0% found this document useful (0 votes)
355 views2 pages

Cable 182911 Datwyler

This document provides information about a shielded copper data cable that is suitable for transmitting digital and analog voice, video, and data signals. It exceeds the requirements for Category 7 cables and provides excellent shielding through individually screened cable pairs and an overall foil screen. The cable can be used for applications up to 600 MHz and for Power over Ethernet. It has a flame retardant orange sheath and meets various industry standards for cable performance and testing.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
355 views2 pages

Cable 182911 Datwyler

This document provides information about a shielded copper data cable that is suitable for transmitting digital and analog voice, video, and data signals. It exceeds the requirements for Category 7 cables and provides excellent shielding through individually screened cable pairs and an overall foil screen. The cable can be used for applications up to 600 MHz and for Power over Ethernet. It has a flame retardant orange sheath and meets various industry standards for cable performance and testing.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

COPPER DATA CABLES, SHIELDED

Data cable F/FTP Cat.7 AWG23


CU 7052 4P / 2x4P F8

Drain wire Wire


Tinned 1.6 mm Ø
copper wire

Outer sheath Screen Screen Inner conductor


FRNC/LS0H Alu PETP foil pair AWG23
orange RAL 2003 Alu PETP foil Bare copper wire

PRODUCT INFORMATION
Copper

FEATURES Electrically and mechanically high-quality Cat.7 data cable - exceeds the requirements
of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-4-1.
Excellent shielding effect due to individually screened pairs and overall foil screen.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.

APPLICATIONS Data cable for structured premises cabling.


For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class F applications (600 MHz) in accordance
with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV)
Fibre Optics

in accordance with IEC 15018.


Applicable for Power over Ethernet (PoE) / PoE+.

VERSIONS
Cabinets & Racks

Article No. Dimension Sheath Sheath Ø Weight Cu weight Fire load PU


n x n x mm (AWG) mm kg/km kg/km kWh/m MJ/m
182911 4 x 2 x 0.57 (AWG23) FRNC/LS0H 1) 7.4 60 31.1 0.16 0.57 1000 m drum
182912 2 x (4 x 2 x 0.57 (AWG23)) FRNC/LS0H 1) 7.4 x 15.6 120 62.2 0.32 1.14 500 m drum
Data Centre

1)
FRNC/LS0H = Flame Retardant Non Corrosive / Low Smoke Zero Halogen
Wireless
Multimedia

CU 7052 4P/2x4P 0712/e


General Information

42 Subject to technical modification.


COPPER DATA CABLES, SHIELDED
Data cable F/FTP Cat.7 AWG23
CU 7052 4P / 2x4P F8

ELECTRICAL CHARACTERISTICS

CATEGORY 5e 6 6A 7
Frequency [MHz] 1 4 10 100 250 500 600 862
Attenuation [dB/100m] 1,9 3,7 5,6 17,9 28 41 46 54
NEXT [dB] 98 98 98 98 98 90 88 81
PS NEXT [dB] 95 95 95 95 95 87 85 78
ACR-N [dB] 96 94 92 80 70 56 42 27
PS-ACR-N [dB] 93 91 89 77 67 53 39 24
ACR-F [dB] 96 96 96 76 68 54 43 35
PS-ACR-F [dB] 93 93 93 73 64 51 40 32
Return loss [dB] 24 28 31 31 26 24 23 20
These performance data are typical measured values.

Copper
[dB]
140
Loop resistance at 20° C: 140 Ω/km
Mutual capacitance: 42 pF/m 120
1 NEXT 7052
Impedance at 100 MHz: 100 Ω ±5 Ω 1 2 NEXT
Coupling attenuation 100
EN 50288-4-1
(limit curve of critical state -
80
IEC 61156): ≥ 75 dB 2 3 Attenuation
Near end unbalance att. LCL: > 40 dB 60
EN 50288-4-1

Delay Skew: 12 ns/100 m 4


40 4 Attenuation 7052
NVP: 81 %

Fibre Optics
20 3

0
1 [MHz] 10 100 1'000 10'000

CU 7052 4P CU 7052 2x4P F8


MECHANICAL Bending radius (flat side) during draw-in: ≥ 60 mm ≥ 60 mm
CHARACTERISTICS permanently installed: ≥ 30 mm ≥ 30 mm
Tensile strength: ≤ 110 N ≤ 220 N
Crush resistance: ≥ 1000 N/10 cm ≥ 1000 N/10 cm
Impact: ≥ 10 impacts ≥ 10 impacts
Temperature range during installation: 0° C to + 50° C 0° C to + 50° C

Cabinets & Racks


in operation: -20° C to + 60°C -20° C to + 60° C

GENERAL CHARACTERISTICS Wire colour code white/blue


white/orange
white/green
white/brown Data Centre
in accordance with IEC 60189 and IEC 60708

Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»

Zero halogen,
Wireless

non corrosive gases IEC 60754-1/-2, EN 50267-2-1/-2-2, VDE 0482-267-2-1/-2-2


Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24, EN 50266-24 Cat. C, VDE 0482-266-2-4 Cat. C
Smoke density IEC 61034-1/-2, EN 61034-1/-2 (EN 50268-1/-2),
Multimedia

VDE 0482-1034-1/-2 (VDE 0482-268)-1/-2)


Power over Ethernet plus IEEE 802.3at
EMC shielded
Cat./Class better than Cat.7 / Class F
General Information

Subject to technical modification. 43