Winda Motor - Load Flow Report

This document contains a load flow report for a power system with 7 buses (Bus1 to Bus7) and 1 generator (Gen1) at different time steps. At time 0, Bus1 is voltage regulated at 13.8kV. Gen1 is not generating any power. The loads and power flows between buses are reported. At time 0.1, the voltages and power flows have changed from the initial conditions due to increased loads. Bus1 voltage is now regulated at 99.7% and Gen1 is generating a small amount of power. Load and power flows are reported. This report provides the key parameters of the power system at different time steps, including voltages, generation, loads and

Uploaded by

Lody
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views

Winda Motor - Load Flow Report

This document contains a load flow report for a power system with 7 buses (Bus1 to Bus7) and 1 generator (Gen1) at different time steps. At time 0, Bus1 is voltage regulated at 13.8kV. Gen1 is not generating any power. The loads and power flows between buses are reported. At time 0.1, the voltages and power flows have changed from the initial conditions due to increased loads. Bus1 voltage is now regulated at 99.7% and Gen1 is generating a small amount of power. Load and power flows are reported. This report provides the key parameters of the power system at different time steps, including voltages, generation, loads and

Uploaded by

Lody
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Project:

ETAP Page: 1
12.6.0H
Location: Date: 30-10-2018
Contract: SN:
Engineer: Revision: Base
Study Case: MS
Filename: winda 2 motor Config.: Normal

LOAD FLOW REPORT @ T = 0.000-

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp % PF % Tap

* Bus1 13.800 100.000 0.0 0 0 0 0 Bus2 4.896 3.093 242.3 84.5

Bus3 1.281 0.399 56.1 95.5

U1 -6.176 -3.492 296.8 87.1

Bus2 4.160 98.362 -1.4 0 0 4.322 2.449 Bus4 0.566 0.476 104.3 76.5

Bus1 -4.887 -2.926 803.7 85.8

Gen1 0.000 0.000 0.0 0.0

Bus3 4.160 99.771 -0.4 0 0 0 0 Bus6 1.280 0.390 186.2 95.7

Bus1 -1.280 -0.390 186.2 95.7

Bus4 4.160 97.148 -0.8 0 0 0 0 Bus2 -0.554 -0.476 104.3 75.9

Bus5 0.554 0.476 104.3 75.9

Bus5 0.480 96.024 -1.4 0 0 1.792 0.816 Bus4 -0.553 -0.464 904.2 76.6

Bus7 -1.239 -0.352 1613.3 96.2

Bus6 4.160 97.108 0.1 0 0 0 0 Bus3 -1.243 -0.388 186.2 95.5

Bus7 1.243 0.388 186.2 95.5

Bus7 0.480 96.024 -1.4 0 0 0 0 Bus6 -1.239 -0.352 1613.3 96.2

Bus5 1.239 0.352 1613.3 96.2

* Gen1 4.160 98.362 -1.4 0 0 0 0 Bus2 0.000 0.000 0.0 0.0

* U1 13.800 100.291 0.3 6.177 3.532 0 0 Bus1 6.177 3.532 296.8 86.8

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
Project:
ETAP Page: 2
12.6.0H
Location: Date: 30-10-2018
Contract: SN:
Engineer: Revision: Base
Study Case: MS
Filename: winda 2 motor Config.: Normal

LOAD FLOW REPORT @ T = 0.100+

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp % PF % Tap

* Bus1 13.800 99.773 0.0 0 0 0 0 Bus2 5.100 3.424 257.6 83.0

Bus3 1.810 2.872 142.4 53.3

U1 -6.909 -6.296 392.0 73.9

Bus2 4.160 97.963 -1.5 0 0 4.315 2.445 Bus4 0.812 0.870 168.6 68.2

Bus1 -5.090 -3.234 854.4 84.4

Gen1 -0.036 -0.081 12.6 41.2

Bus3 4.160 98.294 -0.5 0 0 0.577 2.235 Bus6 1.230 0.579 191.9 90.5

Bus1 -1.807 -2.814 472.2 54.0

Bus4 4.160 96.208 -0.4 0 0 0 0 Bus2 -0.782 -0.869 168.6 66.9

Bus5 0.782 0.869 168.6 66.9

Bus5 0.480 94.193 -1.3 0 0 1.779 0.811 Bus4 -0.778 -0.839 1461.0 68.0

Bus7 -1.001 0.028 1278.5 -100.0

Bus6 4.160 95.686 0.1 0 0 0 0 Bus3 -1.190 -0.578 191.9 90.0

Bus7 1.190 0.578 191.9 90.0

Bus7 0.480 94.193 -1.3 0 0 0.185 0.567 Bus6 -1.186 -0.539 1663.4 91.0

Bus5 1.001 -0.028 1278.5 -100.0

* Gen1 4.160 98.362 -1.4 0.036 0.081 0 0 Bus2 0.036 0.081 12.6 41.0

* U1 13.800 100.291 0.3 6.911 6.366 0 0 Bus1 6.911 6.366 392.0 73.6

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
Project:
ETAP Page: 3
12.6.0H
Location: Date: 30-10-2018
Contract: SN:
Engineer: Revision: Base
Study Case: MS
Filename: winda 2 motor Config.: Normal

LOAD FLOW REPORT @ T = 7.000+

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp % PF % Tap

* Bus1 13.800 99.980 0.0 0 0 0 0 Bus2 4.954 3.112 244.8 84.7

Bus3 1.655 0.621 74.0 93.6

U1 -6.610 -3.733 317.7 87.1

Bus2 4.160 98.331 -1.4 0 0 4.321 2.449 Bus4 0.638 0.498 114.2 78.9

Bus1 -4.946 -2.941 812.1 86.0

Gen1 -0.013 -0.006 2.1 91.6

Bus3 4.160 99.631 -0.5 0 0 0.361 0.183 Bus6 1.293 0.423 189.6 95.1

Bus1 -1.655 -0.606 245.5 93.9

Bus4 4.160 96.964 -0.8 0 0 0 0 Bus2 -0.624 -0.497 114.2 78.2

Bus5 0.624 0.497 114.2 78.2

Bus5 0.480 95.778 -1.5 0 0 1.790 0.816 Bus4 -0.623 -0.483 989.8 79.0

Bus7 -1.167 -0.332 1524.2 96.2

Bus6 4.160 96.936 0.0 0 0 0 0 Bus3 -1.255 -0.421 189.6 94.8

Bus7 1.255 0.421 189.6 94.8

Bus7 0.480 95.778 -1.5 0 0 0.083 0.051 Bus6 -1.251 -0.383 1642.8 95.6

Bus5 1.167 0.332 1524.2 96.2

* Gen1 4.160 98.362 -1.4 0.013 0.006 0 0 Bus2 0.013 0.006 2.1 91.6

* U1 13.800 100.291 0.3 6.611 3.779 0 0 Bus1 6.611 3.779 317.7 86.8

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)

You might also like