Offsites Engineering Works For The Erbil Refinery 40,000 B/D Expansion Project

This document provides specifications for level switches used in an oil refinery expansion project in Erbil, Iraq. It includes data sheets for three level switches (tags 3#-LSHL-2617A, B, C), listing technical details like manufacturer, model, materials, service conditions, electrical ratings and certifications required. The level switches are used to control pumps by signaling high and low liquid level alarms in drain pits via microswitches. All switches require IP65 protection minimum and ATEX explosion proof certification for use in hydrocarbon services.

Uploaded by

Sardar Perdawood
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views2 pages

Offsites Engineering Works For The Erbil Refinery 40,000 B/D Expansion Project

This document provides specifications for level switches used in an oil refinery expansion project in Erbil, Iraq. It includes data sheets for three level switches (tags 3#-LSHL-2617A, B, C), listing technical details like manufacturer, model, materials, service conditions, electrical ratings and certifications required. The level switches are used to control pumps by signaling high and low liquid level alarms in drain pits via microswitches. All switches require IP65 protection minimum and ATEX explosion proof certification for use in hydrocarbon services.

Uploaded by

Sardar Perdawood
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Company: Project: Engineering Contractor:

OFFSITES ENGINEERING WORKS


FOR THE ERBIL REFINERY
40,000 B/D EXPANSION PROJECT

Contract no.: 10J01762-01


Company doc. no.: Job no.: 10J01762 Engineering doc. no.:
N/A Sheet 1 of 2 10J01762-ICT-DS-000-007

OFFSITES ENGINEERING WORKS FOR THE


ERBIL REFINERY 40,000 B/D EXPANSION PROJECT

DATA SHEET FOR LEVEL SWITCHES

D0 31/08/2011 Approved for Design Lucarelli Pagliardini Cilia


C0 08/08/2011 Issued for Company approval Lucarelli Pagliardini Cilia
REV. DATE REVISION TITLE PREPARED CHECKED APPROVED

File name: 10J01762-ICT-DS-000-007-D0.doc Printed on 31/08/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR LEVEL SWITCHES
Company doc. no.: Rev.: C0 D0 Engineering doc. no.:
N/A Sheet 2 of 2 10J01762-ICT-DS-000-007

001 002 003


01 TAG NO. 3#-LSHL-2617A 3#-LSHL-2617B 3#-LSHL-2617C
02 P&ID 10J01762-PRO-DW-000-016 10J01762-PRO-DW-000-016 10J01762-PRO-DW-000-016
03 SERVICE Drain pit Drain pit Drain pit
GENERAL

04 LINE/EQUIPMENT NO. P-2617A P-2617B P-2617C


05 MANUFACTURER/MODEL NO. (*) (*) (*)
06 TYPE Float or displacer Float or displacer Float or displacer
07 DUTY Liquid level switch Liquid level switch Liquid level switch
08 MOUNTING Flanged on 4” still pipe Flanged on 4” still pipe Flanged on 4” still pipe
09 SOUR SERVICE SPEC. - - -
10 AMBIENT TEMPERATURE 0÷50°C 0÷50°C 0÷50°C
11 FLUID Oily Water / Hydrocarbon Oily Water / Hydrocarbon Oily Water / Hydrocarbon
SERVICE

12 FLUID DENSITY/VISCOSITY 840÷ 997 kg/m3 / 1÷3.77 cP 665÷997 kg/m3 / 0.3÷2.2 cP 764÷997 kg/m3 / 0.86÷25 cP
13 OP. PRESS. Min/Norm/Max 0 bar g 0 bar g 0 bar g
14 OP. TEMP. Min/Norm/Max 10 / - / 30 °C 38 / - / 60 °C 38 / - / 100 °C
15 INSTR. CONN. TYPE/SIZE/RATING Flanged – 4” 150# RF Flanged – 4” 150# RF Flanged – 4” 150# RF
DIR. MOUNT. INSTR.

16 FLANGE MATERIAL ASTM-A105 ASTM-A105 ASTM-A105


17 VESSEL INTERNAL SUPPORT Still pipe (by others) Still pipe (by others) Still pipe (by others)
18 VESSEL HEIGHT (X) (NOTE 2) 2000 mm 2000 mm 2000 mm
19 INSERTION DEPTH (*) (*) (*)
20
21 TYPE Mfr. Std. Mfr. Std. Mfr. Std.
FLOAT/DISPLACER

22 QUANTITY n°2 n°2 n°2


23 DIMENSIONS (*) (*) (*)
24 DISPLACER OR FLOAT MATERIAL AISI 316 SS AISI 316 SS AISI 316 SS
25 OTHER WETTED PARTS MATER. AISI 316 SS AISI 316 SS AISI 316 SS
26 DISPLACER EXTENSION (*) (*) (*)
27 FUNCTION Start/Stop pump Start/Stop pump Start/Stop pump
28 ALARM AT INCR./DECR. (NOTE 2) LAH (1700 mm) / LAL (300 mm) LAH (1700 mm) / LAL (300 mm) LAH (1700 mm) / LAL (300 mm)
29 SET POINT ADJUSTMENT (*) (*) (*)
30 DIFFERENTIAL Adjustable (MFR STD) Adjustable (MFR STD) Adjustable (MFR STD)
SWITCH

31 CONTACTS N° / CONFIGURATION 2 / SPDT(hermetically sealed) 2 / SPDT(hermetically sealed) 2 / SPDT(hermetically sealed)


32 CONTACTS ACTION ON ALARM LAH: close / LAL: open LAH: close / LAL: open LAH: close / LAL: open
33 CONTACTS TYPE Microswitch hermetically sealed Microswitch hermetically sealed Microswitch hermetically sealed
34 CONTACTS RATING 4A @ 230VAC 4A @ 230VAC 4A @ 230VAC
35 CONTACTS MATERIAL Noble material Noble material Noble material
36 RESET Automatic Automatic Automatic
37 MOUNTING Top Mounted Top Mounted Top Mounted
SWITCH HOUSING

38 ROTATABLE HEAD (*) (*) (*)


39 DIMENSION/MATERIAL (*) / Aluminium, epoxy coated (*) / Aluminium, epoxy coated (*) / Aluminium, epoxy coated
40 CABLE ENTRY n° 2 ISO M20x1.5 mm n° 2 ISO M20x1.5 mm n° 2 ISO M20x1.5 mm
41 ENCLOSURE PROTECTION IP 65 (min) IP 65 (min) IP 65 (min)
42 EX CLASSIFICATION Ex-d IIB T3 / ATEX 94/9/EC Ex-d IIB T3 / ATEX 94/9/EC Ex-d IIB T3 / ATEX 94/9/EC
43 TROPICALIZATION Required Required Required
ACC.

44 TAG/DATA PLATE MATERIAL Required/SS Required/SS Required/SS


NOTES:
(*) Data to be provided or to be confirmed by Supplier
(1)The following documents shall be included in the supply: Technical bulletins,
O&M manuals, calibration certificates, mechanical and electrical protection
certificates, material certificates as required on purchaser requisition documents
(2) Data to be confirmed basing on actual drain pit depth and pump characteristics

File name: 10J01762-ICT-DS-000-007-D0.doc Printed on 31/08/2011

You might also like