Location: Project: Date:: Bus Directly Connected Load Total Bus Load
Location: Project: Date:: Bus Directly Connected Load Total Bus Load
Project: Page: 1
12.6.0H
Location: Date: 10-08-2018
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: SLD_Aang_tugas_1 Config.: Normal
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
ETAP
Project: Page: 2
12.6.0H
Location: Date: 10-08-2018
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: SLD_Aang_tugas_1 Config.: Normal
Transformer
CKT / Branch Cable & Reactor
Ampacity Loading Capability Loading (input) Loading (output)
(Amp) Amp (MVA)
ID Type % MVA % MVA %
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
Cable1 0.320 0.277 -0.319 -0.277 0.2 0.0 99.6 99.6 0.05
1.8 8.6
ETAP
Project: Page: 4
12.6.0H
Location: Date: 10-08-2018
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: SLD_Aang_tugas_1 Config.: Normal
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Cable 100.0 95.0
Reactor 100.0 95.0
Line 100.0 95.0
Transformer 100.0 95.0
Panel 100.0 95.0
Protective Device 100.0 95.0
Generator 100.0 95.0
Inverter/Charger 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
UnderVoltage 95.0 98.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
UnderExcited (Q Min.) 100.0
Critical Report
Marginal Report
MW Mvar MVA % PF
Number of Iterations: 2