01 Operator Guide
01 Operator Guide
Operator Guide
E
Copyright
Disclaimer
The contents of this document are subject to revision without notice due to
continued progress in methodology, design and manufacturing.
Ericsson shall have no liability for any error or damages of any kind resulting
from the use of this document.
Contents
1 Operator Guide 1
1.1 Introduction 1
1.2 Getting Started 1
1.3 Starting And Stopping IMA 1
1.4 The IMA Program Group 3
1.5 Working With IMA Network Explorer 4
1.6 Working With Maps 20
1.7 Working With The Alarm List 32
1.8 Fault Management 39
1.9 Performance Management 52
1.10 Inventory Viewer And Editor 62
1 Operator Guide
1.1 Introduction
This chapter describes working procedures for a user who functions in
an operator role. A typical operator daily manages the surveillance of the
network. Basically this means handling the start and stop state of applications
and handling the presentation of status collected from the network under
surveillance.
Start up phase:
• Start up IMA (if not already started), refer to Section 1.3 on page 1.
Iteration phase:
Caution!
If IMA Startup Manager is used to stop and start the system, when a large
number of adaptation with many network elements are configured, adaptations
must be stopped separately before stopping IMA. Failing to do so may lead to
system instability when the “Start IMA” is launched this then would be solved
only by a machine reboot.
To start IMA, right-click on the IMA Startup Manager icon and select the "Start
IMA" menu option from the popup menu, see figure below.
To Stop IMA, right-click on the IMA Startup Manager and select the "Stop IMA"
menu option from the popup menu.
• IMA, start and stop of the IMA core system on the IMA Client Application
only
Optionally the IMA Network Explorer and the IMA Workspace applications can
be started directly from the shortcuts installed on the Windows NT desktop.
IMA applications, such as Workspace, Login, Alarm History and so on, can
also be launched from the IMA Network Explorer, which almost always acts as
the starting point application.
The IMA Network Explorer provides three main dropdown menus: Action, View
and Help.
From the Action menu you perform operations such as Always on top, Find,
Login or Exit. See figure below.
• Find, opens the search dialog. Refer to Section 1.5.8 on page 19 for
further information.
From the View menu you can refresh the network tree display.
• Refresh, updates IMA Network Explorer against the IMA Database. Refer
to Section 1.5.7 on page 17 for further information.
Finally the Help menu provides functions for on line help and the about dialog
box.
The IMA Network Explorer contains an active alarm summary banner that
counts all active alarms, on a severity basis, sent from the IMA Servers. From
the alarm banner you can open the alarm list in the IMA Workspace by pressing
any of the severity buttons. Thereby you can quickly get a list of, for example,
all critical alarms in this IMA Workplace. See figure below.
If the connection with any of the IMA servers is lost, the summary counters will
count the active alarms for still connected IMA Servers. However all buttons will
be coloured blue, indication that an IMA Server connection is lost. When the
connection later is re-established, all counters will be updated and the button
colours will be set back to defaults.
1.5.3 Operations
Operations are performed by selecting one or more items in the tree, right click
and select one of the operations from the displayed popup menu. Which type of
item that is selected determines the scope of the operation, for example if an
operation is selected for a sub-network item, then all NEs in that sub-network
will be affected.
From the IMA Workplace icon the following operations can be performed. See
figure below.
• Alarm List, opens alarm list with all alarms sent to this IMA Workplace.
From the IMA Server icon the following operations can be performed. See
figure below.
• Alarm List, opens alarm list with all alarms related to this IMA Server.
• FM, starts, stops or syncs FM for all NEs on selected IMA Server.
• PM, starts and stops PM for all NEs on selected IMA Server.
From the Sub-network icon the following operations can be performed. See
figure below.
• Alarm List, opens alarm list with all alarms related to selected sub-network.
From the Network Element icon the following operations can be performed.
See figure below.
• Alarm List, opens alarm list with all alarms related to selected NE.
It is also possible to select multiple items and get a menu of operations common
to that category of items. If your selected items for example are all NEs then
you will get a menu of operations common to all NEs. If you also select only
items of a specific type, for example all ERION NEs then the multiple select
menus will also show operations specific for that type of NE.
Multiple select operations exist also for IMA Servers and sub-networks. That
is to view all alarms for both sub-networks SUB01 and SUB02, simply select
the sub-network icons, right mouse click and select the Alarm List operation.
See figure below.
In the Network view four types of icons can be found, representing the IMA
Workplace, IMA Servers, Sub-networks and Network Elements. The colour for
a specific icon (except for the IMA Workplace icons) reflects the status of the
part of the network it represents. The colour also propagates from the children
to its parents in the network hierarchy, meaning that if an alarm is activated on
a network element (resulting in a red colour for the NE icon), then both its
sub-network icon and the IMA Server icon (parent items) will be coloured red.
An operator mostly uses the Network view when surveying the network.
In the System view there also are four types of icons, representing the IMA
Workplace, IMA Servers, Adaptations and Network Elements. Here the colour
of the Network Element and Adaptation propagate directly to the IMA Server,
that is the colour of the Network Element does not propagate to the Adaptation.
The Adaptation icon indicates alarm status for the adaptation itself only.
Adaptation alarms are generated by the adaptation if it fails to operate correctly
for some reason.
Note: For MINI-LINK Manager 6.1, in the Settings tab of the Desktop
Properties screen, the Colours must be set to ’High Color 16 bit’
otherwise the icons are shown with a green background.
Azure RGB (0, 255, 255), lost connection with the NE (FM or PM),
trying to re-connect
Note: If FM and PM are started and you stop the FM on the NEs but the
PM is still active, the Network Element icon shows a colour according
to the last active alarms status.
In the following table will be described the icon look. The colour of the icon is
chosen according to the standard of IMA.
When the IMA Network Explorer is in the ’Refresh Needed’ state, a yellow
blinking text indicates this on the Status bar.
This means that another client has updated the IMA Database and that the IMA
Network Explorer needs to be manually refreshed with the new data, that is
the tree structure in the explorer has changed. A smaller set of operations is
available to permit continued surveillance of the network but no configuration of
the IMA database. These operations are:
• Alarm List, opens alarm list associated to selected item (refer to Section 1.7
on page 32 for further information).
To manually refresh the IMA Network Explorer and get out of the ’Refresh
Needed’ state, select View:Refresh from the IMA Network Explorer menu bar or
press the F5 key. The IMA Network Explorer is then updated with the new data
and continues to work as before it entered the ’Refresh Needed’ state.
The IMA Network Explorer tree can be searched for a specific item. If the item
is found, the explorer tree will be expanded and the item will be highlighted. To
search for an item do the following:
• Open the find dialog by selecting View:Find from the explorer main menu or
by pressing the CTRL+F keys when the explorer window is active.
• Enter the whole alias or part of the alias to search for in the ’Find’ text
box. The search is case insensitive. Entering for example ’ne’ will look up
items with alias containing the sub string ’ne’, ’Ne’, ’nE’ or ’NE’. Press the
Enter key or press the Find Next button to start the search. The explorer
tree will be searched from top to bottom and the first item matching the
searched text will be highlighted. To search for more items matching the
criteria press the Enter key or the Find Next button again. Entering a new
search text will make the search start over from the top of the tree when
Enter or Find Next is pressed.
• Close the dialog by pressing the Esc key or the Cancel button.
Note: When running IMA Workspace in full screen mode, all menus
disappear, type F10 or Alt key to show it again.
The colour of a specific item reflects the status of the network element it
represents. The status of the icon and its children decides the colour of the
icon, for example, if an alarm is activated on a NE then NE, Sub-network and
IMA server items will be red.
Colours in the table below are listed in priority order (for example blue take
precedence over red).
Check mark on
top, all alarms
acknowledged
Overlaid question
mark, alarm
synchronisation
needed
For the body part of the icon, refer to Section 1.6.1.1 on page 21.
Colours in the table below are listed in priority order (for example blue take
precedence over red).
Every time a new alarm or set of alarms arrives the colour of the background
is determined by the severity of the highest new alarm and the central label
indicates the number of the active alarms of the highest severity and the
presence of active alarms of lesser severity.
A coloured balloon displays that some alarms are unacknowledged. The colour
of the balloon is also determined by the highest severity of unacknowledged
alarms and the internal label repeats the number of unacknowledged alarms of
highest severity. If unacknowledged alarms of lesser severity are also present,
the alarm counter on the balloon is terminated by a "+".
The Alarm banner in a map work in the same way as the Alarm banner in the
IMA Network Explorer (refer to Section 1.5.2 on page 6). It displays the number
of alarms on a severity basis and you are able to open the alarm list with a
severity filter by simply pressing any of the buttons. In contrast to the alarm
banner in the IMA Network Explorer, which is a summary of all alarms in the
IMA Workplace, the map alarm banner exist in two versions; One for counting
all alarms for an IMA Server and one for counting all alarms for a sub-network.
The IMA Server banner is inserted in maps associated with IMA Server icons
and the sub-network banner with maps associated with sub-network icons.
By utilising the supplied dynamic objects (map icons) the operator can
easily create his own interactive pictures with icons that match any specific
requirements on the look and feel of the GUI. As an example, the user can
create network maps where NE/EM icons are inserted. When the user clicks on
a icon, a window with the corresponding system inside is opened on the screen.
As default, a set of icons for screen integrated applications is provided.
(1) NOTE! Do NOT shut down by using Close in the control-menu box or ALT-F4.
(1) NOTE! Do NOT shut down by using Close in the control-menu box or ALT-F4.
• From an icon in a map in IMA Workspace. Either directly from a left mouse
click or from the popup menu using a right mouse click. Result as above.
• From the Active Alarm Summary in the IMA Network Explorer. Press any
of the severity buttons. This will open the alarm list with a default filter set
to the severity of the button. For example Pressing the Critical button will
show all alarms, for all IMA Servers, with critical severity.
• From the Alarm banner in a map in IMA Workspace. Same as above, but in
addition the filter will be limited to the particular IMA Server or sub-network.
For example pressing the Major button for a sub-network banner will show
all alarms with Major severity for this particular sub-network.
A typical alarm list is shown in the figure below. Operations on alarms are made
from a popup menu. Some operations, such as alarm deletion, comments and
acknowledge, may be lengthy so a progress bar is used to show the current
progress. There is also a toolbar that controls attributes of the alarm list such as
size, sound and running mode. Below the alarm list is the alarm details window,
visible when a single alarm is selected.
1.7.1 Operations
Clicking on the column header performs sorting. Sorting is supported for the
following columns:
• Server
• Source
• AO Type
• Severity
• Alarm Id
You may change the alarm comment as many times as needed. An alarm
comment can be deleted by writing a space character to it. Writing an alarm
comment always causes a new entry in the alarm log to track which operator
who made the changes.
To view the comment for an alarm select it from the alarm list and the comment
text is visible in the alarm details window.
Note that this operation may take some time if multiple alarms are selected.
The current progress of the operation is displayed in the progress bar.
• Server
• Source
• AO Type
• AO Id
• Probable Cause
• Severity
• Type
In addition filter can also be set for sub-network, which is not a visible column
in the alarm list.
When a value greater than 5 is configured (see configurator guide to know how
to do this) the following will be true instead.
The subnetwork field from the filter alarm dialog will work only using subnetwork
ids, selection base on the subnetwork alias will not be possible any more.
*SUB0001*
*SUB00*
Selecting one or more alarms and then Filter from the popup menu will display
the following dialog:
Use the checkboxes to the left for enabling the different filtering options.
Normally you never edit the text in the edit fields, except for Date & Time.
Change these fields if a filtering on larger time span is wanted.
Use the Apply button, instead of the OK button, if you want the filter to take
affect, but still want the filter dialog box to remain open.
Use the toolbar to reset the filter. Refer to Section 1.7.1.11 on page 38.
You can send one or more selected alarms to the default printer using the
Print function from the popup menu.
Select Silence Alarm Horn from the popup menu to temporary silence the
horn. The horn starts beeping again when a new alarm becomes active or
when the operator acknowledges an alarm.
To turn off the alarm horn, press the Enable/Disable button in the toolbar.
This operation displays additional information about an alarm in the alarm list.
Select a single alarm and the additional information is visible in the alarm
details window below the alarm list.
In addition you can select Details from the popup menu. This is mainly used
when the alarm list is in max size (thereby there is no room left for the details
window) or when the related alarms list is visible.
This operation starts the local manager associated to a specific NE. Select an
alarm in the alarm list and then Local Manager from the popup menu.
You can open the map associated with the sub-network that directly contains
the alarming NE by selecting Map from the popup menu.
This operation views alarms grouped together by the configurator into the
selected alarm. Grouping of alarms is available for customers that bought the
IMA-ERIONtm SNM functionality.
Select an alarm (called root alarm) in the alarm list and then click on the
Related Alarms from the popup menu. All sub alarms related to the root alarm
are shown in the sub alarm list opened. See figure below:
When all group alarms that are related to a sub alarm have been acknowledged
and ceased the sub alarm also disappears. Sub alarms cannot be manually
deleted. Supported operations, from a popup menu, are open the alarm details
and start the local manager.
One or more of the alarms can be deleted from the IMA Server by selecting
the alarms (multiple alarms using the ’shift’ and ’ctrl’ keys) and then Delete
from the popup menu.
Note that this operation may take some time if multiple alarms are selected.
The current progress of the operation is displayed in the progress bar.
The filter can reset to default (for example filter set as when the alarm list was
opened, refer to Section 1.7 on page 32) by pressing the Reset button in the
toolbar. See figure below:
You can pause or resume new alarms from being displayed in the alarm list by
pressing the Pause/Resume buttons in the alarm list toolbar. See figure below.
The alarm list will also be automatically paused upon a multiple select of alarms,
and in then automatically resumed at a single click with the left mouse button.
The alarm list has a grid function, which can be enabled from the Grid button in
the toolbar. See figure below:
The alarm list can be resized using the two size buttons in the alarm list toolbar.
See figure.
In max size there is no room left for the alarm details window or the related
alarm list.
The alarm horn can be enabled to give an audible warning to the operator when
there are alarms in the system. On new alarm the alarm horn gives a beep
about once per second. When the user acknowledges an alarm in the alarm list
the beep rate changes to about once every other second. When the system is
free from alarms the horn silences.
To enable the alarm horn, press the Enable Alarm Horn button in the alarm
list tool bar. See figure below:
Use the popup menu to temporary silence the Alarm Horn. Refer to Section
1.7.1.6 on page 36.
Figure 29
By starting the Fault Management application for a NE, active alarms are able
to propagate from the NE to the IMA database (A). The operator can monitor
the active alarms by viewing the alarm list or observe the status of the different
network levels in the IMA Explorer or in the maps (B). Alarms, user events
and system events are stored in the IMA server history log and in the FM
database (C). The alarms are also distributed to all IMA Clients connected to
the IMA server and are stored in their local history logs as well. Alarms can
also be sent to a printer (D).
Start of FM is accomplished by right clicking the item (in IMA Network Explorer
or map in IMA Workspace) and then selecting FM:Start from the menu. See
figure below. Use FM:Stop to disable the alarm reporting. This means that the
item now starts reporting alarms to the IMA system. The scope of the operation
is determined from the type of item (IMA Server/adaptation/sub-network/NE)
that is selected. For example if made from a sub-network item then all NEs
within that sub-network will be affected. Start/Stop FM is also available as
a multiple select command in the IMA Network Explorer if all selected items
are NEs.
The Alarm List has to be synchronised mainly when you start or when the
connection between the IMA and the NE has been down. The need of
synchronisation is indicated to the user by an overlaid question mark in the NE
icon in the map. It is also indicated in the Status window for the NE when the
command response is "Alarm synchronisation needed." To open the status
window for a NE, right click on the item and select Status.
IMA can automatically synchronise the alarm list with the NE. Automatic alarm
synchronisation on FM start is enabled by default for the NEs (the Auto Sync
option in the NE Properties dialog is set). IMA can also be configured, using
the Auto Start option, to perform automatic alarm synchronisation when the
connection with a NE has been down and is re-established. This is also enabled
by default. See the Configuration Guide section 4.4.3.
1.8.3 Realign
The first time FM application is started for a NE or when the NE type has been
changed from a Local Manager, IMA needs information of what type of NE to
survey and how this NE is configured.
By right clicking on the item (in IMA Network Explorer or map in IMA
Workspace) and selecting the FM:Realign from the menu this information is
retrieved The scope of the operation is determined from the type of item (IMA
Server/adaptation/sub-network/NE) that is selected. For example if the realign
operation is made from the SMUX adaptation, then all NEs in that adaptation
will be affected. Realign is also available as a multiple select command in the
IMA Network Explorer if all selected NEs are of the same type.
1.8.4 AlarmWatchDog
In order to make more efficient the active alarms handling, the AlarmWatchDog
feature is provided. It manages the alarms flow according to the following
behaviour:
• When the number of ceased alarms not acknowledged yet is greater than
1000 a warning window will be activated and the operator will be asked to
acknowledge the alarms. This window if dismissed will be shown after
one minute until the number of alarms ceased not acknowledged is less
than 1000.
• When the number of total active alarms is greater than 7000 the system will
show a warning window asking the operator to reduce the number of active
alarms using the alarm suppression at adaptation level.
• When the number of total active alarms is greater than 8000 the system will
show a warning telling the operator that exceeding number of alarms will be
automatically be deleted according to the lowest severity and oldest time in
first. However the alarms will still be available using the alarm history log.
When IMA wants to make the operator aware of some problem regarding the
operation of the IMA system it generates a system alarm. The table below
describes these system alarms.
1.8.6 FM Report
Alarm and event information in the alarm history log can be viewed in the FM
Alarm History viewer.
Start up the FM report application from the IMA Network Explorer by right
clicking on the ’Workplace’ icon and select Reports:FM from the menu. A
server selection dialog will be shown to the user if several IMA servers are
configured.
The alarm list is sorted with the ’DateIn’ column by default. Clicking on a
column header can change the active sorting column. Clicking twice on a
column header alters the sorting order.
The alarm list can be saved on file by selecting File->Save on a text csv or XML
file. The alarm list can also be printed by selecting File->Print.
It is possible to change between the normal grid view and a chart view. Alter
between the two views with View->Chart respective View->Grid.
The same result we have if click on "Graph" and "Text" button. Clicking on
"Text " button will be possible to show the Graphical and Textual data
respectively.
It is possible to change the chart layout by right clicking in the dialog. For
example the font size can be changed and if the chart should be 2 or 3
dimensional.
The ’*’ character can be used in the free-text fields to match zero or several
characters, for example ’STA*’ matches ’STA’, ’STATUS’, ’STATE’ and so on.
It is possible to select an alarm in the list, right-click and select ’Preset And Show
Filter…’. The Filter Settings dialog is then opened with the alarm data pre-set.
This operation is used to customise the colour settings in the alarm list. The
colour setting is based on the alarm severity. The dialog is opened with
Options->Colour Settings.
The IMA PM Viewer application enables the operator to create PM reports. The
PM data is collected from IMA PM databases. Please take notice of these hints
before you start working with IMA PM Viewer.
The IMA PM Viewer requires a printer to be installed on the machine you are
operating from, if you will make printouts of your reports.
In order to get the total picture of the performance of a network, the IMA PM
Viewer provides the possibility of creating different kinds of reports.
The PM data originates from equipment that has been configured to measure
PM values. Utilising a local configuration tool (a local manager) you may
typically make configuration changes in the device. When an operator has
started the PM data collection, the collected PM data is stored in the PM
Database.
In order to make reports and present the collected PM data for the user, an
IMA PM Viewer is used.
The PM data is stored in (in accordance with G.783, G.784, G.821, G.826):
• BBE
• EB
• ES
• SES
• UAS
• BER
• CV
• OFS
• PSC
• PSD
• CSES
• PJE
• PJE+
• PJE-
If there are problems in the network and the user wants to identify which NE
(equipment) generates the problems, the specific equipment can be selected
and the viewed report might give the answer.
The date and time filter will be default set to current day and current hour.
Note: Only adaptations that has received any PM-data is visible in the
PM-viewer.
Table 27 PM Viewer
List box control Comment
Server All connected IMA servers are listed, each server has
a PM database. Select the one you will work against.
Adaptations Adaptations that have stored PM data at the selected
server. Select the adaptation to work with.
Network Elements Lists all available network elements for the selected
adaptation. Select one or several to work with.
Table 27 PM Viewer
Objects Lists all available objects for all selected network
elements. Select the object you will work with.
Values Lists all PM values stored for the previous selections
done. Select one or several items.
Note: Chart and List tabs do not show any data until F5 (Refresh) is pushed.
Select the menu choice File - Print, a report with your selection and filter will be
printed at your default printer.
• The chart
• A data list
Select the menu choice File - Save As to save your selected and filtered
data as:
• A comma delimited file, for further post processing with Microsoft Excel or
similar product
• XML file, for further post processing with a tool handling data saved in
XML format
When finished with the Report Generation, select the menu choice File - Close.
Inventory data contained within the IMA Inventory Database can be viewed and
edited using the inventory viewer and editor (below referred to as inventory
viewer).
Start up the inventory viewer application from the IMA Network Explorer by right
clicking on the ’Workplace’ icon and select Reports: Inventory from the menu.
1.10.2 Overview
The main window of the Inventory viewer will show the inventory database as a
spreadsheet. This allows a user with the appropriate permission to edit values
in the database.Figure 51 on page 64 Inventory Viewer overview and Table 30
on page 64 Functionality description show and describe the functionality of
the main window.
In the Inventory viewer there are 7 different ways to view the data in the
inventory database. Of these 7 there are 3 hierarchical views and 4 basic views.
Hierarchical views represent logical relationships in the inventory database
and consist of two different basic views. A view is selected using the View
Selector. The differences between the views are summarised in Table 31 on
page 66 Database views.
• To edit the data in the database double click on a cell in the spreadsheet or
start typing when standing with the cursor over the selected cell. To save
the entries press Return, Tab or click on any other cell in the spreadsheet;
to cancel press Esc.
• To clear a cell contents select Edit->Delete, select ’Clear current cell and
press Ok. Note that some columns are locked and can neither be edited
nor cleared. The names of these columns are found in Table 32 on page
66 Locked columns.
The editing wizard provides easier ways to edit, add and delete than the
spreadsheet.Figure 54 on page 68 The Editing wizard and Table 33 on page 68
show and describe the functionality of the wizard.
In the filter settings dialog filtering parameters can be specified. The inventory
viewer has 3 separate filters, each filtering different views. The filters and the
corresponding views are shown in Table 34 on page 69. Figure 55 on page 69
The Filter settings dialog and Table 35 on page 70 show and describe the
functionality of the dialog.
Example: If you want to filter out Network Elements with neAlias OLA2 or OTM4,
you start by choosing the NetworkElements tab. Then you click the enable
filter checkbox next to the parameters list and continue by clicking the checkbox
next to neAlias. For the first expression you select ’=’ in the operator selector,
edit ’OLA2’ in the string field and select OR in the logic operator selector. To
add the next expression, click the Add button, select ’=’ in the operator selector,
edit ’OTM4’ in the string field and select ’<none>’ in the logic operator.
Since the Inventory viewer only shows the Network Elements currently existing
in IMA, these have to be ’discovered’ by Inventory.exe and added to the
Inventory database before any manual editing can take place. Thus, it is not
possible to insert new Network Elements manually using the inventory viewer.
Below is an example how to manually add data to an existing Network Element.
NE : 620.1
1 Start the wizard by clicking the editing wizard button in the toolbar or by
choosing ’editing wizard’ in the edit menu.
2 In the wizard, choose the node name and neAlias of the Network Element
you want to edit from the drop-down menus. If there are two or more NEs
with the same alias, neName has to be chosen as well.
3 In the ’Common’ frame under the ’Network Element’ tab enter the ACTIVE
VERS. value ’S39-0322/07.03.12’ in the ’version’ box and the NE value
’620.1’ in the ’userLabel’ box.
4 Click on the ’Equipment’ tab. This is where the data of the cards in the
network element is entered.
2 Enter ’NE value ’620.1’ and enter the ACTIVE VERS. value
’S39-0322/07.03.12’ in the ’userLabel’ and ’version’ column respectively
on the row containing the node name and neAlias of the NetworkElement
you want to edit.
3 Select the ’Equipment - Common’ view in the view selector and answer
’yes’ on the question whether to save the changes.
4 Select the node name and neAlias of the NetworkElement you want to
edit from the dropdown menu on the star marked row in the ’node’ and
’neName’ column respectively.
5 Enter ’1’ in the position column (card is in slot 1), enter the BANK 1 value
’S38-0473/08.10.01’ in the ’version’ column, ’STM-4 Line W A-Slot 1’ in the
’userLabel’ column, the SERIAL NUMBER value ’MC99GUT531’ in the
’serialNumber’ column and the HARDWARE VERS. value ’131-8681/73.03’
in the ’firmwareRev’ column.
6 Select the ’Equipment - Parameters’ view in the view selector and answer
’yes’ on the question whether to save the changes.
7 Select the node name and neAlias of the NetworkElement you want to
edit from the dropdown menu on the star marked row in the ’node’ and
’neName’ column respectively.
8 Enter ’1’ in the ’position’ column, ’Boot eprom’ in the ’param’ column and
’S38-0328/01.02’ in the ’value’ column.
10 Use the same procedure (step 4-9) to enter the data of the card in slot 2