Eolo Maior KW 0093 GB

EOLO Maior kW is the wall-mounted instant boiler with sealed chamber and forced draught. It's approved for operation both indoors and outdoors in partially protected places. It is available with 24 kW, 28 kW and 32 kW power ratings.

Uploaded by

sisf
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
332 views28 pages

Eolo Maior KW 0093 GB

EOLO Maior kW is the wall-mounted instant boiler with sealed chamber and forced draught. It's approved for operation both indoors and outdoors in partially protected places. It is available with 24 kW, 28 kW and 32 kW power ratings.

Uploaded by

sisf
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

EOLO Maior kW Export

EOLO Maior kW VIP Export


EOLO Maior kW X Export
Wall-mounted instant boilers

EOLO Maior kW is the wall-mounted boiler with sealed


chamber and forced draught that's approved for operation
both indoors and outdoors in partially protected places, so as
to gain space inside buildings. It features an elegant Schumann
design with covered console. This, along with a compact size,
makes the boiler well able to blend in with other wall units
and furnishings while meeting all types of planning requi-
rement since it is available with 24 kW, 28 kW and 32 kW
power ratings. The EOLO Maior kW boiler features the new
high-performance hydraulic unit, and can also cope with small
service requirements or low domestic water inlet pressure va-
lues. It is also simple to use thanks to user-friendly electronics,
while the controls and signals are easy to interpret. The boiler
can be used in conjunction with the exclusive Amico Remote
Control and external probe (both optional) which allow it to
be controlled, monitored and programmed at a distance in an
extremely simple way, thus optimizing its operation through
climatic thermoregulation.

1 SPECFICATIONS OF EOLO Maior kW

Wall-mounted boiler for heating and instantenaous production of adjuster knob, general selector with function (stand-by, domestic hot
domestic hot water, with sealed chamber, forced draught and 24 kW water, heating, Reset);
(20,640 kcal/h), 28 kW (24,080 kcal/h) or 32 kW (27,520 kcal/h) • boiler operating parameters entered by means of knobs with Leds to
nominal heat output, high efficiency and forced circulation. display the status and operating mode;
The boiler classification changes when the type of installation is varied, • check-control system with Leds to display the operating status and
regardless of whether the boiler is installed indoors or outdoors. faults;
Appliance type B22 - if installed using the relative kit (optional). • console with retracting controls complete with electronic board with
Appliance type C12/ C32/ C42/ C52/ C82 - if installed using the Ø 80/80 microprocessor, infinite flame modulation with 2 sensors (domestic
separator kit or concentric vertical or horizontal kits. hot water and heating), P.I.D. monitoring, modulation range:
Both models consist of: - EOLO Maior 24 kW from 9.3 to 24 kW (from 8,000 to 20,640
• main multigas burner with 11 ramps (mod. 24 kW), 14 ramps kcal/h);
(mod. 28 kW) or 15 ramps (mod. 32 kW) and aspirated air. Made - EOLO Maior 28 kW from 10.5 to 28 kW (from 9,000 to 24,080
of stainless steel and complete with ignition electrodes and detection kcal/h);
electrode; - EOLO Maior 32 kW from 12.5 to 32 kW (from 10,750 to 27,520
• electric gas valve with double shutter and built-in modulating coil; kcal/h);
• high-efficiency gas/water primary exchanger made of copper and • electronic ignition with ionizing monitoring function;
consisting of four pipes connected in series in lamellar coils protected • antifreeze protection system (down to -5 °C), circulator anti-blocking
by non-corroding alloy; function and three-way valve, system post-circulation function,
• combustion chamber in steel plate internally insulated with ceramic post-ventilation function, chimney-sweep function, pre-engineered
panels; for connection to the Immergas Amico Remote Control, the Timer-
• sealed chamber in steel plate with fixed speed fumes exhaust fan, thermostat, the Ambient thermostat, the Timer clock, the External
differential pressure switch to ensure the fan and fumes exhaust/air probe and the Electronic control unit for zoned systems;
intake circuit operate correctly; • IP X4D electrical insulation degree.
• secondary water/water exchanger for producing domestic hot water, • (optional) connecting group with depth adjustable fittings, gas cut
made of stainless steel with 16 plates (mod. 24 kW), 20 plate (mod. off cock and filling valve.
28 kW) or 22 plates (mod. 32 kW); Supplied complete with intakes for combustion analysis, bottom
• hydraulic unit consisting of a 3-way electric valve, adjustable speed protection grille.
circulator with built-in air separator, adjustable by-pass, absolute II2H3+ category appliance running on Natural Gas or LPG.. With
pressure switch for the primary circuit, system draining fitting and CE mark.
a cock for filling the system;
• domestic water flow switch to detect when domestic water is used; The following models are available:
• 10 litre diaphragm expansion tank (real capacity 7.4) with 1.0 bar • EOLO Maior 24 kW Export code 3.019355
preload, 3-bar system safety valve and pressure gauge; • EOLO Maior 28 kW Export code 3.019356
• overtemperature safety thermostat; • EOLO Maior 32 kW Export code 3.019357
• heating temperature adjuster knob, domestic hot water temperature

1
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

EOLO Maior kW VIP is the wall-mounted boiler with sealed


chamber and forced draught that's approved for operation
both indoors and outdoors in partially protected places, so
as to gain space inside buildings. The EOLO Maior kW VIP
boiler features the "Aqua Celeris” system which drastically
reduces the time users need to wait for domestic hot water
to be delivered. "Aqua Celeris” is a new system patented by
Immergas. It consists of a small storage tank installed in the
primary circuit and maintained at the right temperature by a
small modulating electric heating element that immediately
brings the domestic water to the right temperature as soon
as the tap is turned on. The EOLO Maior kW VIP boiler is
simple to use thanks to user-friendly electronics, while the
controls and signals are easy to interpret. The boiler can be
used in conjunction with the exclusive Amico Remote Con-
trol and external probe (both optional) which allow it to be
controlled, monitored and programmed at a distance in an
extremely simple way.

1.1 SPECIFICATIONS OF EOLO Maior kW VIP

Wall-mounted boiler for heating and instantaneous production of preload, 3-bar system safety valve and pressure gauge;
domestic hot water, with sealed chamber, forced draught and 24 kW • overtemperature safety thermostat;
(20,640 kcal/h) or 28 kW (24,080 kcal/h) nominal heat output, high • heating temperature adjuster knob, domestic hot water temperature
efficiency and forced circulation. adjuster knob, general selector with function (stand-by, domestic hot
The boiler classification changes when the type of installation is varied, water, heating, Reset);
regardless of whether the boiler is installed indoors or outdoors. • boiler operating parameters entered by means of knobs with Leds to
Appliance type B22 - if installed using the relative kit (optional). display the status and operating mode;
Appliance type C12/ C32/ C42/ C52/ C82 - if installed using the Ø 80/80 • check-control system with Leds to display the operating status and
separator kit or concentric vertical or horizontal kits. faults;
both models consist of: • console with retracting controls complete with electronic board with
• main multigas burner with 11 ramps (mod. 24 kW) or 14 ramps microprocessor, infinite flame modulation with 2 sensors (domestic
(mod. 28 kW) and aspirated air. Made of stainless steel and complete hot water and heating), P.I.D. monitoring, modulation range:
with ignition electrodes and detection electrode; - EOLO Maior 24 kW VIP from 9.3 to 24 kW (from 8,000 to 20,640
• electric gas valve with double shutter and built-in modulating coil; kcal/h);
• high-efficiency gas/water primary exchanger made of copper and - EOLO Maior 28 kW VIP from 10.5 to 28 kW (from 9,000 to 24,080
consisting of four pipes connected in series in lamellar coils protected kcal/h);
by non-corroding alloy; • electronic ignition with ionizing monitoring function;
• combustion chamber in steel plate internally insulated with ceramic • antifreeze protection system (down to -5 °C), circulator anti-blocking
panels; function and three-way valve, system post-circulation function,
• sealed chamber in steel plate with fixed speed fumes exhaust fan, post-ventilation function, chimney-sweep function, pre-engineered
differential pressure switch to ensure the fan and fumes exhaust/air for connection to the Immergas Amico Remote Control, the Timer-
intake circuit operate correctly; thermostat, the Ambient thermostat, the Timer clock, the External
• secondary water/water exchanger for producing domestic hot water, probe and the Electronic control unit for zoned systems;
made of stainless steel with 16 plates (mod. 24 kW) or 20 plates • IP X4D electrical insulation degree.
(mod. 28 kW); • (optional) connecting group with depth adjustable fittings, gas cut
• patented "Aqua Celeris" comprising a small storage tank installed off cock and filling valve.
in the primary circuit and maintained at the right temperature by Supplied complete with intakes for combustion analysis, bottom
a modulating electric heating element; protection grille.
• hydraulic unit consisting of a 3-way electric valve, adjustable speed II2H3+ category appliance running on Natural Gas or LPG.. With
circulator with built-in air separator, adjustable by-pass, absolute CE mark.
pressure switch for the primary circuit, system draining fitting and
a cock for filling the system; The following models are available:
• domestic water flow switch to detect when domestic water is • EOLO Maior 24 kW VIP export code 3.019358
used; • EOLO Maior 28 kW VIP Export code 3.019359
• 8 litre diaphragm expansion tank (real capacity 6.5) with 1.0 bar

2
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

EOLO Maior kW X is the wall-mounted boiler with sealed


chamber and forced draught nfor heating purposes only, that's
approved for both indoor and outdoor operation in partially
protected places. All the boilers in the EOLO maior kW series
are equipped with an antifreeze system that protects them down
to a temperature of -5°C. Thanks to a special kit (optional),
the boiler can be connected to a separate 80, 105, 120, or
200 litre capacity Water Heater manufactured by Immergas.
This accessory ensures an abundant production of hot water
and is particularly ideal for homes with several bathrooms
or whenever lots of hot water is needed quickly. Optimum
thermoregulation is guaranteed as the boiler can be used in
conjunction with the exclusive Amico Remote Control and
external probe (both optional). To complete the installation,
there is a wide range of air intake kits and ones to dispose
of the products of combustion, all with push-in connection
mechanisms and silicone seals.

1.2 SPECIFICATIONS OF EOLO Maior kW X


Wall-mounted boiler for room heating only, with sealed chamber, • heating temperature adjuster knob, general selector with function
forced draught and 28 kW (24,080 kcal/h) nominal heat output, (stand-by, heating, Reset);
high efficiency and forced circulation. It is pre-engineered for use • the boiler's operating parameters are selected by means of knobs
in conjunction with a separate 80, 105, 120 and 200 litre capacity while Leds display the status and operating mode;
Water Heater unit. • check-control system with Leds to display the operating status and
The boiler classification changes when the type of installation is varied, faults;
regardless of whether the boiler is installed indoors or outdoors. • console with retracting controls complete with electronic board with
Appliance type B22 - if installed using the relative kit (optional). microprocessor, infinite flame modulation with P.I.D. monitoring,
Appliance type C12/ C32/ C42/ C52/ C82 - seif installed using the Ø modulation range from 10.5 to 28 kW (from 9,000 to 24,080
80/80 separator kit or concentric vertical or horizontal kits. kcal/h);
The boiler consists of: • electronic ignition with ionizing monitoring function;
• main multigas burner with 14 ramps and aspirated air. Made of • antifreeze protection system (down to -5 °C), circulator anti-blocking
stainless steel and complete with ignition electrodes and detection function and three-way valve, system post-circulation function,
electrode; post-ventilation function, chimney-sweep function, pre-engineered
• electric gas valve with double shutter and built-in modulating for connection to the Immergas Amico Remote Control, the Timer-
coil; thermostat, the Ambient thermostat, the Timer clock, the External
• high-efficiency gas/water primary exchanger made of copper and probe and the Electronic control unit for zoned systems;
consisting of four pipes connected in series in lamellar coils protected • IP X4D electrical insulation degree.
by non-corroding alloy; • (optional) connecting group with depth adjustable fittings and
• combustion chamber in steel plate internally insulated with ceramic on-off cocks for gas and domestic cold water.
panels; Supplied complete with intakes for combustion analysis, bottom
• sealed chamber in steel plate with fixed speed fumes exhaust fan, protection grille.
differential pressure switch to ensure the fan and fumes exhaust/air II2H3+ category appliance running on Natural Gas or LPG.. With
intake circuit operate correctly; CE mark.
• hydraulic unit consisting of a circulator with variable speed and
built-in air separator, adjustable by-pass, absolute pressure switch
for the primary circuit, system draining fitting and a cock for filling The following model is available:
the system; • EOLO Maior 28 kW X Export code 3.018923
• 10 litre diaphragm expansion tank (real capacity 7.4) with 1.0 bar
preload, 3-bar system safety valve and pressure gauge;
• overtemperature safety thermostat;

3
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

2 MAIN COMPONENTS OF Maior kW

LEGEND:
1 - Gas valve 14 - Safety thermostat
2 - D.h.w. probe 15 - Flue hood
3 - D.h.w. flow switch 16 - Primary heat exchanger
4 - D.h.w. heat exchanger 17 - System expansion vessel
5 - Burner 18 - Ignition and detection electrodes
6 - Combustion chamber 19 - Automatic vent valve
7 - Sealed chamber 20 - Boiler pump
8 - Fan 21 - System pressure switch
9 - Sample point (air A) - (flues F) 22 - 3-bar safety valve
10 - Positive signal pressure point 23 - Three-way valve (motorized)
11 - Negative signal pressure point 24 - Draining valve
12 - Flue pressure switch 25 - Filling valve
13 - Flow probe

4
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

2.1 MAIN COMPONENTS OF Maior kW VIP

LEGEND:
1 - Gas valve 14 - Safety thermostat
2 - D.h.w. probe 15 - Flue hood
3 - D.h.w. flow switch 16 - Primary heat exchanger
4 - D.h.w. heat exchanger 17 - System expansion vessel
5 - Burner 18 - Ignition and detection electrodes
6 - Combustion chamber 19 - Aqua celeris
7 - Sealed chamber 20 - Automatic vent valve
8 - Fan 21 - Boiler pump
9 - Sample point (air A) - (flues F) 22 - System pressure switch
10 - Positive signal pressure point 23 - 3-bar safety valve
11 - Negative signal pressure point 24 - Three-way valve (motorized)
12 - Flue pressure switch 25 - Draining valve
13 - Flow probe 26 - Filling valve

5
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

2.2 MAIN COMPONENTS OF EOLO Maior kW X

LEGEND:
1 - Gas valve 12 - Flue hood
2 - Burner 13 - Primary heat exchanger
3 - Combustion chamber 14 - Ignition and detection electrodes
4 - Sealed chamber 15 - System expansion vessel
5 - Fan 16 - Automatic vent valve
6 - Sample point (air A) - (flues F) 17 - Boiler pump
7 - Positive signal pressure point 18 - System pressure switch
8 - Negative signal pressure point 19 - 3-bar safety valve
9 - Flue pressure switch 20 - Three-way valve plug
10 - Flow probe 21 - Draining valve
11 - Safety thermostat 22 - Filling valve

6
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

3 MAIN DIMENSIONS OF EOLO Maior kW / VIP

Model Height mm Width mm Depth mm intake/exhaust Ø mm

EOLO Maior kW 830 440 350 100/60


EOLO Maior kW VIP 830 440 350 100/60

3.1 CONNECTIONS

B A B

Upper casing line

A = inlet/outlet
B = inlet

Distance between upper casing line and


Ø 60/100 concentric elbow axis: 95 mm

Note: Coupling system (OPTIONAL) Distance between upper casing line and
Ø 80/80 separator elbow axis: A=135 mm B = 115

Model Flow Return Hot outlet Cold inlet Gas Expansion vessel
M R AC AF G Litres
EOLO Maior kW 3/4" 3/4" 1/2" 1/2" 1/2" 10 (real 7.4)
EOLO Maior kW VIP 3/4" 3/4" 1/2" 1/2" 1/2" 8 (real 6.6)

7
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

4 MAIN DIMENSIONS OF EOLO Maior kW X

Model Height mm Width mm Depth mm intake/exhaust Ø mm

EOLO Maior kW X 830 440 350 100/60

4.1 CONNECTIONS

B A B

Upper casing line

A = inlet/outlet
B = inlet

Note: Coupling system (OPTIONAL) Distance between upper casing line and
Ø 60/100 concentric elbow axis: 95 mm
Water Heater Capacity Height Width Depth
UB 80 (80 l.) 850 mm 500 mm 500 mm Distance between upper casing line and
UB 105 (105 l.) 1020 mm 500 mm 500 mm Ø 80/80 separator elbow axis: A=135 mm B = 115
UB 120 (120 l.) 850 mm 600 mm 600 mm
UB 200 (200 litri) 1250 mm 600 mm 600 mm * Only if mounted Storage Tank coupling kit

Model Flow Return * Storage tank * Storage tank System filling Gas Expansion vessel
M R flow MU return RU RR G Litres
EOLO Maior kW X 3/4" 3/4" 3/4" 3/4" 1/2" 1/2" 10 (real 7.4)

8
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

5 PUMP HEAD AND FLOW RATE GRAPH

“EOLO Maior kW” boilers are supplied with a built-in circu- The “EOLO Maior kW” boilers are equipped with an adju-
lation pump and three-position electric speed governor. The stable by-pass. The by-pass is regulated in the factory for curve
pump is already equipped with a condenser. B. This setting can be modified by means of the screw on the
by-pass unit.

5.1 PUMP - EOLO 24 kW / 24 kW VIP


GRUNDFOS UPS 15-50 AO HB

Head (m H2O)
Head (kPa)

B A

Flow rate l/h

5.2 PUMP- EOLO 28 kW / 28 kW VIP / 28 kW X


GRUNDFOS UPS 15-60 AO HB
Head (m H2O)
Head (kPa)

Flow rate l/h

A: Available head at top speed with by-pass closed (adjuster screw fully tightened).
B: Available head at top speed with factory setting (screw turned 1-1/2 turns in relation to the setting with the adjuster screw
fully loosened).
C: Available head at top speed with by-pass fully open (adjuster screw fully unscrewed).

9
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

5.3 PUMP - EOLO 32 kW


GRUNDFOS UPS 15-70 AO HB

Head (m H2O)
Head (kPa)

Flow rate l/h

A: Available head at top speed with by-pass closed (adjuster screw fully tightened).
B: Available head at top speed with factory setting (screw turned 1-1/2 turns in relation to the setting with the adjuster
screw fully loosened).
C: Available head at top speed with by-pass fully open (adjuster screw fully unscrewed).

10
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

6 WIRING DIAGRAM - EOLO Maior kW

AMBIENT THERMOSTAT OR REMOTE CONTROL used, connect to terminals 40 and 41 and eliminate jumper
The boiler is pre-engineered for installation of the Amico Re- X40. If both are used, connect S20 to terminals 40 and 7
mote Control (CAR), which must be connected to terminals 42 and P1 to terminals 8 and 41 after having eliminated jumper
and 43 of connector X2 on the integrated electronic board, in X40.
compliance with the polarity and eliminating jumper X40. The External Probe (B4) must be connected to terminals 38
The boiler is pre-engineered for installation of the Ambient and 39 of connector X2 on the integrated electronic board.
Thermostat (S20) and Programmer Clock (P1). If only one is

Zone Control
Unit
230 Vac
50Hz
supply
brown

white

white
white
black

black

black
black

black
black
grey
blue

grey
grey
grey
grey
red

red
red
red

red
RELAY
BOARD
yellow/green
brown
blue

NAT-LPG
brown
blue

Primary
Secondary

LEGEND:
A5 - CAR interface board M30 - Three-way valve
B1 - Flow probe P1 - Heating Timer
B2 - D.h.w. probe R5 - D.h.w. temperature trimmer
B4 - External probe (optional) R6 - Heating temperature trimmer
CAR - Comando Amico Remoto remote control R10 - Main switch
(optional) S4 - D.h.w. flow switch
CZ - Zoned control unit (optional) S5 - System pressure switch
E1 - Ignition electrodes S6 - Flue pressure switch
E2 - Detection electrode S8 - Gas type selector
E4 - Safety thermostat S20 - Room thermostat (optional)
F1 - Line fuse T1 - Ignition transformer
F2 - Neutral fuse X40 - Room thermostat jumper
M1 - Boiler pump Y1 - Gas valve
M20 - Fan Y2 - Gas valve modulator

11
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

6.1 WIRING DIAGRAM - EOLO Maior kW VIP

AMBIENT THERMOSTAT OR REMOTE CONTROL used, connect to terminals 40 and 41 and eliminate jumper
The boiler is pre-engineered for installation of the Amico Re- X40. If both are used, connect S20 to terminals 40 and 7
mote Control (CAR), which must be connected to terminals 42 and P1 to terminals 8 and 41 after having eliminated jumper
and 43 of connector X2 on the integrated electronic board, in X40.
compliance with the polarity and eliminating jumper X40. The External Probe (B4) must be connected to terminals 38
The boiler is pre-engineered for installation of the Ambient and 39 of connector X2 on the integrated electronic board.
Thermostat (S20) and Programmer Clock (P1). If only one is

Connector on the
electronic board

brown
blue

blue
brown
brown

white
white
white

black
black

black

black

black
black
grey
blue

grey
grey
grey
grey

red

red
red

red

red
230 Vac Zone Control
50Hz Unit
supply
brown
blue
y/g

brown
blue

NAT-LPG

Primary
Secondary

K3-1 - Aqua celeris heating element relay


LEGEND: M1 - Boiler pump
A5 - CAR interface board M20 - Fan
B1 - Flow probe M30 - Three-way valve
B2 - D.h.w. probe P1 - Heating Timer
B4 - External probe (optional) R5 - D.h.w. temperature trimmer
CAR - Comando Amico Remoto remote control R6 - Heating temperature trimmer
(optional) R10 - Main switch
CZ - Zoned control unit (optional) S4 - D.h.w. flow switch
E1 - Ignition electrodes S5 - System pressure switch
E2 - Detection electrode S6 - Flue pressure switch
E4 - Safety thermostat S8 - Gas type selector
E11 - Aqua Celeris heating element S20 - Room thermostat (optional)
F1 - Line fuse T1 - Ignition transformer
F2 - Neutral fuse X40 - Room thermostat jumper
K1-1 - Configurable relay Y1 - Gas valve
K2-1 - Configurable relay Y2 - Gas valve modulator

12
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

6.2 WIRING DIAGRAM - EOLO Maior kW X

AMBIENT THERMOSTAT OR REMOTE CONTROL used, connect to terminals 40 and 41 and eliminate jumper
The boiler is pre-engineered for installation of the Amico Re- X40. If both are used, connect S20 to terminals 40 and 7
mote Control (CAR), which must be connected to terminals 42 and P1 to terminals 8 and 41 after having eliminated jumper
and 43 of connector X2 on the integrated electronic board, in X40.
compliance with the polarity and eliminating jumper X40. The External Probe (B4) must be connected to terminals 38
The boiler is pre-engineered for installation of the Ambient and 39 of connector X2 on the integrated electronic board.
Thermostat (S20) and Programmer Clock (P1). If only one is

Zone Control
Unit
230 Vac
50Hz
supply
brown

white
white
white
black

black

black
black
black
black
blue

grey
grey
grey

grey

red
red
red

red
red
RELAY
BOARD
yellow/green
brown
blue

brown
blue

NAT-LPG

Primary
Secondary

LEGEND: M30 - Three-way valve (optional)


A5 - CAR interface board P1 - Heating Timer
B1 - Flow probe R5 - D.h.w. temperature trimmer (optional)
B2 - D.h.w. probe R6 - Heating temperature trimmer
B4 - External probe (optional) R8 - Water heater funct. inhibiting resistance
CAR - Comando Amico Remoto remote control R10 - Main switch
(optional) S4 - D.h.w. flow switch
CZ - Zoned control unit (optional) S5 - System pressure switch
E1 - Ignition electrodes S6 - Flue pressure switch
E2 - Detection electrode S8 - Gas type selector
E4 - Safety thermostat S20 - Room thermostat (optional)
F1 - Line fuse T1 - Ignition transformer
F2 - Neutral fuse X40 - Room thermostat jumper
M1 - Boiler pump Y1 - Gas valve
M20 - Fan Y2 - Gas valve modulator

13
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

7 HYDRAULIC LAYOUT - EOLO Maior kW

LEGEND: 12 - Safety thermostat


1 - D.h.w. flow switch 13 - System expansion vessel
2 - D.h.w. probe 14 - Automatic vent valve
3 - D.h.w. heat exchanger 15 - Boiler pump
4 - Gas valve 16 - Three-way valve (motorized)
5 - Burner 17 - Draining valve
6 - Primary heat exchanger 18 - Filling valve
7 - Flue hood 19 - Adjustable by-pass
8 - Fan 20 - System pressure switch
9 - Sealed chamber 21 - 3-bar safety valve
10 - Flue pressure switch 22 - One-way valve
11 - Flow probe 23 - Flow limiter

14
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

7.1 HYDRAULIC LAYOUT - EOLO Maior kW VIP

LEGEND: 13 - Flow probe


1 - D.h.w. flow switch 14 - Safety thermostat
2 - D.h.w. probe 15 - System expansion vessel
3 - D.h.w. heat exchanger 16 - Air venting valve
4 - Aqua celeris heating element (PTC) 17 - Boiler circulator
5 - Aqua celeris 18 - Three-way valve (motorized)
6 - Gas valve 19 - Draining valve
7 - Burner 20 - Filling valve
8 - Primary heat exchanger 21 - Adjustable by-pass
9 - Flue hood 22 - System pressure switch
10 - Fan 23 - 3-bar safety valve
11 - Sealed chamber 24 - One-way valve
12 - Flue pressure switch 25 - Flow limiter

15
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

7.2 HYDRAULIC LAYOUT - EOLO Maior kW X

LEGEND:
1 - Gas valve 10 - System expansion vessel
2 - Burner 11 - Automatic vent valve
3 - Primary heat vexchanger 12 - Boiler pump
4 - Flue hood 13 - Draining valve
5 - Fan 14 - Three-way valve (without motor)
6 - Sealed chamber 15 - Adjustable by-pass
7 - Flue pressure switch 16 - System pressure switch
8 - Flow probe 17 - 3-bar safety valve
9 - Safety thermostat 18 - Filling valve

16
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

8 TECHNICAL SPECIFICATIONS - EOLO Maior kW

EOLO 24 EOLO 28 EOLO 32

Maximum nominal heat input kW (kcal/h) 25.9 (22,241) 30.1 (25,920) 34.4 (29,579)
Maximum useful heat ouput kW (kcal/h) 24.0 (20,640) 28.0 (24,080) 32.0 (27,520)
Minimum nominal heat input kW (kcal/h) 10.7 (9,195) 12.2 (10,488) 14.6 (12,590)
Minimum useful heat output kW (kcal/h) 9.3 (8,000) 10.5 (9,030) 12.5 (10,750)
Efficiency at 100% heat output % 92.8 92.9 93.0
Efficiency at 30% heat output load % 90.7 90.9 91.5
Central heating circuit
Adjustable central heating temperature °C 35 - 85 35 - 85 35 - 85
Max system operating temperature °C 90 90 90
Max system operating pressure bar 3 3 3
Nominal (actual) capacity of expansion vessel litres 10 / (7.4) 10 / (7.4) 10 / (7.4)
Preload pressure of system expansion vessel bar 1.0 1.0 1.0
Available head with 1000 l/h flow rate kPa (m H2O) 35.30 (3.6) 38.24 (3.9) 39.22 (4.0)
Domestic hot water circuit
Useful heat output for D.H.W. production kW (kcal/h) 24.0 (20,640) 28.0 (24,080) 32.0 (27,520)
D.H.W. temperature adjustable range °C 30 - 60 30 - 60 30 - 60
Minimum D.H.W. dynamic circuit pressure bar 0.3 0.3 0.3
Maximum D.H.W. circuit pressure bar 10 10 10
Min. D.H.W. flow rate litres/min 1.5 1.5 1.5
Flow rate for continuous service (∆t 30°C) litres/min 11.5 13.4 15.3
Gas supply
NATURAL GAS (G20) MIN - MAX mbar 2.20 - 12.20 1.80 - 10.50 2.20 - 12.40
nozzles n°- ø mm 11 x 1.35 14 x 1.35 15 x 1.35
LPG (G30) MIN - MAX mbar 6.00 - 27.50 4.95 - 27.41 5.39 - 28.20
nozzles n°- ø mm 11 x 0.79 14 x 0.77 15 x 0.79
LPG (G31) MIN - MAX mbar 7.00 - 36.20 6.30 - 36.30 7.09 - 36.00
nozzles n°- ø mm 11 x 0.79 14 x 0.77 15 x 0.79
Supply voltage V/Hz 230 - 50 230 - 50 230 - 50
Nominal power absorption A 0.62 0.83 0.96
Installed electric power W 130 150 170
Power absorbed by fan W 25 48 60
Power absorbed by pump W 90 88 98
Electrical insulation degree IP X4D X4D X4D
Boiler water content litres 1.3 3.3 3.5
Empty boiler weight kg 43 45 46

17
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

8.1 TECHNICAL SPECIFICATIONS - EOLO Maior kW VIP

EOLO 24 EOLO 28

Maximum nominal heat input kW (kcal/h) 25.9 (22,241) 30.1 (25,920)


Maximum useful heat ouput kW (kcal/h) 24.0 (20,640) 28.0 (24,080)
Minimum nominal heat input kW (kcal/h) 10.7 (9,195) 12.2 (10,488)
Minimum useful heat output kW (kcal/h) 9.3 (8,000) 10.5 (9,030)
Efficiency at 100% heat output % 92.8 92.9
Efficiency at 30% heat output load % 90.7 90.9
Central heating circuit
Adjustable central heating temperature °C 35 - 85 35 - 85
Max system operating temperature °C 90 90
Max system operating pressure bar 3 3
Nominal (actual) capacity of system expansion vessel litres 7.5 / (6.6) 7.5 / (6.6)
Preload pressure of system expansion vessel bar 1.0 1.0
Available head with 1000 l/h flow rate kPa (m H2O) 35.30 (3.6) 38.24 (3.9)
Domestic hot water circuit
Useful heat output for D.H.W. production kW (kcal/h) 24.0 (20,640) 28.0 (24,080)
D.H.W. temperature adjustable range °C 30 - 60 30 - 60
Minimum D.H.W. dynamic circuit pressure bar 0.3 0.3
Maximum D.H.W. circuit pressure bar 10 10
Min. D.H.W. flow rate litres/min ≤ 2.0 ≤ 2.0
Flow rate for continuous service (∆t 30°C) litres/min 11.5 13.4
Gas supply
NATURAL GAS (G20) MIN - MAX mbar 2.20 - 12.20 1.80 - 10.50
nozzles n°- ø mm 11 x 1.35 14 x 1.35
LPG (G30) MIN - MAX mbar 6.00 - 27.50 4.95 - 27.41
nozzles n°- ø mm 11 x 0.79 14 x 0.77
LPG (G31) MIN - MAX mbar 6.99 - 36.19 6.30 - 36.30
nozzles n°- ø mm 11 x 0.79 14 x 0.77
Supply voltage V/Hz 230 - 50 230 - 50
Nominal power absorption A 0.62 0.83
Installed electric power W 130 150
Power absorbed by fan W 25 48
Power absorbed by pump W 90 88
Electrical insulation degree IP X4D X4D
Boiler water content (Aqua Celeris contents) litres 1.3 (4.0) 3.3 (4.0)
Empty boiler weight kg 43 45

18
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

8.2 TECHNICAL SPECIFICATIONS - EOLO Maior kW X

EOLO 28

Maximum nominal heat input kW (kcal/h) 30.1 (25,920)


Maximum useful heat ouput kW (kcal/h) 28.0 (24,080)
Minimum nominal heat input kW (kcal/h) 12.2 (10,488)
Minimum useful heat output kW (kcal/h) 10.5 (9,030)
Efficiency at 100% heat output % 92.9
Efficiency at 30% heat output load % 90.9
Central heating circuit
Adjustable central heating temperature °C 35 - 85
Max system operating temperature °C 90
Max system operating pressure bar 3
Nominal (actual) capacity of system expansion vessel litres 10 / (7.4)
Preload pressure of system expansion vessel bar 1.0
Available head with 1000 l/h flow rate kPa (m H2O) 38.24 (3.9)
D.W. circuit (in conjunction with Water Heater Unit)
Useful heat output for domestic hot water production kW (kcal/h) 28.0 (24,080)
Specific flow rate for 10 min. (∆t 30°C) 80 litre WHU litres/min 20.9
Specific flow rate for 10 min. (∆t 30°C) 105 litre WHU litres/min 23.8
Specific flow rate for 10 min. (∆t 30°C) 120 litre WHU litres/min 26.6
Specific flow rate for 10 min. (∆t 30°C) 200 litre WHU litres/min 35.4
Flow rate for continuous service with WHU (∆t 30°C) litres/min 13.3
Gas supply
NATURAL GAS (G20) MIN - MAX mbar 1.80 - 10.50
nozzles n°- ø mm 14 x 1.35
LPG (G30) MIN - MAX mbar 4.95 - 27.40
nozzles n°- ø mm 14 x 0.77
LPG (G31) MIN - MAX mbar 6.30 - 36.30
nozzles n°- ø mm 14 x 0.77
Supply voltage V/Hz 230 - 50
Nominal power absorption A 0.83
Installed electric power W 150
Power absorbed by fan W 48
Power absorbed by pump W 88
Electrical insulation degree IP X4D
Boiler water content litres 2.5
Empty boiler weight kg 45

19
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

9 COMBUSTION SPECIFICATIONS - EOLO 24 kW / 24 kW VIP

Nat. gas (G20) LPG (G30) LPG (G31)

Combustion efficiency at 100% nominal heat output % 93.6 93.6 93.6


Combustion efficiency min heat output % 88.0 88.0 88.0
Flue losses with burner on (100% nom. heat output) % 6.4 6.4 6.4
Flue losses with burner on (min heat output) % 12.0 12.0 12.0
Flue losses with burner off % 0.02 0.02 0.02
Casing losses with burner off % 0.70 0.70 0.70
Casing losses with burner on (100% nom. heat output) % 0.80 0.80 0.80
Casing losses with burner on (min heat output) % 1.0 1.0 1.0
Flue temperature Maximum Heat Input °C 122 113 107
Flue temperature Minimum Heat Input °C 96 88 89
Flue flow rate at Maximum Heat Input kg/h 51 57 60
Flue flow rate at Minimum Heat Input kg/h 54 60 59
CO2 at Maximum Heat Input % 7.40 7.50 7.00
CO2 at Minimum Heat Input % 2.70 2.80 2.80
CO at Maximum Heat Input mg/kWh 66 49 37
CO at Minimum Heat Input mg/kWh 89 18 16
NOx at Maximum Heat Input mg/kWh 265 358 338
NOx at Minimum Heat Input mg/kWh 176 90 89
Weighted CO mg/kWh 54 - -
Weighted NOx mg/kWh 176 - -
NOx class - 2 2 2

The gas flow rates refer to the NHV at 15°C and with a 1013 mbar pressure.
The fumes temperature values refer to a 15°C inlet air temperature.

20
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

9.1 COMBUSTION SPECIFICATIONS - EOLO 28 kW / 28 kW VIP / 28 kW X

Nat. gas (G20) LPG (G30) LPG (G31)

Combustion efficiency at 100% nominal heat output % 93.3 93.3 93.3


Combustion efficiency min heat output % 87.0 87.0 87.0
Flue losses with burner on (100% nom. heat output) % 6.7 6.7 6.7
Flue losses with burner on (min heat output) % 13.0 13.0 13.0
Flue losses with burner off % 0.02 0.02 0.02
Casing losses with burner off % 0.62 0.62 0.62
Casing losses with burner on (100% nom. heat output) % 0.40 0.40 0.40
Casing losses with burner on (min heat output) % 0.9 0.9 0.9
Flue temperature Maximum Heat Input °C 117 118 116
Flue temperature Minimum Heat Input °C 92 95 93
Flue flow rate at Maximum Heat Input kg/h 64 64 65
Flue flow rate at Minimum Heat Input kg/h 68 66 68
CO2 at Maximum Heat Input % 6.80 7.80 7.60
CO2 at Minimum Heat Input % 2.40 2.90 2.80
CO at Maximum Heat Input mg/kWh 48 67 42
CO at Minimum Heat Input mg/kWh 91 103 100
NOx at Maximum Heat Input mg/kWh 208 340 267
NOx at Minimum Heat Input mg/kWh 141 152 116
Weighted CO mg/kWh 62 - -
Weighted NOx mg/kWh 124 - -
NOx class - 3 3 3

The gas flow rates refer to the NHV at 15°C and with a 1013 mbar pressure.
The fumes temperature values refer to a 15°C inlet air temperature.

21
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

9.2 COMBUSTION SPECIFICATIONS - EOLO 32 kW

Nat. gas (G20) LPG (G30) LPG (G31)

Combustion efficiency at 100% nominal heat output % 93.5 93.5 93.5


Combustion efficiency min heat output % 86.1 86.1 86.1
Flue losses with burner on (100% nom. heat output) % 6.5 6.5 6.5
Flue losses with burner on (min heat output) % 13.9 13.9 13.9
Flue losses with burner off % 0.01 0.01 0.01
Casing losses with burner off % 0.46 0.46 0.46
Casing losses with burner on (100% nom. heat output) % 0.50 0.50 0.50
Casing losses with burner on (min heat output) % 0.70 0.70 0.70
Flue temperature Maximum Heat Input °C 125 125 122
Flue temperature Minimum Heat Input °C 118 117 115
Flue flow rate at Maximum Heat Input kg/h 67 68 70
Flue flow rate at Minimum Heat Input kg/h 73 74 76
CO2 at Maximum Heat Input % 7.5 8.4 8.1
CO2 at Minimum Heat Input % 2.7 3.1 3.0
CO at Maximum Heat Input mg/kWh 118 99 63
CO at Minimum Heat Input mg/kWh 75 80 84
NOx at Maximum Heat Input mg/kWh 282 378 373
NOx at Minimum Heat Input mg/kWh 176 199 178
Weighted CO mg/kWh 56 - -
Weighted NOx mg/kWh 190 - -
NOx class - 2 2 2

The gas flow rates refer to the NHV at 15°C and with a 1013 mbar pressure.
The fumes temperature values refer to a 15°C inlet air temperature.

22
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

10 OptionalS - EOLO Maior kW

Amico Remote Control External Probe


code 3.011236 code 3.014083

Telephone control Remote timer-thermostat (wireless)


code 3.013305 code 3.014439

Digital weekly timer-thermostat Polyphosphate dispenser kit


code 3.014438 code 3.014945

Configurable relay interface kit Remote filling kit


code 3015350 (including configurable relay interface kit)
code 3.015349

Antifreeze electric heating element kit (-15 °C) Supplementary system expansion vessel kit (2 litres)
code 3.015348 code 3015413

Control unit kit for zoned systems code 3.011668 Universal connection kit code 3.011667
Connections set kit code 3.019319 Disconnector kit for the water main code 3.015408

The boiler can be coupled to the DIM (Multi-system Distribution Manifold) available in 5 recessing kits.

23
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

10.1 OptionalS - EOLO Maior kW VIP

Amico Remote Control External Probe


code 3.011236 code 3.014083

Telephone control Remote timer-thermostat (wireless)


code 3.013305 code 3.014439

Weekly digital timer-thermostat Polyphosphate dispenser kit


code 3.014438 code 3.014945

Control unit kit for zoned systems Remote filling kit


code 3.011668 code 3.015411

Antifreeze electric heating element kit (-15 °C) Supplementary system expansion vessel kit (2 litres)
code 3.015348 code 3015450

On-off cock kit code 3.4297 Universal connection kit code 3.011667
Disconnector kit for the water main code 3.015408 Connections set kit code 3.019319
The boiler can be coupled to the DIM (Multi-system Distribution Manifold) available in 5 recessing kits.

24
EOLO Maior kW Export
EOLO Maior kW VIP Export
EOLO Maior kW X Export

10.2 OptionalS - EOLO Maior kW X

Amico Remote Control External Probe


code 3.011236 code 3.014083

Telephone control Remote timer-thermostat (wireless)


code 3.013305 code 3.014439

Weekly digital timer-thermostat Antifreeze electric heating element kit (-15 °C)
code 3.014438 code 3.015348

Configurable relay interface kit Control unit kit for zoned systems
code 3.015350 code 3.011668

Water Heater connection kit Supplementary system expansion vessel kit (2 litres)
code 3.015359 code 3.015413

On-off cock kit code 3.4297 Connections set kit code 3.019328
Riser pipe connection kit (WHU 105 and WHU 200) code 3.014920

The boiler can be coupled to the DIM (Multi-system Distribution Manifold) available in 5 recessing kits.

25
Immergas reserves the right to carry out, without notice, any modification to its models which it deems useful for the evolution of the
product. Code S.0093 rev. 000 - 03/2008 - Technical Documentation Office - Immergas Marketing Office
During their working life,
the performances of the
products are influenced by
external factors such as the
hardness of the domestic
water, the weather condi-
tions, scaling in the system,
etc. The data indicated in
this brochure refer to new
products, installed and
used in compliance with the
current standards in force.
N OT E : r e m e m b e r t o
have your applian-
ce periodically serviced.

42041 Brescello (RE) Italy - Tel. 0522.689011 - Fax 0522.689102


www.immergas.com