configured as a generator by disconnecting the start output) and press the Manual mode
button. Check to see if the start signal energises.
• Set the modules internal clock/calendar to ensure correct operation of the scheduler and event
logging functions. For details of this procedure see section entitled Front Panel Configuration –
Editing the date and time.
• If, despite repeated checking of the connections between the controller and the customer’s
system, satisfactory operation cannot be achieved, then the customer is requested to contact the
DSE Technical Support Department for further advice.
8 FAULT FINDING
8.1 STARTING
8.2 LOADING
8.3 ALARMS
8.4 COMMUNICATIONS
8.5 INSTRUMENTS
8.6 MISCELLANEOUS
NOTE: The above fault finding is provided as a guide check-list only. As the module can
be configured to provide a wide range of different features, always refer to the source of the
module configuration if in doubt.
NOTE: Terminals 24 and 27 are fitted to controllers but must not be connected.
84
Maintenance, Spares, Repairs and Servicing
NOTE: A maximum of six (6) expansion modules can be connected to the DSENet®.
NOTE: DSENet® utilises an RS485 connection. Using Belden 9841 (or equivalent) cable
allows for the expansion cable to be extended to a maximum of 1.2 km.
DSE Stock and supply Belden 9841 cable. DSE Part Number 016-030.
10 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any
applicable warranty, refer to the original equipment supplier (OEM).
11 DISPOSAL
11.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of
WEEE separately from your other waste.