Manual Book Generator
Manual Book Generator
www.fgwilson.com/warranty
ORIGINAL INSTRUCTIONS
2. SAFETY 7
2.1 General .....................................................................................................................................................................................7
2.1.1 Emergency Stop Button................................................................................................................................................7
2.2 Personal Protective Equipment........................................................................................................................................7
2.3 General Hazard Information..............................................................................................................................................8
2.3.1 Pressurized Air and Water.............................................................................................................................................8
2.3.2 Containing Fluid Spillage.............................................................................................................................................8
2.3.3 Lines, Tubes and Hoses..................................................................................................................................................8
2.3.4 Disposal of Waste............................................................................................................................................................9
2.4 Fire and Explosion ................................................................................................................................................................9
2.4.1 Fire Extinguisher..............................................................................................................................................................9
2.5 Exhaust Gases.......................................................................................................................................................................10
2.6 Mechanical.............................................................................................................................................................................10
2.7 Chemical ................................................................................................................................................................................10
2.7.1 Coolant............................................................................................................................................................................. 10
2.7.2 Oils..................................................................................................................................................................................... 10
2.7.3 Batteries........................................................................................................................................................................... 10
2.8 Noise .......................................................................................................................................................................................11
2.9 Electrical .................................................................................................................................................................................11
2.9.1 Neutral-Earth Link (NEL)............................................................................................................................................. 11
2.9.2 Generator Isolating...................................................................................................................................................... 11
2.10 First Aid For Electric Shock ..............................................................................................................................................12
2.11 Hazard Label Legend ........................................................................................................................................................14
3. GENERAL DESCRIPTION 16
3.1 Typical Rating Plate.............................................................................................................................................................16
3.2 Generator set Description................................................................................................................................................17
3.3 Power Factor ........................................................................................................................................................................18
4. INSTALLATION, HANDLING AND STORAGE 19
4.1 General....................................................................................................................................................................................19
4.2 Outdoor Installation...........................................................................................................................................................20
4.2.1 Positioning of Walk-in Containers.......................................................................................................................... 21
4.2.2 Concrete Plinth.............................................................................................................................................................. 21
4.2.3 Installation Location.................................................................................................................................................... 21
4.2.4 Exhaust Discharge........................................................................................................................................................ 21
4.3 Moving the Generator set................................................................................................................................................ 22
4.3.1 Approved Lifting Methods for ISO Walk-in Containers................................................................................... 26
4.3.2 Approved Lifting Methods for Non-ISO Walk-in Containers ........................................................................ 26
3 356-5901(GB) V12 01/17
4.4 Foundations and Vibration Isolation.............................................................................................................................27
4.4.1 Foundation..................................................................................................................................................................... 27
4.4.2 Vibration Isolation........................................................................................................................................................ 27
4.5 Storage....................................................................................................................................................................................28
4.5.1 Engine Storage.............................................................................................................................................................. 28
4.5.3 Battery Storage............................................................................................................................................................. 28
5. CONTROL SYSTEM DESCRIPTION AND TROUBLE SHOOTING 29
5.1 Control System Description.............................................................................................................................................29
5.1.1 Pre-Start Checks (applicable to all control systems)........................................................................................ 29
5.2 PowerWizard 1.1, 1.1+ & 2.1 (Quickstart).......................................................................................................................31
5.2.1 General Information.................................................................................................................................................... 31
5.2.2 PowerWizard Control Module Description......................................................................................................... 31
5.2.3 Basic Operation............................................................................................................................................................. 32
5.2.4 Fault / Alarm Reset Process....................................................................................................................................... 33
5.2.5 User Interface Overview............................................................................................................................................ 33
5.2.6 Alarm Log and Resetting........................................................................................................................................... 35
5.2.7 Security............................................................................................................................................................................ 36
5.2.8 Real Time Clock Programming (PowerWizard 2.1)........................................................................................... 37
5.2.9 Fuel Transfer (PowerWizard 2.1).............................................................................................................................. 37
5.2.10 Additional Features Available................................................................................................................................ 37
5.2.11 Trouble Shooting Guide for PowerWizard........................................................................................................ 38
5.3 PowerWizard 2.1+ / 4.1.......................................................................................................................................................39
5.3.1 PowerWizard 2.1+ Control Module Description................................................................................................ 39
5.3.2 PowerWizard 4.1 Control Module Description.................................................................................................. 41
5.3.3 Alarm Log and Resetting........................................................................................................................................... 42
5.3.4 Security............................................................................................................................................................................ 43
5.3.5 Real Time Clock Programming................................................................................................................................ 44
5.3.6 Fuel Transfer................................................................................................................................................................... 44
5.3.7 Additional Features Available.................................................................................................................................. 44
5.3.8 Trouble Shooting Guide for PowerWizard........................................................................................................... 45
5.4 DCP-10 & DCP-20................................................................................................................................................................. 46
5.4.1 General Information.................................................................................................................................................... 46
5.4.2 DCP Control Module Description........................................................................................................................... 46
5.4.3 Basic Operation............................................................................................................................................................. 47
5.4.4 Fault / Alarm Reset Process - DCP-10................................................................................................................... 48
5.4.5 Fault / Alarm Reset Process - DCP-20................................................................................................................... 48
5.4.6 User Interface Overview............................................................................................................................................ 48
5.5 DeepSea Controller................................................................................................................................................................51
5.5.1 Description..................................................................................................................................................................... 51
5.5.1 Alarm Icons...................................................................................................................................................................... 52
5.5.2 Electrical Trip Alarm Icons.......................................................................................................................................... 52
5.5.3 Stop/Reset Mode........................................................................................................................................................... 52
5.5.4 Fault Finding................................................................................................................................................................... 53
4 356-5901(GB) V12 01/17
5.6 Control System Options and Upgrades.......................................................................................................................55
5.6.1 Battery Trickle / Auto Boost Chargers................................................................................................................... 55
5.6.2 Heaters ............................................................................................................................................................................ 55
5.6.3 Electric Fuel Transfer Pumps..................................................................................................................................... 55
5.6.4 Meters / Gauges............................................................................................................................................................ 56
5.6.5 Speed / Voltage Control ............................................................................................................................................ 56
5.6.6 Alarm Signalling ........................................................................................................................................................... 56
5.6.7 Automatic Preheat Control....................................................................................................................................... 56
5.6.8 Remote Annunciator Panels .................................................................................................................................... 56
6. OPERATION 57
6.1 Priming Procedure for 1100 Series.................................................................................................................................57
6.1.1 Products fitted with the small Perkins pre-filter / water separator............................................................ 57
6.1.2 Perkins 1506, 2206, 2506, 2806 Engines fitted with pre-filter / water separator................................... 58
6.1.3 Products fitted with the Racor Pre-Filter / Water Separator (Option)........................................................ 59
6.1.3 Troubleshooting........................................................................................................................................................... 60
6.1.4 Starting with Jump Start Cables............................................................................................................................. 61
6.2 Fuel Conservation................................................................................................................................................................61
6.3 Cold Weather Operation...................................................................................................................................................62
6.3.1 Hints for Cold Weather Operation.......................................................................................................................... 62
6.3.2 Viscosity of the Engine Lubrication Oil.................................................................................................................................................... 62
6.3.3 Recommendations for the Coolant....................................................................................................................... 62
7. LOAD TRANSFER PANELS 63
7.1 Engine Interface Module Description (where fitted).............................................................................................. 64
7.2 Output Circuit Breaker Description.............................................................................................................................. 64
8. ELECTRONIC ENGINE FAULT DETECTION FLASH CODES 65
9. MAINTENANCE 66
9.1 Battery Maintenance......................................................................................................................................................... 66
9.1.1 Battery Removal and Fitting...................................................................................................................................... 67
9.1.2 Battery Fluid Levels...................................................................................................................................................... 67
9.2 Preventative Maintenance Interval Schedule........................................................................................................... 68
9.3 Alternator Preventative Maintenance.......................................................................................................................... 68
9.4 Engine Preventative Maintenance................................................................................................................................ 68
9.5 Welding on or near Generator Sets...............................................................................................................................69
9.6 Decommissioning, Dismantling and Disposal..........................................................................................................69
5 356-5901(GB) V12 01/17
1. INTRODUCTION
Thank you for choosing our company to supply your electrical power needs. In line with our policy of continuous product
improvement, we reserve the right to change the information contained within this manual without notice.
This Operator Instruction Manual has been designed to help you operate and maintain your electrical generator set correctly.
We recommend that the operator should take the time to read this manual. Certain tasks may require work to be completed by
specifically trained technicians, an operator should only attempt a task detailed for an operator to complete.
This generator set is one of a family of heavy duty industrial generator sets designed to be ready to run when it arrives. Years of
diesel generator set experience has gone into the set to produce a quality source of electrical power that is efficient and reliable.
Always ensure that maintenance, adjustments and repairs are done by personnel who are authorised to do the work and
have been properly trained. Maintenance and repairs should also be carried out at regular intervals using genuine parts, this
will prolong the life of the generator set. The manufacturer is not liable for any defects or claims due to the user’s improper
installation, maintenance or use, or for any products which have been modified in any way from the state in which they were sold.
All generator sets should only be operated by those required to do so and therefore be safely kept away from non authorised use.
Some photographs or illustrations in this manual show details or attachments that may be different from your generator set.
These images are for illustrative purposes only. If you have any questions regarding your generator set, please contact your local
Dealer for the latest available information.
Every generator set is uniquely defined by a model number and serial number indicated on a rating plate generally affixed to the
alternator housing (See Section 3.1). This information is required when ordering spare parts or when service or warranty work is
required.
6 356-5901(GB) V12 01/17
2. SAFETY
2.1 General
The generator set is designed to be safe when used in the correct manner. Responsibility for safety, however, rests with the
personnel who use the set. Before performing any procedure or operating technique, it is the user’s responsibility to ensure that
it is safe to do so.
Warning:
II Read and understand all safety precautions and warnings before operating the generator set.
II Failure to follow the instructions, procedures and safety precautions in this manual may increase the possibility of
accidents and injuries.
II Never start the generator set unless it is safe to do so.
II Do not attempt to operate the generator set with a known unsafe condition.
II If the generator set is unsafe, fit danger notices and disconnect the battery negative (–) lead so that it cannot be
started until the condition is corrected.
II Ensure the generator set is protected from any unauthorised use, use signs were appropriate.
II Disconnect the battery negative (–) lead prior to attempting installation, repairs or cleaning on the generator set.
II Install and operate this generator set only in full compliance with relevant National, Local, or Federal Codes,
Standards or other requirements.
Warning
II Familiarise yourself with the location of the Emergency Stop Button. Emergency shutoff controls
are for EMERGENCY use ONLY.
II DO NOT use emergency shutoff devices or controls for normal stopping procedure.
II Do not start the engine until the problem necessitating the emergency stop has been located and corrected.
Note:
• If fluid containment is incorporated into the baseframe it must be inspected at regular intervals. Any liquids present (fuel,
oil, coolant, rainwater or condensation) should be drained out and disposed of in accordance with local regulations and
mandates.
8 356-5901(GB) V12 01/17
2.3.4 Disposal of Waste
Improper disposal of waste can threaten the environment. Potentially harmful fluids should be disposed
of according to local regulations. Always use leakproof containers when you drain fluids. Do not pour
waste onto the ground, down a drain, or into any source of water.
Warning
II Do not charge a frozen battery, this may cause an explosion.
II Ensure the generator set room is properly ventilated.
II Keep the room, the floor and the generator set clean. When spills of fuel, oil, battery
electrolyte or coolant occur, they should be cleaned up immediately.
II Never store flammable liquids near the engine.
II Store oily rags in covered metal containers.
II Do not smoke or allow sparks, flames or other sources of ignition around fuel or batteries. Fuel vapours are
explosive. Hydrogen gas generated by charging batteries is also explosive.
II Avoid refilling the fuel tank while the engine is running.
II Do not attempt to operate the generator set with any known leaks in the fuel system.
II Do not use aerosol types of starting aids such as ether. Using these types of items could result in an explosion and
personal injury.
9 356-5901(GB) V12 01/17
2.5 Exhaust Gases
Always start and operate the engine in a well-ventilated area. If the engine is in an enclosed area, vent the engine exhaust to the
outside.
Warning
II Engine exhaust contains products of combustion which may be harmful to your health.
2.6 Mechanical
The generator set is designed with guards for protection from moving parts. Care must still be taken to protect personnel and
equipment from other mechanical hazards when working around the generator set.
Warning:
II Do not attempt to operate the generator set with safety guards removed. While the generator set is running do not
attempt to reach under or around the guards for any reason.
II Keep hands, arms, long hair, loose clothing and jewellery away from pulleys, belts and other moving parts. Some
moving parts can not be seen clearly when the set is running.
II Keep access doors on enclosures, if equipped, closed and locked when not required to be open.
II Avoid contact with hot oil, hot coolant, hot exhaust gases, hot surfaces, sharp edges and corners.
II Wear protective clothing including gloves and hat when working around the generator set.
2.7 Chemical
Fuels, oils, coolants, lubricants and battery electrolyte used in this generator set are typical of the industry. However, they can be
hazardous to personnel if not treated properly. The disposal of fuels, oils, coolants, lubricants, battery electrolyte and batteries
should be carried out in accordance with local government laws and regulations.
2.7.1 Coolant
When the engine is at operating temperature, the engine coolant is hot. The coolant is also under pressure. The radiator and all
hoses to the heaters or to the engine contain hot coolant. Any contact with hot coolant or with steam can cause severe burns.
Allow cooling system components to cool before the cooling system is drained. Cooling system conditioner contains alkali. Alkali
can cause personal injury. Do not allow alkali to contact the skin, the eyes, or the mouth.
2.7.2 Oils
Hot oil and hot lubricating components can cause personal injury. Do not allow hot oil to contact the skin. Also, do not allow hot
components to contact the skin.
2.7.3 Batteries
Electrolyte is an acid. Electrolyte can cause personal injury. Do not allow electrolyte to contact the skin or the eyes. Always wear
protective glasses for servicing batteries. Wash hands after touching the batteries and connectors. Use of gloves is recommended.
Warning:
II Do not swallow or have skin contact with fuel, oil, coolant, lubricants or battery electrolyte. If swallowed, seek
medical treatment immediately. Do not induce vomiting if fuel is swallowed. For skin contact, wash with soap and
water.
II Do not wear clothing that has been contaminated by fuel or lube oil.
II It is recomended to check the electrolyte level in accessible batteries every 500 hours.
10 356-5901(GB) V12 01/17
2.8 Noise
Sound levels will vary depending on the configuration of the generator set and the final installation of the generator set.
Refer to the following for factors that influence the level of exposure:
• The characteristics of the area around the generator set
• Gaps below generator set base and installation surface or plinth.
• Other sources of noise
• The number of machines and other adjacent processes
• The length of time of exposure to the noise
This information will enable the user of the machine to evaluate the hazard and the risk.
Warning:
II Prolonged exposure to noise levels above 80 dBA is hazardous to hearing.
II Ear protection must be worn when operating or working around an operating generator set.
2.9 Electrical
Warning
II Before the generator set is operated please consult your local dealer to establish whether an NEL has been fitted.
As more than one NEL per site may be unsafe, it is important to establish whether one has already been installed on
site.
Warning:
II Ensure the generator set, including a mobile set, is effectively grounded/earthed prior to operation.
II Do not touch electrically energised parts of the generator set and/or interconnecting cables or conductors with any
part of the body or with any non insulated conductive object.
II Use only Class BC or Class ABC extinguishers on electrical fires.
II For generator sets with external socket outlets only – Residual Current Device (RCD) protection on socket outlets,
where fitted, is designed to operate within a TN earthing system. Ensure local wiring regulations are met prior
to generator set operation and that all equipment connected via the generator set sockets, including plugs and
electrical cables, are of the correct specification and are known to be in a safe and undamaged condition.
11 356-5901(GB) V12 01/17
2.10 First Aid For Electric Shock
Warning:
II Do not touch the victim’s skin with bare hands until the source of electricity has been turned off.
II Switch off the power, if possible.
II Otherwise pull the plug or pull the cable away from the victim.
II If this is not possible, stand on dry insulating material and pull the victim clear of the conductor, preferably using
insulated material such as dry wood.
II If victim is breathing, turn the victim into the recovery position.
II If victim is unconscious, perform resuscitation as required:
CIRCULATION:
1. Check for pulse in the victim’s neck or wrist.
WARNING
II Do not apply pressure over the ribs, lower tip of the victim’s breastbone or the abdomen.
12 356-5901(GB) V12 01/17
RECOVERY POSITION:
1. Turn the victim onto the side.
2. Keep the head tilted with the jaw forward to maintain the open airway.
3. Make sure the victim cannot roll forwards or backwards.
4. Check for breathing and pulse regularly. If either stops, proceed as above.
Warning:
II Do not give liquids until victim is conscious.
13 356-5901(GB) V12 01/17
2.11 Hazard Label Legend
Ensure that all of the safety messages are legible. Clean the safety messages or replace them if the words cannot be read or if the
illustrations are not visible. Use a cloth, water and soap to clean the safety messages. Do not use solvents, gasoline, or other harsh
chemicals as these could loosen the adhesive that secures the safety messages. Safety messages that are loosened could drop off
the engine. Replace any safety message that is damaged or missing. If a safety message is attached to a part of the engine that is
replaced, install a new safety message on the replacement part. Your local Dealer can provide new safety messages.
Extended Life Coolant Oil Drain Coolant Drain Diesel Fuel Fill Remote Fuel Fill
Remote Fuel Fill Control Hot Fluid Under Pressure Warning Auto Start
14 356-5901(GB) V12 01/17
X Kg
(X LBS)
Warning -
Four Point Lift is Rated at ’X’ kg Do Not Lift Symbol
Read the manual
Desel Fuel -
Read the manual
15 356-5901(GB) V12 01/17
3. GENERAL DESCRIPTION
This generator set has been designed as a complete package to provide superior performance and reliability.
Each generator set is provided with a Rating Plate generally affixed to the alternator housing / panel enclosure. This label
contains the information needed to identify the generator set and its operating characteristics. This information includes, but is
not limited to, the model and serial numbers, output characteristics such as voltage, phase and frequency, output rating in kVA
and kW and rating type (basis of the rating). The model and serial numbers uniquely identify the generator set.
The diesel engine powering the generator set has been chosen for its reliability and the fact that it has been specifically designed
for powering generator sets. The engine is of the heavy duty industrial type with 4 stroke compression ignition and is fitted with
all accessories to provide a reliable power supply.
The engine electrical system is either 12 or 24 volts DC depending on the size of the set.
The engine cooling system comprises of a radiator, a high capacity pusher fan and a thermostat. The main AC alternator has its
own internal fan to cool the alternator components.
The output electrical power is produced by an alternator fine tuned to the output of this generator set.
The engine and alternator are coupled together and mounted on a heavy duty steel base frame. The base frame incorporates an
integrated or polyethylene fuel tank except for the largest sets (approximately 1,000 kVA and above).
The generator set is fitted with vibration isolators which are designed to reduce engine vibration being transmitted to the
foundation on which the generator set is mounted. These isolators are fitted between the engine/alternator feet and the base
frame. Alternatively, on 4008, 4012 and 4016 powered models the engine/alternator is rigidly mounted on the base frame and
the vibration isolators are supplied loose to be fitted between the base frame and the foundation.
An exhaust silencer is provided loose for installation with the generator sets. The silencer and exhaust system reduce the noise
emission from the engine and can direct exhaust gases to safe outlets.
One of several types of control systems and panels is fitted to control the operation and output of the generator set and to
protect the set from possible malfunctions. Section 5 of this manual provides detailed information on these systems and will aid
in identification of the control system fitted on the generator set.
To protect the alternator, a suitably rated circuit breaker selected for the generator set model and output rating is supplied
mounted in a steel enclosure.
This generator set is designed to operate in ambient temperatures up to 50 deg C and at higher altitudes 6.
Please consult Dealer / Helpdesk for outputs available
17
19. Anti Vibration Mounts*
20. Drag Points
21. Fan Guards
12
* = Opposite side
13
15
II G
enerator sets contain moving
parts and hot surfaces. Wear the
14 17 19 21 appropraite PPE as required.
20
18
16
Figure 3.2 – Typical Generator set Description (this may differ from the Generator set you have received)
Note:
The generator does NOT control power factor. Power factor is determined by the load.
In most applications, loads such as electric motors, solid-state controls, and transformers determine the power factor of the
system. Induction motors usually have a power factor that is no larger than 0.8. Incandescent lighting is a resistive load of about
1.0 power factor, or unity. Solid-state controls, variable frequency drives (VFD), variable speed drives (VSD), and control systems
Uninterruptible Power Supplies (UPS) can operate at any power factor, leading, or lagging. In this case, the power factor can be
between 0.4 and 1.0.
The power factor of a system may be determined by a measurement or by calculation and is displayed on the control panel.
18 356-5901(GB) V12 01/17
4. INSTALLATION, HANDLING AND STORAGE
4.1 General
This section discusses factors important in the effective and safe installation of the generator set.
Selecting a location for the generator set can be the most important part of any installation procedure. The following factors are
important in determining the location:
• Adequate ventilation.
Figure 4.1 – Typical installation showing generator set ventilation
• Protection from the elements such as rain, snow, sleet, wind driven precipitation, flood water, direct sunlight, freezing
temperatures or excessive heat.
• Protection from exposure to airborne contaminants such as abrasive or conductive dust, lint, smoke, oil mist, vapours,
engine exhaust fumes or other contaminants.
• Protection from impact from falling objects such as trees or poles, or from motor vehicles or lift trucks.
• Clearance around the generator set for cooling and access for service: at least 1 metre (3ft 3in) around the set and at least
2 metres (6ft 6in) headroom above the set.
• Access to move the entire generator set into the room. Air inlet and outlet vents can often be made removable to provide
an access point.
• Limited access to unauthorised personnel.
If it is necessary to locate the generator set outside of the building, the generator set should be enclosed in a weatherproof
canopy or container-type housing which is available for all sets.
Figure 4.2 – Typical installation showing generator set access and operator workstation
19 356-5901(GB) V12 01/17
4.2 Outdoor Installation
Installation and handling is greatly simplified when the generator set has been equipped with an enclosure. Two basic types
may be fitted. The first type is a close fitting canopy enclosure. This will be both weatherproof and sound attenuated. The other
enclosure type is a walk-in type container, similar to a shipping container. It may be weatherproof or sound attenuated.
These enclosures provide a self contained generator set system that is easily transportable and requires minimal installation. They
also automatically give protection from the elements and protection from unauthorised access.
Warning:
II Make sure all personnel are out of the canopy or container, if equipped, before closing and latching enclosure doors.
II Enclosures fitted with doors stays or lift off doors (when Applicable) should not be used when wind exceeds 15 mph.
II Before closing canopy or enclosure doors, ensure all obstructions (especially hands and fingers) are clear to prevent
damage or injury.
II For transport purposes, some silencer outlets on generator sets housed in walk-in type enclosures will be fitted with
cover plates. These are to be replaced with the supplied stub pipes complete with fitted rain hood.
II Ensure there is no debris on the base frame prior to starting, as loose items will cause radiator damage.
Because enclosed generator sets are easily transportable and may be installed and operated in a temporary location, many of
the fixed installation details given in this chapter may not apply. The following considerations must be taken into account when
temporarily installing the generator set:
• Locating the generator set where it will be protected from damage and away from the exhaust
fumes of other engines or other airborne contaminants such as dust, lint, smoke, oil mist or
vapours. Sound levels will vary depending on the configuration of the generator set and the
final bolted down installation of the generator set on a flat surface
• Ensure the generator set is not positioned in such a way that it will obstruct the entrance or
exit to the area where the it is situated.
• Locating the generator set on firm, level ground which will not subside or be otherwise
affected by the vibration caused by the operation of the generator set
• Ensuring that fumes from the exhaust outlet will not be a hazard especially when wind
is taken into account.
• Ensure there is enough area around the generator set for access and serviceability.
• Electrical grounding of the generator set at all times, in accordance with local regulations.
• Protecting electrical cables installed between the generator set and the load. If these are laid
on the ground ensure they are boxed in or covered to prevent damage or injury to personnel.
WARNING
II Enclosed generator sets should be installed outside. In the event that the enclosed
generator set is installed inside, adequate fresh cooling air must be provided and that
both engine and hot coolant air exhausts must be ducted outside the building. The
ducting and exhaust pipework must be designed to minimise back pressure which would
have a detrimental effect on generator set performance.
20 356-5901(GB) V12 01/17
4.2.1 Positioning of Walk-in Containers
Proper installation of the container is required if successful generation of power is to be achieved. The following information
must be considered in the selection of the operating site for the container. The containerised generator set must be placed on a
flat surface in order to maintain proper alignment. Containers can be successfully installed on a concrete plinth or level, natural
surface. The foundation must bear the static weight of the module plus any dynamic forces from engine operation.
Warning:
II For generator sets housed in walk-in type containers, crankcase breather outlets terminated at the external face of
the enclosure will be plugged. These must be removed prior to operation.
21 356-5901(GB) V12 01/17
4.3 Moving the Generator set
Prior to any movement or installation of the generator set please review the following steps
II Keep all non-essential personnel clear of the area.
II Load the package and unload the package on a level surface.
II Block the transport vehicle so the vehicle cannot move.
II Keep both the trailer bed and the ramps for the trailer clean. Remove any clay, oil, or other slippery materials.
II If ramps are used, ensure that the ramps are of adequate size and strength. The ramps should be installed at the
proper height and the angle of the ramps should be low.
II Use the lifting eye of the enclosure. Ensure that all the lifting devices have adequate capacity.
II Chain the package or block the package securely before you transport the package.
II Check the height and width of the package for clearance for traveling. Check the weight of the package for load
limitations.
The generator set base frame is specifically designed for ease of moving the set. Improper handling can seriously damage
components.
Warning:
II Always use wood between forks and the base frame to spread the load and also between the forklift carriage and
the side of the canopy to prevent damage.
Figure 4.4 – Transporting a generator set using a forklift truck and forklift trolley
22 356-5901(GB) V12 01/17
1
2
1. Forklift Pockets
2. Oil FIeld Skid
Figure 4.5 – Typical generator set with Oil Field Skid base option
If the generator set will be regularly moved, it should be fitted with the optional Oil Field Skid which provides forklift pockets in
the base frame along with eyes for pulling. The smaller sets have forklift pockets in the base frame as standard.
Warning:
II Please ensure the fuel tank is empty when lifting the generator set to ensure safe and stable lifting.
II Never lift the generator set by attaching to the engine or alternator lifting lugs.
II Ensure the lifting rigging and supporting structure is in good condition and is suitably rated.
II Keep all personnel away from the generator set when it is suspended.
To lift and install the generator set you can use the single / two point lifting points or the lifting points provided on the baseframe.
Points of attachment should be checked for cracked welds or loose nuts and bolts before lifting. A spreader bar is required to
prevent damage to the generator set whilst lifting from the baseframe. It should be positioned over the centre of gravity, to allow
a vertical lift. Generator sets fitted with dual point lift frame, the lifting eyes are positioned either side of the canopy to allow easy
access. The lifting points are positioned as close to the center of gravity of the generator set as is possible. Guide ropes should
be used to prevent twisting or swinging of the generator set once it has been lifted clear of the ground. Place the generator set
down on a level surface capable of supporting its weight.
II Lifting eyes not intended for use shall be shielded with the appropriate lifting eye shield. Each shield shall display a
“Do Not Lift” label. Refer to section 2.11
23 356-5901(GB) V12 01/17
II
Warning
II Please ensure the fuel tank is empty when lifting the generator set to ensure safe and stable lifting.
II Centre of gravity decal is located on the base / canopy of the generator set.
II The centre of gravity may not always be located at the centre of the generator set. The center of gravity will change
depending on package options and also volume of liquid on board . The center of gravity shifting may cause lift
angle to vary between +5° and – 5 ° from horizontal. Ensure that generator set is not lifted if the angle of lift is
outside these values.
II Do not attempt to lift in high winds.
24 356-5901(GB) V12 01/17
1. Spreader Bar
Figure 4.8 – Proper lifting arrangement for installing the generator set (open & enclosed)
25 356-5901(GB) V12 01/17
4.3.1 Approved Lifting Methods for ISO Walk-in Containers
Containers are manufactured to ISO dimensions, ISO 1496–4:1994(E) and ISO 668:1995(E). To ensure the safety of all personnel
involved with the handling of containers, it is important that the correct lifting and handling procedures are employed. The
procedures detailed below are derived from ISO 3874:1997(E) and must be followed at all times.
26 356-5901(GB) V12 01/17
4.4 Foundations and Vibration Isolation
The generator set is supplied on a rigid base frame that precisely aligns the alternator and engine and needs only be bolted down
to a suitably prepared surface.
1. Vibration Isolators
2. Flexible Exhaust Coupling
3
3. Flexible Air Discharge Duct
2
4.4.1 Foundation
A reinforced concrete pad makes the best foundation for the generator set. It provides a rigid support to prevent deflection
and vibration. Typically the foundation should be from 150 mm to 200 mm (6 to 8 inches) deep and at least 150 mm (6 inches)
wider and longer than the generator set. The ground or floor below the foundation should be properly prepared and should
be structurally suited to carry the combined weight of the foundation pad and the generator set. (If the generator set is to be
installed above the ground floor the building structure must be able to support the weight of the generator set, fuel storage and
accessories.) Relevant building codes should be consulted and complied with. If the floor is wet from time to time, such as in
a boiler room, the pad should be raised above the floor. This will provide a dry footing for the generator set and for those who
connect, service or operate it. It will also minimise corrosive action on the base frame.
27 356-5901(GB) V12 01/17
4.5 Storage
Long term storage can have detrimental effects on both the engine and alternator. These effects can be minimised by properly
preparing and storing the generator set.
28 356-5901(GB) V12 01/17
5. CONTROL SYSTEM DESCRIPTION AND TROUBLE SHOOTING
5.1 Control System Description
An electronic control system has been designed and installed to control and monitor the generator set. Depending on the
requirements of the generator set, one of several different standard control systems may be fitted. Other more specialised
systems may be fitted for specific installations in which case separate documentation is provided.
These control systems consist of three major components working together:
Control Panel – provides a means of starting and stopping the generator set, monitoring its operation and output and
automatically shutting down the generator set in the event of a critical condition arising such as low oil pressure or high engine
coolant temperature to prevent major damage to the engine / alternator.
Engine Interface Module (where fitted) - provides switching relays for the Starter Motor Solenoid, Glow Plug and Fuel Solenoid.
Each of these circuits is protected with individual fuses mounted in the module. Individual LED’s illuminate when each circuit is
energised.
Power Output Circuit Breaker - serves to protect the alternator by automatically disconnecting the load in the event of overload
or short circuit. It also provides a means of switching the generator set output.
Warning:
II Do not remove the radiator cap or any component of the cooling system while the engine is running and while the
coolant is under pressure, because dangerous hot coolant can be discharged, posing a risk of personal injury. Do
not add large amounts of cold coolant to a hot system as serious engine damage could result.
Note:
• Diesel engines normally consume lube oil at a rate of 0.25% to 1% of the fuel consumption.
• When adding coolant to the radiator system, always pour slowly to help prevent air from becoming trapped in the engine.
Always top up when engine is cold.
Warning:
II When filling the fuel tank, do not smoke or use an open flame in the vicinity.
3. Check the fuel level – fill as necessary. Drain water from the water separator (if equipped)
29 356-5901(GB) V12 01/17
Warning:
II Before tightening the fan belts, disconnect the battery negative (–) lead to ensure the engine cannot be accidentally
started.
4. Check the condition and tension of the fan and engine alternator belts – tighten as necessary.
5. Check all hoses for loose connections or deterioration – tighten or replace as necessary.
6. Check the battery terminals for corrosion – clean as necessary.
Warning:
II When working with the batteries, do not smoke or use an open flame in the vicinity. Hydrogen gas from batteries is
explosive.
II Do not short the positive and negative terminals together.
7. Check the battery electrolyte level – fill with distilled water as necessary.
8. Check the control panel and the generator set for heavy accumulation of dust and dirt – clean as necessary. These can pose
an electrical hazard or give rise to cooling problems.
9. Check the air filter restriction indicator, if fitted – replace the filter as necessary.
10. Clear the area around the generator set of any insecure items that could inhibit operation or cause injury. Ensure cooling air
ventilation screens are clear.
11. Visually check the entire generator set for signs of leaks from the fuel system, cooling system or lubrication seals.
12. Periodically drain exhaust system condensate traps, if equipped.
13. If fluid containment is incorporated into the baseframe it must be inspected. Any liquids present (fuel, oil, coolant, rainwater or
condensation) should be drained out and disposed of in accordance with local regulations and mandates.
14. Ensure the Alternator Output Circuit Breaker is in the “OFF” (handle down) position.
30 356-5901(GB) V12 01/17
5.2 PowerWizard 1.1, 1.1+ & 2.1 (Quickstart)
1. Display screen
2. AC overview key
3. Engine overview key
4. Main menu or home key
5. Alarm acknowledge key
6. Event reset key
7. Event log key
8. Auto key
9. Stop key
10. Run key
11. Escape key
12. Up key
13. Right key
14. OK or Enter key
15. Down key
16. Left key
31 356-5901(GB) V12 01/17
5.2.3 Basic Operation
START Mode
32 356-5901(GB) V12 01/17
5.2.4 Fault / Alarm Reset Process
1. Fault / Alarm Reset Process 2. Fault / Alarm Reset
Engine Overview key – The Engine Overview key will navigate the display to the first screen of engine information. The Engine
Overview information contains various engine parameters that summarise the operation of the generator set.
(Use the up / down keys to navigate within the Engine parameters).
Main Menu key – The Main Menu key will navigate the display to the main menu screen. Pressing the navigation keys will
allow access to menus at all levels.
33 356-5901(GB) V12 01/17
Control Keys:
RUN – Pressing the Run key will cause the engine to enter the run mode.
AUTO – Pressing the Auto key will cause the engine to enter the auto mode.
STOP – Pressing the Stop key will cause the engine to enter stop mode.
Navigation Keys:
Scroll Up – The Scroll Up key is used to navigate up through the various menus or monitoring screens. The Scroll Up key is also
used during setpoint entry. During numeric data entry the Scroll Up key is used to increment the digits (0–9). If the setpoint
requires selection from a list, the Scroll Up key is used to navigate through the list.
Escape – The Escape key is used during menu navigation in order to navigate up through the menu/sub-menu structure. Each
key press causes the user to move backwards/upwards through the navigation menus. The Escape key is also used to exit/
cancel out of data entry screens during setpoint programming. If the Escape key is pressed during setpoint programming,
none of the changes made on screen will be saved to memory.
Scroll Right – The Scroll Right key is used during setpoint adjustment. During numeric data entry, the Scroll Right key is used to
choose which digit is being edited. The Scroll Right key is also used during certain setpoint adjustments to select or deselect a
check box. If a box has a check mark inside, pressing the Scroll Right key will cause the check mark to disappear, disabling the
function. If the box does not have a check mark inside, pressing the Scroll Right key will cause a check mark to appear, enabling
the function.
Enter / OK – The Enter key is used during menu navigation to select menu items in order to navigate forward/downward in
OK the menu/sub–menu structure. The Enter key is also used during setpoint programming in order to save setpoint changes.
Pressing the Enter key during setpoint programming causes setpoint changes to be saved to memory.
Scroll Down – The Scroll Down key is used to navigate down through the various menus or monitoring screens. The Scroll
Down key is also used during setpoint entry. During numeric data entry the Scroll Down key is used in order to decrement the
digits (0–9). If the setpoint requires selection from a list, the Scroll Down key is used to navigate down through the list.
Scroll Left – The Scroll Left key is used during setpoint adjustment. During numeric data entry, the Scroll Left key is used to
choose which digit is being edited. The Scroll Left key is also used during certain setpoint adjustments to select or deselect a
check box. If a box has a check mark inside, pressing the Scroll Left key will cause the check mark to disappear, disabling the
function. If the box does not have a check mark inside, pressing the Scroll Left key will cause a check mark to appear, enabling
the function.
Event Keys and Indicators:
Yellow Warning Light – A flashing yellow light indicates that there are unacknowledged active warnings. A solid yellow light
indicates that there are acknowledged warnings active. If there are any active warnings, the yellow light will change from
flashing yellow to solid yellow after the Alarm Acknowledge key is pressed. If there are no longer any active warnings, the
yellow light will turn off after the Alarm Acknowledge key is pressed.
Red Shutdown Light – A flashing red light indicates that there are unacknowledged active shutdown events. A solid red light
indicates that there are acknowledged shutdown events active. If there are any active shutdown events the red light will
change from flashing red to solid red after the Alarm Acknowledge key is pressed. Any condition that has caused a shutdown
event must be manually reset. If there are no longer any active shutdown events, the red light will turn off.
Alarm Acknowledge – Pressing the Alarm Acknowledge will cause the horn relay output to turn off and silence the horn.
Pressing the key will also cause any yellow or red flashing lights to turn off or to become solid depending on the active status
of the alarms.
Event Reset Key – Pressing the Event Reset key will reset all events when the control is in the stopped position. However, “Reset
All Events” will not reset “Present” events.
34 356-5901(GB) V12 01/17
Event Log Key – Pressing the Event Log key will navigate to the “Active Events” menu. In order to scroll through the events, use
the up and down keys. After highlighting an event, press the “OK” key to see information about the event such as the SPN and
the FMI.
EMERGENCY STOP Push button – A red lock-down push button that immediately shuts down the generator set and will inhibit
start until the push button has been released by turning it clockwise. Prior to restarting the set, this fault must be reset by
pressing the “stop” button on the module and resetting the fault in the “event log menu”.
Note:
• The PowerWizard must be in stop mode to reset events.
Present events cannot be reset.
35 356-5901(GB) V12 01/17
Shut Down Resetting
A flashing red shutdown light indicates there is an unacknowledged shutdown event. The red shutdown light will change from
flashing red to solid red when the Alarm Acknowledged key is pressed. Once a fault has been checked and the cause rectified,
use the following procedure in order to reset the event:
1. Press the “Stop” key.
2. Enter the “EVENT LOGS” option from the main menu.
3. Select a “Module” from the list.
4. Scroll through the events in order to highlight the event to be reset.
5. Make sure the event status is active (not present).
6. Press the “Enter” key.
7. “RESET” will be highlighted if the condition is no longer present and the control is in stop.
8. Press the “Enter” key again. The fault will clear.
9. Press the “Escape” or “Main Menu” key in order to get back to the main menu.
5.2.7 Security
There are 3 levels of password protection on the PowerWizard control panel. All of the adjustable setpoints are associated with a
specific level of security required to make an adjustment to the parameter. The passwords only affect changing setpoints within
the control panel.
The level of password protection that is required for each setpoint is identified on the parameter setpoint entry screen. A security
level identification number “1”, “2” or “3” next to a padlock symbol is displayed on the parameter setpoint entry screen. A Level
3 security is used for the most secure setpoints and Level 1 security is used for the least secure setpoints. If the PowerWizard is
currently at the required level of protection when viewing a parameter, the padlock will not appear.
If a parameter is displayed with a padlock but no security level identification number next to it, the parameter cannot be changed
from the PowerWizard display and the Dealer must be contacted. Level 1 and 2 passwords are disabled when installed. Level 1
and 2 passwords are user level passwords and can be used if desired.
The PowerWizard 2.1 also has a SCADA password, which can be used to secure remote communications.
To view the security menu:
MAIN MENU > CONFIGURE > SECURITY.
At the top of the security menu the current security level is displayed. Within the security menu are the following options:
DROP TO MINIMUM LEVEL – used to return the current security level to the lowest level set-up. Highlight and press Enter to drop
to minimum security level. If no Level 1 or 2 passwords are set-up the minimum level will be 2. If a Level 2 password is set-up, the
minimum level will be 1 and if a Level 1 password is set-up the minimum level will be 0.
ENTER LEVEL 1 OR 2 – used to enter Level 1 or 2 passwords. Highlight and press Enter to proceed to the password entry screen.
Passwords can be entered using the cursor keys. In PowerWizard, Level 1 and 2 passwords must be different. An entered
password is compared against the stored Level 1 and 2 passwords, if the password is correct the PowerWizard will go to the
corresponding security level.
ENTER LEVEL 3 – used to obtain Level 3 access. The Level 3 security password is reserved for critical setpoints that should only be
changed by a skilled operative. As such you must contact your Dealer if you require a change associated with a Level 3 password.
CHANGING LEVEL 1 PASSWORD – used to set-up, change or disable a Level 1 password. In order to use this feature the control
must be at current security Level 1 or higher. Highlight and press Enter to proceed to the password entry screen. To set-up or
change the password, enter the new password using the cursor keys. Passwords may be 16 digits long. To disable the Level 1
security password, set the password to ‘0’. Press the Enter key to save.
CHANGING LEVEL 2 PASSWORD – used to set-up, change or disable a Level 2 password. In order to use this feature the control
must be at current security Level 2 or higher. Highlight and press Enter to proceed to the password entry screen. To set-up or
change the password, enter the new password using the cursor keys. Passwords may be 16 digits long. To disable the Level 2
security password, set the password to ‘0’. Press the Enter key to save.
CHANGING SCADA PASSWORD (PowerWizard 2.1 only) – used to set-up, change or disable a SCADA password. Highlight and
press enter to proceed to the password entry screen. To set-up or change the password, enter the new password using the cursor
keys. Passwords may be 16 digits long. To disable the SCADA security password, set the password to ‘0’. Press the Enter key to save.
36 356-5901(GB) V12 01/17
5.2.8 Real Time Clock Programming (PowerWizard 2.1)
The real time clock provides information for the time and date of an automatic time based start/stop control. It also provides a
mechanism for time stamps in the event log. The real time clock is not calibrated and is for information only. The date and time
are set by the user.
1. In order to set the time or date format:
MAIN MENU > CONFIGURE > TIME/DATE.
2. To set the time, highlight the time then press the “Enter” key twice.
3. Use the cursor keys to set the time and press the “Enter” key to save. Press the “Escape” key to return.
4. To set the date, highlight the date then press the “Enter” key twice.
5. Use the cursor keys to set the date and press the “Enter” key to save. Press the “Escape” key to return.
6. To set the date format, highlight either the FORMAT DD/MM/YY or FORMAT MM/DD/YY and press the “Enter” key.
7. Use the cursor keys to select the required date format and press the “Enter” key to save.
37 356-5901(GB) V12 01/17
5.2.11 Trouble Shooting Guide for PowerWizard
38 356-5901(GB) V12 01/17
5.3 PowerWizard 2.1+ / 4.1
1. Display screen
2. AC overview key – The “AC OVERVIEW” key will navigate the display to the first screen of AC information. The “AC OVERVIEW”
information contains various AC parameters that summarize the electrical operation of the generator set.
3. Engine overview key – The “ENGINE OVERVIEW” key will navigate the display to the first screen of engine information. The
“ENGINE OVERVIEW” information contains various engine parameters that summarize the operation of the generator set.
4. Main menu key – The “MAIN MENU” key will navigate the display to the main menu directly without having to navigate out of
menus.
5. Alarms acknowledge key – Pressing the “ACKNOWLEDGE” key will cause the horn relay to turn off. The horn relay being
turned off will silence the horn. Pressing the “ACKNOWLEDGE” key will also cause any red or yellow flashing lights to either
turn off or to come on continuously. The “ACKNOWLEDGE” key will also send out a global alarm silence signal on the J1939
Data Link. Annunciators on the J1939 Data Link can be configured to silence their individual horns upon receipt of the global
acknowledge
6. Reset event key – Pressing the “RESET” key will reset all events that can be reset at this time. (Events that are PRESENT cannot be
reset at this time.)
7. Event log – Pressing the “EVENT LOG” key will navigate the display to the event log.
8. Run key – Pressing the “RUN” key will put the generator set into a mode where it will attempt to start the engine, except in
cases where there are any active or present shutdown events.
9. Auto key – pressing the “AUTO” key will cause the engine to enter the “AUTO” mode. The engine will start if the module receives
a start command from a remote-start source..
10. Stop key – Pressing the “STOP” key will put the generator set into a mode where it will stop the engine. Depending on
configuration, the set may run on for a cooldown period before stopping the engine.
11. Escape key – The “ESCAPE” key is used to navigate through the menus. When the key is pressed, the user moves backward
or the user moves upward through the menus. The “ESCAPE” key is also used to exit out of entering data when the user is
programming the setpoints. If the “ESCAPE” key is pressed while the user is programming the setpoints, changes made on the
screen will not be saved to memory.
12. Up key – The “UP” key is used to navigate through the various menus and monitoring screens. The “UP” key is also used when
a setpoint is entered. When entering numeric data, the “UP” key is used to increment the digits (0-9). If the setpoint requires
selection from a list, the “UP” key is used to navigate UP through the list.
13. Right key – The “RIGHT” key is used during setpoint adjustment. The “RIGHT” key is used to select which digit is edited while
entering numeric data. The “RIGHT” key is also used during some setpoint adjustments to select or to unselect a check box. If
a check box has a check mark, the function has been enabled. Pressing the “RIGHT” key will disable the function. Pressing the
39 356-5901(GB) V12 01/17
“RIGHT” key will also cause the check mark to disappear. If the check box does not have a check mark, the function is disabled.
Pressing the “RIGHT” key will enable the function. Pressing the “RIGHT” key will also cause a check mark to appear.
14. OK/Enter key – The “ENTER” key is used to navigate through the menus. When the key is pressed, the user moves forward or
the user moves downward through the menus. The “ENTER” key is also used to save any changes while the setpoints are being
programmed. Pressing the “OK” key during programming the setpoints causes the changes to be saved to memory.
15. Down key – The “DOWN” key is used to navigate downward through the various menus or screens. The “DOWN” key is also
used to program the setpoints. The “DOWN” key is used to decrease the digits when entering numeric data. If the setpoint
requires selection from a list, the “DOWN” key is used to navigate DOWN through the list.
16. Left key – The “LEFT” key is used during setpoint adjustment. The “LEFT” key is used to select the digit that is edited during the
entry of numeric data. The “LEFT” key is also used during some of the setpoint adjustments to select a check box. The key is also
used to unselect a check box. If a check box has a check mark, pressing the “LEFT” key will disable the function. Pressing the
key will also remove the check mark. Pressing the “LEFT” key will also cause the check mark to disappear. If the check box does
not have a check mark, pressing the “LEFT” key will enable the function. Pressing the “LEFT” key will also cause a check mark to
appear.
Alarm Indicators
Yellow Warning Lamp – A yellow warning lamp is located above the “ACKNOWLEDGE” key. A flashing yellow light indicates that
there are active warnings that have not been acknowledged. A continuous yellow light indicates that there are acknowledged
warnings that are active. If there are any active warnings, the yellow light will change from flashing yellow to continuous yellow
after the “ACKNOWLEDGE” key is pressed. If there are no longer any active warnings, the yellow light will turn off after the
“ACKNOWLEDGE” key is pressed.
Red Shutdown Lamp – A red shutdown lamp is located above the “RESET” key. A flashing red light indicates that there are active
shutdowns that have not been acknowledged. A continuous red light indicates that there are active shutdowns that have
been acknowledged. If there are any active shutdowns, the red light will change from flashing red to continuous red after the
“ACKNOWLEDGE” key is pressed. Any condition that has caused a shutdown must be manually reset. If there are no longer any
active shutdowns, the red light will turn off.
40 356-5901(GB) V12 01/17
5.3.2 PowerWizard 4.1 Control Module Description
1. Display screen –
2. F4 Soft key – The function of the “F4” soft key can change depending on which screen is active. The space at the bottom of the
screen immediately above each soft key displays what the function of that soft key will be.
3. F3 Soft key – The function of the “F3” soft key can change depending on which screen is active. The space at the bottom of the
screen immediately above each soft key displays what the function of that soft key will be.
4. F2 Soft key – The function of the “F2” soft key can change depending on which screen is active. The space at the bottom of the
screen immediately above each soft key displays what the function of that soft key will be.
5. F1 Soft key – The function of the “F1” soft key can change depending on which screen is active. The space at the bottom of the
screen immediately above each soft key displays what the function of that soft key will be.
6. Control key – The “CONTROL” key will navigate the display to the control menu.
7. AC overview key – The “AC OVERVIEW” key will navigate the display to the first screen of AC information. The “AC OVERVIEW”
information contains various AC parameters that summarize the electrical operation of the generator set.
8. Engine overview key – The “ENGINE OVERVIEW” key will navigate the display to the first screen of engine information. The
“ENGINE OVERVIEW” information contains various engine parameters that summarize the operation of the generator set.
9. Main menu key – The “MAIN MENU” key will navigate the display to the main menu directly without having to navigate out of
menus.
10. Warning indicator lamp (yellow) – A yellow warning lamp is located above the “ACKNOWLEDGE” key. A flashing yellow light
indicates that there are active warnings that have not been acknowledged. A continuous yellow light indicates that there are
acknowledged warnings that are active. If there are any active warnings, the yellow light will change from flashing yellow to
continuous yellow after the “ACKNOWLEDGE” key is pressed. If there are no longer any active warnings, the yellow light will
turn off after the “ACKNOWLEDGE” key is pressed.
11. Alarms acknowledge key and silence key – Pressing the “ACKNOWLEDGE” key will cause the horn relay to turn off. The horn
relay being turned off will silence the horn. Pressing the “ACKNOWLEDGE” key will also cause any red or yellow flashing lights
to either turn off or to come on continuously. The “ACKNOWLEDGE” key will also send out a global alarm silence signal on the
J1939 Data Link. Annunciators on the J1939 Data Link can be configured to silence their individual horns upon receipt of the
global acknowledge.
12. Shutdown indicator lamp (red) – A red shutdown lamp is located above the “RESET” key. A flashing red light indicates
that there are active shutdowns that have not been acknowledged. A continuous red light indicates that there are active
41 356-5901(GB) V12 01/17
shutdowns that have been acknowledged. If there are any active shutdowns, the red light will change from flashing red to
continuous red after the “ACKNOWLEDGE” key is pressed. Any condition that has caused a shutdown must be manually reset. If
there are no longer any active shutdowns, the red light will turn off.
13. Event reset key – Pressing the “RESET” key will reset all events that can be reset at this time. (Events that are PRESENT cannot be
reset).
14. Event log key – Pressing the “EVENT LOG” key will navigate the display to the event log.
15. Run key – Pressing the “RUN” key will put the generator set into a mode where it will attempt to start the engine, except in
cases where there are any active or present shutdown events.
16. Auto key – Pressing the “AUTO” key will cause the engine to enter the “AUTO” mode. The engine will start if the module receives
a start command from a remote-start source.
17. Stop key – Pressing the “STOP” key will put the generator set into a mode where it will stop the engine. Depending on
configuration, the set may run on for a cooldown period before stopping the engine.
18. Escape key – The “ESCAPE” key is used to navigate through the menus. When the key is pressed, the user moves backward
or the user moves upward through the menus. The “ESCAPE” key is also used to exit out of entering data when the user is
programming the setpoints. If the “ESCAPE” key is pressed while the user is programming the setpoints, changes made on the
screen will not be saved to memory.
19. Up key – The “UP” key is used to navigate through the various menus and monitoring screens. The “UP” key is also used when
a setpoint is entered. When entering numeric data, the “UP” key is used to increment the digits (0-9). If the setpoint requires
selection from a list, the “UP” key is used to navigate UP through the list.
20. Right key – The “RIGHT” key is used during setpoint adjustment. The “RIGHT” key is used to select which digit is edited while
entering numeric data. The “RIGHT” key is also used during some setpoint adjustments to select or to unselect a check box. If
a check box has a check mark, the function has been enabled. Pressing the “RIGHT” key will disable the function. Pressing the
“RIGHT” key will also cause the check mark to disappear. If the check box does not have a check mark, the function is disabled.
Pressing the “RIGHT” key will enable the function. Pressing the “RIGHT” key will also cause a check mark to appear.
21. OK/Enter key – The “ENTER” key is used to navigate through the menus. When the key is pressed, the user moves forward or
the user moves downward through the menus. The “ENTER” key is also used to save any changes while the setpoints are being
programmed. Pressing the “OK” key during programming the setpoints causes the changes to be saved to memory.
22. Down key – The “DOWN” key is used to navigate downward through the various menus or screens. The “DOWN” key is also
used to program the setpoints. The “DOWN” key is used to decrease the digits when entering numeric data. If the setpoint
requires selection from a list, the “DOWN” key is used to navigate DOWN through the list.
23. Left key – The “LEFT” key is used during setpoint adjustment. The “LEFT” key is used to select the digit that is edited during the
entry of numeric data. The “LEFT” key is also used during some of the setpoint adjustments to select a check box. The key is also
used to unselect a check box. If a check box has a check mark, pressing the “LEFT” key will disable the function. Pressing the
key will also remove the check mark. Pressing the “LEFT” key will also cause the check mark to disappear. If the check box does
not have a check mark, pressing the “LEFT” key will enable the function. Pressing the “LEFT” key will also cause a check mark to
appear.
42 356-5901(GB) V12 01/17
Quick Shut Down Resetting
In addition to the above procedure there is also a simplified process for resetting all events. To reset all events:
1. Ensure that the control is in the stopped position.
2. Press the “Reset Event” key from any screen.
3. A confirmation prompt will appear.
4. Press the “OK” key to reset all events on all modules. Press the ‘ESCAPE” key to cancel the reset operation.
Note:
• The PowerWizard must be in stop mode to reset events.
Present events cannot be reset.
Shut Down Resetting
A flashing red shutdown light indicates there is an unacknowledged shutdown event. The red shutdown light will change from
flashing red to solid red when the Alarm Acknowledged key is pressed. Once a fault has been checked and the cause rectified,
use the following procedure in order to reset the event:
1. Press the “Stop” key.
2. Enter the “EVENT LOGS” option from the main menu.
3. Select a “Module” from the list.
4. Scroll through the events in order to highlight the event to be reset.
5. Make sure the event status is active (not present).
6. Press the “Enter” key.
7. “RESET” will be highlighted if the condition is no longer present and the control is in stop.
8. Press the “Enter” key again. The fault will clear.
9. Press the “Escape” or “Main Menu” key in order to get back to the main menu.
5.3.4 Security
There are 3 levels of password protection on the PowerWizard control panel. All of the adjustable setpoints are associated with a
specific level of security required to make an adjustment to the parameter. The passwords only affect changing setpoints within
the control panel.
The level of password protection that is required for each setpoint is identified on the parameter setpoint entry screen. A security
level identification number “1”, “2” or “3” next to a padlock symbol is displayed on the parameter setpoint entry screen. A Level
3 security is used for the most secure setpoints and Level 1 security is used for the least secure setpoints. If the PowerWizard is
currently at the required level of protection when viewing a parameter, the padlock will not appear.
If a parameter is displayed with a padlock but no security level identification number next to it, the parameter cannot be changed
from the PowerWizard display and the Dealer must be contacted. Level 1 and 2 passwords are disabled when installed. Level 1
and 2 passwords are user level passwords and can be used if desired.
The PowerWizard 2.1 also has a SCADA password, which can be used to secure remote communications.
To view the security menu:
MAIN MENU > CONFIGURE > SECURITY.
At the top of the security menu the current security level is displayed. Within the security menu are the following options:
DROP TO MINIMUM LEVEL – used to return the current security level to the lowest level set-up. Highlight and press Enter to drop
to minimum security level. If no Level 1 or 2 passwords are set-up the minimum level will be 2. If a Level 2 password is set-up, the
minimum level will be 1 and if a Level 1 password is set-up the minimum level will be 0.
ENTER LEVEL 1 OR 2 – used to enter Level 1 or 2 passwords. Highlight and press Enter to proceed to the password entry screen.
Passwords can be entered using the cursor keys. In PowerWizard, Level 1 and 2 passwords must be different. An entered
password is compared against the stored Level 1 and 2 passwords, if the password is correct the PowerWizard will go to the
corresponding security level.
ENTER LEVEL 3 – used to obtain Level 3 access. The Level 3 security password is reserved for critical setpoints that should only be
changed by a skilled operative. As such you must contact your Dealer if you require a change associated with a Level 3 password.
CHANGING LEVEL 1 PASSWORD – used to set-up, change or disable a Level 1 password. In order to use this feature the control
must be at current security Level 1 or higher. Highlight and press Enter to proceed to the password entry screen. To set-up or
change the password, enter the new password using the cursor keys. Passwords may be 16 digits long. To disable the Level 1
security password, set the password to ‘0’. Press the Enter key to save.
43 356-5901(GB) V12 01/17
CHANGING LEVEL 2 PASSWORD – used to set-up, change or disable a Level 2 password. In order to use this feature the control
must be at current security Level 2 or higher. Highlight and press Enter to proceed to the password entry screen. To set-up or
change the password, enter the new password using the cursor keys. Passwords may be 16 digits long. To disable the Level 2
security password, set the password to ‘0’. Press the Enter key to save.
CHANGING SCADA PASSWORD – used to set-up, change or disable a SCADA password. Highlight and press enter to proceed to
the password entry screen. To set-up or change the password, enter the new password using the cursor keys. Passwords may be
16 digits long. To disable the SCADA security password, set the password to ‘0’. Press the Enter key to save.
44 356-5901(GB) V12 01/17
5.3.8 Trouble Shooting Guide for PowerWizard
45 356-5901(GB) V12 01/17
5.4 DCP-10 & DCP-20
46 356-5901(GB) V12 01/17
5.4.3 Basic Operation
START Mode
47 356-5901(GB) V12 01/17
5.4.4 Fault / Alarm Reset Process - DCP-10
Alarm / Shutdown
Whenever a warning occurs the LED indicator will flash, but the generator set will not shut down.
Once the issue is resolvedthe Warning LED will automatically turn off.
Whenever a shutdown occurs the LED indicator illuminates.. The system is immediately locked out and the
generator set stops.
This fault can be reset by pressing the STOP Key. This clears the fault, the LED indicator extinguishes and the generator set is no
longer locked out and can be started.
Scroll Button – The scroll button will allow the user to navigate through the various screens and parameters available to them.
Control Keys:
RUN – pressing the Run key will cause the engine to enter the run mode.
AUTO – pressing the Auto key will cause the engine to enter the auto mode.
MANUAL – pressing the Manual key will cause the engine to enter manual mode.
When in parameter setting mode this button will confirm any changes and also exit the configuration menu.
48 356-5901(GB) V12 01/17
Navigation Keys – DCP-20
When in parameter setting mode this button is used to increase value/scroll down menu.
When in parameter setting mode this button is used to decrease value/scroll up menu.
When in parameter setting mode this button is used to enter into submenu/confirm modification.
When in parameter setting mode this button is used to return to the upper menu.
When in parameter setting mode this button is used to modify the next value.
Used to enter or exit parameter settings, by pressing and holding for 2 seconds.
Mute Button – When a failure occurs the alarm buzzer sounds. Pressing the Mute Button will mute the buzzer and the LCD will
display the Mute Icon.
Stop Button – Whenever the generator set is at rest pressing the stop button will reset any alarms that have occurred. It will
not reset any active events. If a warning or shutdown occurs either text or a symbol will appear on the display indicating what
the event is. Please refer to the relevant technical manual for the controller for an accurate description of these events.
When the controller is running normally it cycles through the following data:
49 356-5901(GB) V12 01/17
Display Preferences for DCP-20 Panel
Each page can display multi-row information simultaneously. Pressing will allow the user to scroll to the next page. The display
can also be configured to scroll automatically. When an alarm occurs, the alarm is displayed on the LCD immediately.
When the Generator set is running the LCD scrolls through the screens showing the following data –
operation Description
U=380V I=0A
P=0kW F=50.0Hz
The voltage/current value displayed on this screen is the average value of 3 phases.
SP=1500rpm Bat=25.4V
Press “ “ to scroll to the next page.
OP=4.6Bar TEMP=70⁰C
RUN
V1=220V U12=380V
I1=0A A1=0kVA
This page displays electrical parameters for L1.
P1=0kW PF1=1.00
Press “ “ to scroll to the next page.
Q1=0kVAr
RUN
V2=220V U23=380V
I2=0A A2=0kVA
This page displays electrical parameters for L2.
P2=0kW PF2=1.00
Press “ “ to scroll to the next page.
Q2=0kVAr
RUN
V3=220V U31=380V
I3=0A A3=0kVA
This page displays electrical parameters for L3.
P3=0kW PF3=1.00
Press “ “ to scroll to the next page.
Q3=0kVAr
RUN
G. P=0kW
G. A=0kVA
This page displays Gen power and average power factor.
G. Q=0kVAr
Press “ “ to scroll to the next page.
G. PF=1.00
RUN
Run Hours = 0.0
Counters = 0
This page displays running hours, crank attempt and auxiliary sensor level.
Press “ “ to scroll to the next page.
Fuels = 46% Heat = 40⁰C
RUN
G. kWHr = 0
G. kVArHr = 0
This page displays total active and reactive energy.
Press “ “ to scroll to the next page.
RUN
Relay Outputs:
Relay Outputs refer to the status of configurable relay output. ---0 ----
Digital Inputs refer to the status of configurable inputs.
Digital Inputs:
“0“ indicates an active Ouput or Input.
Press “ “ to scroll to the next page. ---- --0-
RUN
50 356-5901(GB) V12 01/17
5.5 DeepSea Controller
5.5.1 Description
51 356-5901(GB) V12 01/17
5.5.1 Alarm Icons
An icon is displayed in the Alarm Icon section to indicate the alarm that is current active on the controller. In the event of a
warning alarm, the LCD only displays the Alarm Icon. In the event of an electrical trip or shutdown alarm, the module displays the
Alarm Icon and the Stop/Reset Mode button LED begins to flash.
If multiple alarms are active at the same time, the Alarm Icon automatically cycles through all the appropriate icons to indicate
each alarm which is active.
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the
operators attention to an undesirable condition. By default, warning alarms are self-resetting when the fault condition is removed.
However enabling ‘all warnings are latched’ will cause warning alarms to latch until reset manually. This is enabled using the DSE
Configuration Suite in conjunction with a compatible PC.
52 356-5901(GB) V12 01/17
5.5.4 Fault Finding
53 356-5901(GB) V12 01/17
54 356-5901(GB) V12 01/17
5.6 Control System Options and Upgrades
A large variety of options may be fitted to customise the control system to a specific installation. The following sections cover the
use and operation of some of these options.
II To ensure safe operation in the instance where a generator set is ordered and supplied without a factory fitted
control panel, the operator should ensure a compliant** control panel has been connected and tested by an official
FG Wilson Dealer prior to generator set operation.
(**Compliance requirements may vary. All local and application specific requirements should be adhered to.)
5.6.2 Heaters
Immersion type heaters (engine heaters) may be fitted in the engine coolant system to
ensure that the engine is easy to start and able to take load more quickly.
Alternator anti-condensation heaters (alternator heaters) may be fitted to the alternator stator winding to keep them dry in
humid conditions.
Panel anti-condensation heaters (panel heaters) may be fitted in the control panel to keep moisture levels down.
Control switches are not normally fitted but may be fitted as an additional option. With or without control switches, the heaters
are automatically disconnected on engine start up.
55 356-5901(GB) V12 01/17
5.6.4 Meters / Gauges
The following additional meters or gauges may be fitted to the control panel:
• Three ammeters mounted on the panel instead of one ammeter and a selector switch. This allows a continuous indication
of the current flowing in each phase, not applicable for PowerWizard as this module will display all phase currents. (Not
applicable to 26 – 220 kVA product).
• Kilowatt (kW) Meter to provide accurate readings of the load being supplied by the generator set, not applicable for
PowerWizard as the PowerWizard 2.1 can display kilowatts.
• Lube Oil Temperature Gauge to monitor the lubricating oil temperature when the engine is operating. The normal
operating temperature should be approximately 90° – 110°C (195° – 230°F), not applicable for PowerWizard 1.1 and 2.1+ as
the modules will display this.
• Ammeter for Battery Trickle Charger to monitor the current flow to the battery. It is used to observe the charging current
being supplied by the battery trickle charger. When the batteries are fully charged this current will be small
(less than 5 Amps) but with a partially discharged battery this current may be as high as 40 Amps.
56 356-5901(GB) V12 01/17
6. OPERATION
6.1 Priming Procedure for 1100 Series
Warning:
II Please wear appropriate Personal Protective Equipment (Section 2.2) before carrying out any of the following
procedures as the operator will be in direct contact with diesel fuel. There will also be a risk of spillage.
Note:
• If unsure of your engine model please consult your local Dealer.
• Please see section 3.2 / 3.3 on where the fuel fill can be found on generator set
Following fuel filter servicing or draining of the low pressure fuel system for any reason, re-prime the fuel system as follows.
6.1.1 Products fitted with the small Perkins pre-filter / water separator
a
Note:
• Do not open the vent screws (a) when the fuel system is being primed, as diesel fuel will be discharged.
Note:
• The generator set may only be primed when the generator set is stopped and there are no active or present shutdown
conditions.
57 356-5901(GB) V12 01/17
6.1.2 Perkins 1506, 2206, 2506, 2806 Engines fitted with pre-filter / water separator
1. Pre-Filter/Water separator
2. Drain valve (2)
NOTE
• The water separator is under suction during normal engine operation. Ensure that the drain valve is tightened securely to
help prevent air from entering the fuel system.
Water separator bowl should be drained each week
1. Open drain valve(2). The drain valve is a self ventilated drain valve. Catch the draining water in a suitable container. Dispose of
the water properly.
2. Close drain valve(2).
58 356-5901(GB) V12 01/17
6.1.3 Products fitted with the Racor Pre-Filter / Water Separator (Option)
1
1. T Handle
2. Racor Lid
3. Racor Filter
2
59 356-5901(GB) V12 01/17
6.1.3 Troubleshooting
Having completed the designated priming procedure, if the engine does not start, there may be air in the Pressure Regulator
Valve (PRV) return loop hose.
B
A
Figure 6.3 – Tooling (Not supplied) & Pressure Regulator Valve (PRV) return loop hose
1. Close the PRV return loop hose (B). Use Tooling (A) in order to close the PRV return loop hose (B). A typical example of Tooling
(A) is shown in the illustration.
2. Repeat the priming procedure that is applicable to the configuration of the fuel system.
3. Release Tooling (A).
4. Start engine. Allow engine to run until smooth operation has been ensured and the pump is free from air.
60 356-5901(GB) V12 01/17
6.1.4 Starting with Jump Start Cables
WARNING
II Improper jump start cable connections can cause an explosion resulting in personal injury.
II Prevent sparks near the batteries. Sparks could cause vapors to explode. Do not allow jump start cable ends to
contact each other or the engine.
If the installation is not equipped with a backup battery system, it may be necessary to start the engine from an external electrical
source.
After jump starting, the alternator may not be able to fully recharge batteries that are severely discharged. The batteries must be
charged to the proper voltage with a battery charger.
Use a battery that is sourced with the same voltage as the electric starting motor. Use ONLY equal voltage for jump starting. The
use of higher voltage will damage the electrical system.
Ensure that the main power switch is in the OFF position before jump start cables are attached to the engine that is being started.
1. Turn the start switch on the stalled engine to the OFF position. Turn off all accessories.
2. Connect one positive end of the jump start cable to the positive cable terminal of the discharged battery. Connect the other
positive end of the jump start cable to the positive cable terminal of the charging or starting source.
3. Connect one negative end of the jump start cable to the negative cable terminal of the charging or starting source. Connect
the other negative end of the jump start cable to the stalled engine block or to the chassis ground. This procedure helps to
prevent potential sparks from igniting combustible gases that are produced by some batteries.
4. Charge the batteries. The engine will not continue to run after starting if the batteries have not been charged.
5. Start the engine.
6. Immediately after the stalled engine is started, disconnect the jump start cables in reverse order.
Consult your local Dealer for more information.
IMPORTANT: BOTH BATTERIES OR SETS OF BATTERIES MUST HAVE THE SAME VOLTAGES.
DO NOT MIX VOLTAGES
62 356-5901(GB) V12 01/17
7. LOAD TRANSFER PANELS
When the generator set is required to automatically provide switching to standby power in the event of mains failure, an optional
load transfer panel is required. These transfer panels are designed to sense when the mains have failed, signal the generator set to
start, switch the load from the failed mains to the generator set and then switch it back after the mains supply is re-established.
5 1. Generator set
2. Mains
1 3. Load Fed from Generator set
4. Load Fed from Mains
5. Two Wire Control
3
6. Load Transfer Panel
7 7. Load
6
2
63 356-5901(GB) V12 01/17
7.1 Engine Interface Module Description (where fitted)
The Engine Interface Module is a sealed, engine mounted module that provides switching relays for the Starter Motor Solenoid,
Glow Plug and Fuel Solenoid. Each of these circuits is protected with individual fuses mounted in the module. Individual LED’s
illuminate when each circuit is energised.
There are two versions of the Engine Interface Module available:
EIM Basic: The EIM is utilised in conjunction with control panels equipped with overspeed shutdown.
EIM Plus: The EIM plus is used in conjunction with control panels not equipped with overspeed shutdown.
Overspeed Signal (EIM Plus only): The EIM Plus monitors the speed signal from the magnetic pick-up. If the engine speed
rises above a certain pre-setable value, the module sends a zero volt signal to the generator set control panel to activate the
Overspeed Fault circuitry.
The Overspeed Set Point is factory set at 55 Hz for 50 Hz sets and 66 Hz for 60 Hz sets. This can be adjusted using the adjustment
screw accessed through the hole beside the Overspeed Set-up LED. While the engine is running at the rated speed (1500 rpm for
50 Hz or 1800 rpm for 60 Hz) the adjustment screw should be adjusted until the Overspeed Set-up LED just goes out. This sets
the overspeed value at 10% above the speed at which the generator set is operating.
8 7 6 5
Figure 7.3 – Engine Interface Module (EIM)
Warning
II Maintenance and/or replacement of circuit breakers should only be completed by a fully trained technican.
64 356-5901(GB) V12 01/17
8. ELECTRONIC ENGINE FAULT DETECTION FLASH CODES
Perkins 1306–E87 electronic engines automatically record engine faults in the Electronic Control Module (ECM) to assist the
engineer in troubleshooting. The fault codes can be read using the red and amber lamps situated on the top of the relay box, as
shown in the picture below.
1. Relay Box – This interfaces between the Electronic Control Module (ECM) and the control panel.
2. Amber Light – If lit indicates an active fault. Please contact your local Dealership for assistance. The generator set may continue
to run but may be on reduced power.
3. Red Light – Used for flash code reading, this will not light in normal operation.
4. Push Buttons – Push buttons 1 & 0 are used for fault code reading only.
5. Diagnostic Plug – This is used for communication with a laptop / PC. This should only be used by an authorised technician.
Please consult your local Dealership.
Note:
• The engine protection systems e.g. low oil pressure, high coolant temperature, are within the control of the generator set
control panel. These sensors will shut the engine down before the ECM sensors.
65 356-5901(GB) V12 01/17
9. MAINTENANCE
Warning:
II The following procedures should only be carried out by a qualified technician.
A good maintenance programme is the key to long generator set life. Maintenance and service should only be carried out by
qualified technicians. Records of this work should be kept to aid in developing an efficient maintenance programme.
In general, the generator set should be kept clean. Do not permit liquids such as fuel or oil film to accumulate on any internal or
external surfaces or on, under or around any acoustic material, if fitted. Wipe down surfaces using an aqueous industrial cleaner.
Do not use flammable solvents for cleaning purposes.
Any acoustic material with a protective covering that has been torn or punctured should be replaced immediately to prevent
accumulation of liquids or oil film within the material.
Refer to a qualified generator set technician for details of required preventative maintenance.
Warning:
II Ensure personnel have been trained in the handling and proper use of batteries. Always wear the correct personal
protection equipment (PPE) when handling batteries.
II Battery maintenance checks should also be completed as part of your routine maintenance inspections.
II Always wear the appropriate PPE when handling electrolyte. If splashed with electrolyte, immediately flush the
affected area with clean water and seek medical advice.
II Never add undiluted sulphuric acid to a battery.
II Keep batteries upright to prevent electrolyte spillage. Electrolyte is a dilute sulphuric acid and is harmful to the
skin.
II Use tools with insulated handles when removing or fitting the abttery. Never place tools or metal objects across the
battery terminals.
II During charging, the battery gives off explosive gases. Keep the battery in a well ventilated area and away from
naked flames and sparks. Smoking is also prohibited.
Generator set batteries, by law, must not be disposed of with household waste.
Batteries contain hazardous materials and in the charged state, each cell contains electrodes of lead metal (Pb) and lead (IV)
dioxide (PbO2) in an electrolyte of about 33.5% w/w (6 Molar) sulphuric acid (H2SO4). In the discharged state both electrodes
turn into lead (II) sulphate (PbSO4) and the electrolyte loses its dissolved sulphuric acid and becomes primarily water.
It can be damaging to the environment to send these to landfill, burning batteries can also cause atmospheric pollution.
Dealing with lead acid batteries can be hazardous so it is important to follow all safety guidelines.
Batteries are an essential part of the generator set and should be maintained appropriately. Keep the battery area clean and dry
and ensure any vent caps are tight (if fitted).
Clean the battery case with one of the following cleaning solutions:
• A mixture of 0.1 kg (0.2 lb) of baking soda and 1 L (1 qt) of clean water
• A mixture of 0.1 L (0.11 qt) of ammonia and 1 L (1 qt) of clean water
Thoroughly rinse the battery case with clean water.
All battery connections must be kept clean and tight. Use a fine grade of sandpaper to clean the terminals and the cable clamps.
Clean the items until the surfaces are bright or shiny. Do not remove material excessively. Excessive removal of material can
cause a poor connection between the clamps and the battery terminals. Coat the clamps and terminals with grease or other
terminal protector to prevent corrosion.
66 356-5901(GB) V12 01/17
The electrolyte level should be covering the plates/grids (1/2 inch / 13 mm) within the battery to maximize full charge transfer. If
the liquid level is below the plates/grids, only add distilled water; never add battery acid to top up the volume, as the addition of
extra acid will destroy the grids.
It is recommended to check the electrolyte and condition of the batteries every 500 running hours. In high ambient conditions,
it is recommended to use thermal compensation and check electrolyte levels more frequently, for example every 200 running
hours. These checks should also be completed as part of your routine maintenance inspections.
67 356-5901(GB) V12 01/17
9.2 Preventative Maintenance Interval Schedule
Depending on the application of the generator set, requirement for preventative maintenance will vary.
Warning:
II Enclosures fitted with doors stays or lift off doors (when Applicable) should not be used when wind exceeds 15 mph
II Maintenance intervals for the engine may be more frequent than those shown in this section. Please consult your
local dealer for maintenance guidelines specific to your engine
II Operators should only perform the Pre-Start Check tasks detailed in the Control System Description – Section 5.
II The following procedures should only be carried out by a qualified technician.
Daily or at Each Startup:
(For standby generator sets these procedures may be performed weekly.) A walk around inspection should be performed on a
daily basis and prior to starting the engine. The Pre-Start checks contained in Section 5 should be performed during this walk
around.
Every Two Weeks:
(For standby generator sets that have not been run.) Perform an operational check on the generator set by starting and running it
for only 5 minutes.
Every Month:
(For standby generator sets that have not been run on load.) Perform an operational and load check on the generator set by
starting and running the generator set on at least 50% load for 1 to 2 hours.
Drain the Water and the Sediment from Fuel tank – Fuel tanks can be drained from the bottom of the fuel tank by the drain plug
or drain valve (if applicable) or by using a hand pump accessible through the fuel fill pipe or tank access socket. Dispose of the
water properly.
Drain dual wall tank bund area – Dual wall tanks (if applicable), outer bund area should be drained by a hand pump accessible
through the rear access socket located behind the generator, dispose of any removed fluid properly.
Warning:
II Do not run diesel engines at low loads for long periods.
Every Twelve Months or 500 Hours:
Repeat the daily procedures plus the following:
1. Check all control system safety devices by electrically simulating faults.
2. Clean all battery cap vents.
3. Tighten all exhaust connections.
4. Tighten all electrical connections.
5. Start the engine and observe the instrument panel to ensure that all gauges and meters are operating properly.
68 356-5901(GB) V12 01/17
9.5 Welding on or near Generator Sets
When welding is being performed near or on Generator Sets, without precautions and correct procedures, the electrical/
electronic and other components could be severely damaged by the current flow from the welder.
If the engine is electronic, due to the complexity and type of components within the engine ECM, this could be severely
damaged.
Proper welding procedures are necessary in order to avoid damage to the engine ECM, sensors, and associated components.
When possible, remove the component that requires welding from the unit and then weld the component. If removal of the
component is not possible, the correct procedure must be followed.
When welding on a unit that is equipped with an Electronic Engine, the following is considered to be the safest procedure.
Warning:
II Do not ground the welder to electrical components such as the ECM or sensors. Improper grounding can cause
damage to the drive train, the bearings, hydraulic components, electrical components, and other components.
II Do not ground the welder across the centerline of the package. Improper grounding could cause damage to the
bearings, the crankshaft, the rotor shaft, and other components.
II Clamp the ground cable from the welder to the component that will be welded. Place the clamp as close as possible
to the weld. This will help reduce the possibility of damage.
II Perform the welding in areas that are free from explosive hazards.
1. Stop the engine. Turn the switched power to the OFF position.
2. Disconnect the battery cables from the battery. If a battery disconnect switch is provided, open the switch. If possible, remove
the battery completely.
3. Disconnect the connectors from the ECM. Move the harness to a position that will not allow the harness to move back
accidentally and contact any of the ECM pins.
69 356-5901(GB) V12 01/17
NOTES
70 356-5901(GB) V12 01/17
NOTES
71 356-5901(GB) V12 01/17