GFRG/RAPIDWALL BUILDING
STRUCTURAL DESIGN MANUALUse of Glass Fibre Reinforced
Gypsum (GFRG) Panels in Buildings
STRUCTURAL DESIGN
MANUAL
SE
Prepared by
Structural Engineering Division
Department of Civil Engineering
IIT Madras
Published by
iimlac
Building Materials & Technology Promotion Council
Ministry of Housing & Urban Poverty Alleviation
Government of indiaISBN: 978-81-928379-0-1
December, 2013
Disclaimer
‘The information presented in this Manual is supplied in good faith and is based entirely on
the test data and design guidelines furnished for GFRG building panel, Indian Institute of
Technology Madras is not responsible for incorrectness, if any, in such data furnished for
GFRG building panels.
Acknowledgment
The support of Rapid Building Systems Pty Ltd Australia, RBS India Pvt Ltd, Rashtriya
Chemicals and Fertilizers (RCF) Mumbai, FACT-RCF Building Products Ltd (FRBL) Cochin ~
Govt of india Public undertaking, is gratefully acknowledged.FOREWORD
The Glass Fibre Reinforced Gypsum (GFRG) Panel System, commonly known as Rapidwall, is an
alternate technology for construction of buildings originally developed and being in use for last
‘two decades in Australia. The panels are manufactured in semi-automatic machine using
phosphogypsum - an industrial waste from fertilizer plants and glass fibre rovings. The technology
is evaluated by BMTPC under the Performance Appraisal Certified Scheme (PACS). The evaluation
of the system is based on various tests performed on the panels. The panels, due to unique
configuration and materials have properties different than normal conventional construction.
Besides Australia and China, materials properties, strength and behavior of the panels have been
studied in India at IIT Madras.
While evaluating the system, it was realized that the design Manual used in Australia for the
system, needed appropriate modification to ensure conformity with the prevailing Indian standards
and to incorporate the research findings of the studies undertaken at IIT Madras. Accordingly, this
Designs Manual has been prepared by IIT Madras and being published by BMTPC. The Manuals
deals with the engineering design aspect of GFRG Panels and endeavours to provide guidelines to
the engineers who intend to design building using GFRG Panels.
This Manual is mandatory and required to be followed for design of any buildings using GFRG
Panels manufactured by RCF as per the design specifications.
BMTPC places deep appreciation for the valuable technical contributions made by Dr. Devdas
Menon and Dr. A. Meher Prasad of IIT Madras in developing painstakingly this Manual. | also
acknowledge the team at BMTPC specially Shri J.K.Prasad, Shri A.KTiwari and Shri Dalip Kumar for
successful operation of the scheme and bringing out the publication in time.
hope the Manual will serve the purpose for designing the buildings using GFRG Panels and will
0 a long way in propagating the Rapidwall technology as an alternate technology for building
construction.
Dr. Shailesh Kr. Agrawal
Executive Director, BMTPCPREFACE
GFRG is the abbreviation for glass fibre reinforced gypsum. It is the name of a new building panel
product, made essentially of gypsum plaster, reinforced with glass fibres, and is also known in the
industry as Rapidwall®. This product, suitable for rapid mass-scale building construction, was
originally developed and used since 1990 in Australia. GFRG is of particular relevance to india,
where there is a tremendous need for cost-effective mass-scale affordable housing, and where
gypsum is abundantly available as an industrial by-product waste. The product is not only eco-
friendly or green, but also resistant to water and fire. GFRG panels are presently manufactured to
a thickness of 124 mm, a length of 12m and a height of 3m, under carefully controlled conditions.
The panel can be cut to required size. Although its main application is in the construction of walls,
it can also be used in floor and roof slabs in combination with reinforced concrete.
The panel contains cavities that may be filled with concrete and reinforced with steel bars to
impart additional strength and provide ductility. The panels may be unfilled, partially filled or
fully filled with reinforced concreteas per the structural requirement. Experimental studies and
research have shown that GFRG panels, suitably filled with reinforced concrete, possess substantial
strength to act not only as load-bearing elements, but also as shear walls, capable of resisting
lateral loads due to earthquake and wind. It is possible to design such buildings up to ten storeys
in low seismic zones (and to lesser height in high seismic zones). However, such construction
needs to be properly designed by @ qualified structural engineer. Manufacture of GFRG panels
with increased thickness (150 mm, 200 mm) withsuitable flange thickness can facilitate design
and construction of taller buildings.
GFRG panels can also be used advantageously as infills (non-load bearing) in combination with
reinforced concrete(RC) framed columns and beams (conventional framed construction of multi-
storey buildings) without any restriction on the number of storeys. Also, GFRG panels with
‘embedded micro-beams and RC screed (acting as T-beams) can be used as floor/roof slabs. Design
of an eight storeyed building with GFRG panels as load bearing shear walls as well as infill walls in
framed construction is included in this manual for reference.
Some of the advantages of construction using GFRG panels are:
(i) Substantial reduction in the structural weight of the building;
(ii) No plastering requirement for walls and ceiling;
(iii) Increased speed of construction with less manpower;{iv) Saving of cement, steel, river sand, burnt clay bricks / concrete blocks and hence saving of
energy and reduced CO, emissions, contributing to environmental protection and mitigating
climate change;
(v) Use of reprocessed / recycled industrial by product, viz., waste gypsum, to manufacture
GFRG panel, helping to abate pollution and protect the environment.
GFRG building systems can be constructed only with technical support or supervision by qualified
engineers and constructors, based on structural designs carried out in detail complying to prevailing
standards; this is applicable even for low-rise and affordable mass housing, to provide for desirable
safety margins against natural disasters (such as earthquakes and cyclones).
GFRG panels can be unfilled when used as partition walls, but when used as external walls, need
to be suitably designed (with reinforced concrete filling) in order to resist the design wind pressures.
For single-storey construction (suitable for affordable mass housing), unfilled GFRG panels can be
used for walls as well as roof (which may be pitched suitably), with local reinforced concrete filling
at the joints between walls and between the roof and walls. It is mandatory to provide embedded
RC horizontal tie beams over all the walls below the floor slab / roof slab.
Based on the experience in Australia, as well as tests and independent evaluation reported by IIT
Madras and SERC Chennai, Building Materials & Technology Promotion Council (BMTPC),
Government of India, has accorded approval of GFRG panels for construction in India. However,
to facilitate such construction, it was felt necessary to bring out appropriate design and construction
manuals that meet the statutory requirements of relevant Indian Standards. The task of preparing
the Design Manual has been entrusted to IIT Madras by Rapidwall manufacturers and technology
promoters, viz. Rahstriya Chemicals and Fertilizers(RCF) Ltd, Mumbai, a Govt of India fertiliser
company. RCF and The Fertilizers and Chemicals Travancore(FACT) Ltd, another fertiliser company
owned by the Government of india, are also jointly setting Rapidwall manufacturing plantin Cochin,
kerala.
This Manual deals
the engineering design aspects of GFRG panel construction. Much of the
material presented here is adapted from the design manual presently in use in Australia
(“Rapidwall® Engineering Design Guidelines”, prepared by Dare Sutton Clarke, Australia).
Appropriate changes have been made to ensure conformity with the prevailing indian Standards,
and to incorporate recent research findings atllT Madras. There is a need for continued structural
testing of various aspects of GFRG panels, manufactured in India. GFRG panels, manufactured byRCF, Mumbai have been tested by IIT Madras and found to match the strength and performance
of panels manufactured in Australia, as specified by the technology provider.Details regarding the
method of construction and its sequence, including erection of GFRG panels, are explained in the
GFRG building construction manual.
Itis strongly recommended that structural engineers and building designers associated with GFRG
panel construction should be thoroughly familiar with the various structural design aspects, as
outlined in this Manual. It is also recommended that architects and construction engineers who
undertake GFRG / Rapidwall building design and construction gain familiarity with the properties
and material characteristics of Rapidwall and its applications and construction systems.
Dr. Devdas Menon (Professor)
Dr. A. Meher Prasad (Professor)
Structural Engineering Division
Department of Civil Engineering
Indian Institute of Technology Madras
Chennai 600 036, India
December 2013TABLE OF CONTENTS
PREFACE
eCmvranewne
10
a
12
13
14
15
16
7
18
19
20
REFERENCES
INTRODUCTION ..
NOTATION
PRODUCT DIMENSIONS ........
APPLICATIONS ..
MECHANICAL PROPERTIES
DESIGN PHILOSOPHY
AXIAL LOAD CAPACITY ......
OUT-OF-PLANE BENDING CAPACITY ......
SHEAR STRENGTH ..
IN-PLANE BENDING CAPACITY
DESIGN OF LINTEL...
DESIGN OF FLOOR / ROOF SLAB ..
ANALYSIS & DESIGN OF A TYPICAL MULTI-STOREYED BUILDING .....
LOW RISE AFFORDABLE MASS HOUSING .
GFRG PANEL AS INFILL WALL IN RC FRAMED CONSTRUCTION ....
ANNEXURE 1...
ANNEXURE 2....
ANNEXURE 3
ANNEXURE 4....
ANNEXURE 5...1. INTRODUCTION
This Design Manual provides guidelines and recommendations for the design of
GFRG /Rapidwall building panels as structural walling and flooring systems in
buildings. The Manual is intended to be used by structural design engineers, for the
purpose of ensuring that adequate strength and safety requirements are met with in
the design of such buildings. Designers are also advised to follow the guidelines given
in the Construction Manual for construction using GFRG building panels, joint details,
ete.
This Manual, which is a revision of an earlier 2003 version,has been prepared,
essentially based on the following references:
1.
RAPIDWALL'(2002) Engineering Design Guidelines, compiled by Ms Dare
Sutton Clarke Engineers, Adelaide, Australia,
RAPIDWALL (2001) Report on Physical Testing and Development of Design
Guidelines for the structural application of Rapidwall” in building construction
prepared by Ms Dare Sutton Clarke Engineers, Adelaide, Australia.
IS: 456 (2000), Code of practice for plain and reinforced concrete for general
building construction, Bureau of Indian Standards, New Delhi.
IS: 1905 (1987), Code of practice for structural use of unreinforced masonry,
Bureau of Indian Standards, New Delhi
SERC (2002), Evaluation of seismic performance of gypcrete building panels,
Structural Engineering Research Centre, Chennai, India; August 2002. Project
no. CNP 053241/2.
SERC (2002), Investigation on the behaviour of gypcrete panels and blocks
under static loading, Structural Engineering Research Centre, Chennai, india;
‘August 2002. Project no. CNP 053241/1.
IITM (2002), Material properties and assessment of gypcrete building panels,
Indian Institute of Technology, Madras, India; September 2002. Project no.
CE/BTCM/2557/2002.
Sreenivasa, R. L (2010), Strength and behaviour of glass fibre reinforced
gypsum wall panels, Indian Institute of Technology Madras, PhD Thesis.9. Janardhana, M. (2010), Cyclic behaviour of glass fibre reinforced gypsum wall
panels, Indian Institute of Technology Madras,PhD Thesis.
The main content of this Manual deals with the design of GFRG panels subject to
(i) axial compression, (ii) compression with out-of-plane bending and (ii) compression
with in-plane bending and shear. The design of lintels, slabs and pitched roofs are
also included.
GFRG building panels are considered with and without reinforced concrete as infill in
the cavities. Other data related to building design, such as fire resistance and sound
transmission, are also included in the guidelines. The guidelines are presented in
various Sections, each covering a specific property of GFRG building panel.
To facilitate design calculations, example problems are taken up for demonstration,
wherever appropriate. In Sections 13-15, detailed examples are provided for the
design of GFRG shear walls in multi-storeyedand low-rise buildings. The use of GFRG
panels as infill walls in RC framed construction is also demonstrated. All design load
calculations in this Manual in general are in accordance with IS:875 1987 - (Parts 1-
5) 1944324929) and IS:1893 2002 -(Part 1),
The design methodologies presented in this Manual may be treated as a set of
guidelines for the safe and efficient structural use of GFRG building panel in general
building construction, rather than as a strict code of practice. The guidelines are for
use by appropriately experienced and qualified structural engineers who are familiar
with concrete and masonry design and construction. The designers are expected to
have knowledge about the general behaviour of GFRG building panel2. NOTATION
A=
A=
a
mM =
Be
Ay
Aw =
B
& =
o =
DL
d=
dg =
4 =
e =
El =
EL =
fa =
Mz =
Muc-pero=
Gross cross-sectional area of panels with cavities
Net area of cross-section of concrete infill
Net area of cross-section of the panel
Design horizontal seismic coefficient
Total area of steel bars in a panel
Area of steel bar in a cell
Area of stirrup steel bars
Breadth of a section
Total design compressive force (factored)
Depth or width of cross-section
Dead load
Effective depth of cross-section
Base dimension of the building at the plinth level along the
direction of lateral force.
Effective depth
Eccentricity
Flexural
ity
Earthquake load
Characteristic cube strength of concrete
Stress in steel bars
Characteristic strength of stee!
Height of the building
Height of i" floor measured from base
Second moment of area
Importance factor
Length of panel
Live load
Factored bending moment
Out-of-Plane moment capacity, rib parallel to span
Out-of-Plane moment capacity, perpendicular to spanx)
xy
%
Ym
%
%
te
Design bending moment capacity
Number of floor levels at which masses are distributed
Percentage of tension steel
Factored axial load
Uni-axial Compressive Strength
Design axial load capacity
Design lateral force at i" floor
Response reduction factor
Spacing of stirrups (steel bars)
Thickness of panel
Time period of the building
Uni-axial Tensile Strength
Uniformly distributed load
Factored shear force
Ultimate shear strength
Design shear capacity
Design wind speed at a height z from the ground
Seismic weight of i"floor
Wind load
Distance from the centre of the panel to the centre of the
rebar in each cavity
Depth of compression zone
Distance to centroid of cross ~ section from base
Zone factor
Partial safety factor for load
Partial safety factor for GFRG building panel
Partial safety factor for reinforcing steel
Ratio of infilled cavities to total number of cavities
Stress
Nominal shear stress
Permissible shear stress3. PRODUCT DIMENSIONS
These design guidelines are applicable to GFRG building panels, presently
manufactured as Rapidwall®, for the typical dimensions and material properties
described in this manual. Typical dimensions of a GFRG building panel are
12.0m x 3.0m x 0.124 m, as shown in Fig. 3.1. Each 1.0 m segment of the panel
contains four ‘cells’. Each cell is 250 mm wide and 124 mm thick, containing a cavity
230 mm x 94 mm, as shown in Fig. 3.2. The various cells are inter-connected by solid
‘ribs’ (20 mm thick) and ‘flanges’ (15 mm thick), comprising gypsum plaster,
reinforced with 300 - 350 mm glass fibre roving, located randomly but centrally.
Ss
filam
Elevation
12 m: >
A
Plan 0.124m
Fig. 3.1: Typical Cross Section of GFRG Panel
250
Gypcrete glass fibre
(gypsum
“7 plaster+glass fibre S&S
+other
oe ‘nange’
y Me
> 20 << 230 ———_____>
All dimensions are in mm
Fig. 3.2: Enlarged View of a Typical Cell4. APPLICATIONS
GFRG building panels are generally used structurally in the following four ways:
1. Asload bearing walling(refer Fig.4.1) in buildings. When the cavities are filled
with concrete, the compressive strength gets enhanced considerably, and
when reinforcing bars are introduced, the panel's ability to resistlateral loads
is also enhanced, rendering such load bearing constructions suitable for
multi-storeyed housing. In single or two storeyed constructions (refer Fig.
4.2), the cavities may be filled with alternative non-structural material, such
as quarry dust mixed with 5% cement. In any case, it is recommended that
every third or fourth cavity, and at every joint or opening location, filling shall
be done with M20 concrete and reinforced with one 8mm reinforcing bar.
2. As partition infill walls in multi-storey framed buildings. Panels can also be
filled suitably. Such walls can also be used as cladding for industrial buildings
or sport facilities, ete.
3. As compound walls / security walls(refer Fig. 4.3).
4. As horizontal floor slabs / roof stabs(refer Fig. 4.4): with reinforced concrete
micro beams and screed (T-beam action). This system can also be used in
inclined configurations, such as staircase waist slabs and pitched (sloped)
roofing(refer Fig. 4.5)
4,1 Use as Load Bearing Structural Walling
In typical multi-storeyed constructions involving the use of GFRG as load bearing
structural walling, the connections between cross walls and with the foundations
and floor/rocf are achieved through reinforced concrete filling or R.C beams. All
GFRG wall panels at the ground floor are to be erected over a network of RC plinth
beams supported on suitable foundation (typically, strip masonry footings). ‘Starter
bars’ shall be embedded in the RC plinth beams, at the precise locations where the
cavities are to be filled with reinforced concrete, with appropriate lap length (refer
Figs 4.6 and 4.7). In the case of multi-storeyed buildings, where the base shear due
to lateral loading (wind or earthquake) is required to be transferred to the
foundation, appropriate detailing, such as provision of shear keys at the starter bar
locations, shall be provided.a
ic
a
a
a
7
Fig. 4.2GFRG demo building at IIT Madras
Note: A video describing details of the construction can be seen at:
http://www. youtube.com/watch?v=UUQEUCB7¢MMFig. 4.3 GFRG compound wall
(b)
Fig. 4.4 GFRG floor slab with micro beam and screedFig. 4.5 Small GFRG house with pitched roof
Fig. 4.6Erection of GFRG panels over plinth beam at site
3 starter bars
¢ cross beam RC plinth beam
=
minimum v
150 mm. &
minimum.
100 mm
Fig. 4.7 Provision of starter bars in RC plinth beams for the erection of GFRG panels10
For constructing an additional GFRG floor above an existing RC building, connectivity
between GFRG wall and the existing floor can be achieved by proper detailing
(insertion of starter bars with proper anchorage) as shown in Fig. 4.8. If the existing
floor slab does not have sufficient depth for anchorage, an ad
ional RC beam may
be constructed above the roof before erecting the GFRG walls.
imum 150mm deep
with suitable diameter
hole drilled to insert
starter bars & apply
lock fix solution
starter bars
min. 50d
Fig. 4.8 Starter bars in case of an existing RC floor/roof slab
When GERG panel is used as structural walling, an embedded horizontal RC tie beam
has to be provided on top of all the walls. Tie beam size of 200 mm depth and 94 mm
width is suggested by cutting and removing the top portion of the web of GFRG
panels as shown in Fig. 4.9.
4.2 Use as Floor /Roof Slabs
GFRG panel can also be used for intermediate floor slab/roof slab in combination
with RC (Refer Figs 4.4). The strength of GFRG slabs can be significantly enhanced by
embedding reinforced concrete micro beams. For providing embedded micro beams,
top flange of the respective cavity is cut and removed in such a way that minimum
25 mm flange on both end is protruded as shown in Fig. 4.4, RC concrete screed of
minimum 50 mm thickness is provided above the GFRG floor panel, which is
reinforced with weld mesh of minimum size of 10 gauge 100 mm x 100 mm. This RC
screed and micro beam act together as series of embedded T-beams. The thickness
of the RC screed, reinforcement and interval of embedded RC micro beams depends
on the span and intensity of imposed load. The connectivity between the horizontal
tie beam, embedded RC micro beams, concrete screed and vertical rods in GFRG
wall, ensures perfect connection between floor/roof slab and walling system (refer
Fig. 4.9).‘external
wall
{174mm
reinforcement
bar inter
‘connecting
‘micro beams
atexternal end
| at floor slab
\ evel
______GFRG wall panel for upper
ra floor
ae 10 gauge weld mesh at
100 x 100 mm at c/e
special ‘C’ anchorage
>< [1m tong)@ 0.75m ¢/c
between verticalrebars
and micro beam.
50 mm RC screed
embedded RC micro beam
in floor slab @ 0.75 m c/c
—=}- GFRG panel
Re pa at bearing into wall
| exnbedied RChorizonta
tie beam 200x84 mm
below floor slab
—. vertical rebar
~ ——GFRG wall panel
Fig. 4.9 Connectivity between floor slab and wall
oeMECHANICAL PROPERTIES
Table 5.1 provides a summary of typical mechanical properties of the GFRG building
panel. These properties have been determined from tests on GFRG building
panel’*®"*°), The compressive strength to be considered when the panel is filled
with concrete is given in Table 5.2'"5°7),
Table 5.1Mechanical Properties of GFRGBuilding Panel (Unfilled)
‘Mechanical Property Nominal Value Remarks
Unit weight : (0.433 kN/m?
Modulus of elasticity, Ee 7500 N/mm?
Uni-axial compressive strength, Pye 160 kN/m Strenettnebtetrad
from longitudinal
compression /
tension tests with
axial tensile strength, Tue 34-37 N/m oe
longitudinal direction
Ultimate shear strength, Voe 22.6 kN/m
Out-of plane moment capacity, Rib parallel
2.1 kNm /m
to span, Mec
‘Out-of plane moment capacity, Rib
(0.88 kNim /m
Perpendicular to span, Mycperr
Mohr hardness 16
Out-of-plane flexural rigidity, E, Rib parallel ee
35x10" Nmm'/m
to span
Outof plane flenural rigidity, El, Rib me
1.710" Nmm'/m
perpendicular to span
Coefficient of thermal expansion 240° mm/mm /°C
1.0%: ihr ‘Average water
Water absorption absorption by weight
ne % after certain hours:
of immersion
Fire resistance: aie
140/140/140 minutes
Structural adequacy/Integrity/Insulation Gina Alasah
Sound transmission cass (STC) 4048 150 1403-1996
12Table 5.2 Properties of compressive strength of GFRG building panel (filled with minimum
M20 grade concrete in all the cores)
Property Nominal Value Remarks
Obtained from longitudinal
eee een Be 1310kN/m’ | compression tests with ribs
7 in the longitudinal direction
Uni-axial compressive strength, Poe asealaunt a =
(one end fixed and other end hinged) 2s above
Ultimate shear strength, Vac 61 kN/mt Leng crt owe
Fire resistance: reas
minutes woe
Structural adequacy/Integrty/Insulation CSIRO, Australia
L
The nominal value of uniaxial compressive strength and in-plane shear strength of
partially infilled GRFG panel with M120 concrete (both ends fixed) may be calculated
as follows.
P= (160-+12007)kN/m (5.1)
V,,. = (21.6+38.47)kN/m (5.2)
where sis given by
Number of infilled cavities in the panel
5.3)
Total number of cavities in the panel ia
The typical stress-strain curve of GFRG under compression, obtained from tests on
4,
small prisms of 250mm high and 520mm wide is shown in the Fig.
Stress (MPa)
°
© 0.0005 0,001 0.0015 0.002 0.0025 0.003 0.0035
Strain
Fig, 5.1 Stress — strain curve of GFRG unfilled prism under compression
* Wu, Y. F, and M. P. Dare (2004), Axial and shear behaviour of glass fibre reinforced gypsum wall
panels: tests. Journal of Composites for Construction ASCE, 8(6), 569-78
+ Janardhana, M. (2010), Cyclic behaviour of glass fibre reinforced gypsum wall panels, Indian Institute
of Technology Madras, PhD Thesis.
1314
6. DESIGN PHILOSOPHY
The design capacities given in these guidelines are based on limit states design
procedures, considering the ultimate limit state for strength design, treating the
3.0 m high GFRG building panel as the unit material, and considering the strength
capacity as obtained from test results. The design should be such that the structure
should withstand safely all loads (as per relevant Indian Standards) likely to act on
the structure during its lifetime. It shall also satisfy serviceability requirements, such
as limitations of deflection and cracking. In general, the structure shall be designed
on the basis of the most critical limit state and shall be checked for other limit states.
6.1 Limit States Design
For ensuring the design objectives, the design should be based on the characteristic
values of material strengths and applied loads (actions), which take into account the
probability of variations in material strength and load. The design values are derived
from the characteristic values through the use of partial safety factors, both for
material strengths and for loads, for limit states of collapse and serviceability.
6.1.1Partial Safety Factors for Load, y,
The design must account for various combinations of loads acting on the structure
simultaneously. The various load combinations and corresponding partial safety
factor for loads shall be used as given in IS 456: 2000 "! as summarized in Table 6.1.
Table 6.1 Values of Partial Safety Factor y, for Loads
Load Combination Limit State of collapse Limit State of Serviceability
DL u WL/EL ao | WiLL
Duele 15 1s - 10 10 :
| 15 0r
DL+WL/EL ue . 4s 1.0 - 10
DL+LL+WL/eL 12 12 12 10 oa os
Note: - For the limit state of serviceability, the values of ygiven in this table are
applicable for short-term effects. While assessing long term effects due to creep, the
dead load and that part of live load likely to be permanent should be considered.
"this value is to be considered when stat
ity against overturning or stress reversal is critical6.1.2 Partial Safety Factor for Material, ym
The magnitude of partial safety factor for the material must take into account the
uncertainty related to the material strength. Although GFRG building panels are
manufactured under carefully controlled conditions, it is considered prudent to treat
the material like concrete, for which the partial safety factor specified in 1S 456: 2000
is 1.50, The partial safety factor for the GFRG building panel (with and without
concrete infill) shall be taken as 7m =1.50 in general. The above partial safety factor
yn = 1.50 is applicable to situations involving out of plane bending where the
observed mode of failure is brittleas well as in plane bending of RC filled GFRG
panels where the mode of failure is expected to be ductile.
In the case of reinforcing steel, the partial safety factor shall be taken as y= 1.15 in
all cases, as recommended in IS 456 : 2000.
While investigating serviceability limit states, the partial safety factor for all
materials should be taken as unity.
6.2Response Reduction Factor for Earthquake Resistant Design
Earthquake resistant design shall be carried out in compliance with the requirements
of IS 1893 (Part 1). In such design, an important and difficult task is the
determination of the response reduction factor (R). This is traditionally arrived at,
based on the general observed performance of similar buildings during past
earthquakes, estimates of general system toughness and the amount of damping
present during inelastic response. As GFRG buildings constitute a new type of
structure, a reasonable choice of R factor can only be made by comparing the GFRG
building system with traditional structures, such as reinforced concrete wall building
systems for which the response modification factors are already available.
GFRG walls are composite members with partial interaction, and the ductility of a
partially interactive member is generally greater than that of a fully interactive
reinforced concrete member. In terms of strength reserve, it is recommended that
the safety margin adopted for the design of GFRG walls be at least as large as that
adopted for concrete structures. Therefore, it is not unreasonable to treat buildings
constructed with GFRG walls as reinforced concrete shear wall structures and to16
adopt the R values from the respective code of practice (Wu 2009)"""!. Hence, the
response reduction factor (R) is taken as 3.0 (IS 1893-2002) for seismic load
calculations.7. AXIAL LOAD CAPACITY
While assessing the axial load capacity of GFRG building panel (under compression),
it is important to consider possible eccentricities in loading. A minimum eccentricity
(causing out-of-plane bending) must always be accounted for in the design.
7.1 Minimum Eccentricity
According to IS 456: 2000 (cl.32.2.2), the design of a reinforced concrete wall shall
take into account the actual eccentricity of the vertical force subjected to a minimum.
value of 0.05t (6.2 mm for panel thicknesst = 124 mm). As per IS 1905: 1987, the
design of a masonry wall shall consider appropriate eccentricity, which in no case
shall be taken to be less than t/24 (5.2 mm for t= 124 mm).
In the case of wall panels supporting floor slabs from one side only, the eccentricity
to be considered should be more than the minimum values indicated above. It is
recommended that a value of minimum eccentricity equal to /6 (i.e., 20.7 mm)
shall be considered conservatively. Additional value of eccentricity may be
considered when out-of-plane bending is explicitly involved (for example, action of
local wind effects on an exposed walll panel).
7.2 Axial Compressive Strength
The characteristic values of axial compressive strength of the GFRG building panel,
expressed in kN/m, are obtained from compression test results on GFRG building
panel for full height panel, subject to various eccentricities of loading (20 mm, 30
(gan
mm and 45 mm) and different boundary conditions’ In general, it is
conservative to assume pinned — pinned condition, as shown in Fig. 7.1.
1718
as
ie
Ia tt et at teeta
|
Fig. 7.1 Experimental setup for pinned — pinned panels
It may be noted that, for design purposes, the reported nominal values should be
divided by ym = 1.5. The design values (including partial safety factor) are depicted in
Figs 7.2 and 7.3, corresponding to unfilled and filled cases respectively, assuming a
linear variation of axial load with eccentricity.Unfilled Panels
The design axial load capacity (Pz), including partial safety factor, of the unfilled
GFRG building panel can be found from the following equation for all heights of the
wall less than 3.0m (assuming pinned-pinned end conditions).
Pg = (680.92) (7.4)
where, e is eccentricity in mm and Pug is in KN/m.
80.0
60.0
400
200
Axial load capacity PyskN/m.
00
° 5 10 15 20 2s
Eccentricity, e (mm)
Fig.7.2 Axial Load capacity of unfilled GFRG building panel for all
heights of walls < 3 m with both ends pinned
19Filled Panels
The design axial load capacity (P,.), including partial safety factor, of the filled GFRG
building panel (filled with minimum M 20 grade concrete) can be found from the
following equation for all heights of the wall less than 3.0m (assuming pinned-pinned
end conditions).
P., =(600-13.75e) (7.22)
where, e is eccentricity in mm and Py is in kN/m.
The contribution of reinforcing bars in compression shall be ignored. Experimental
studies"have established that there is no significant enhancement in strength
under pure compression due to the presence of rebars, as the failure is caused by
buckling of the panel.
600.0
E
z
= 2000 = |
7
2
E 200 +—+_+_+ + } 1} 1 fy
3 |
& } |
|
00 !
° 5 10 15, 20 25
Eccentricity, e (mm)
Fig 7.3 Axial load capacity for concrete filled ( > 20 MPa) GFRG
Building panel for all wall heights (< 3m) with both ends pinned7.3 Design Example
‘An external GFRGbuilding panel of 3.0 m high, filled with 20MPa concrete, is
required to resist a vertical load from the roof, comprising a dead load of 7SkN/m
and alive load of 25kN/m at service stage. Check the adequacy of the panel to resist
the vertical load.
The factored axial load on the wall panel is given by 1.5 DL + 1.5 LLas:
P, = 1.5 x (75 +25) = 150 kN/m
Minimum eccentricity =t/6 =20.7mm
Applying equation (7.2), design capacity in axial compression,
P., =(600-13.75x20.7) = 315.4 kN/m >P,= 150 kN/m;Hence, OK.
28. OUT-OF-PLANE BENDING CAPACITY
Unfilled GFRG Panels
The out-of-plane design flexural strength of the 124 mm thickGFRGbuildingpanel
without concrete filling is given in Table 8.1. The bending capacity depends on the
orientation of the ribs, with respect to the direction of bending. Higher capacity is
obtained when the ribs are oriented parallel to the span.
Table 8.1 Out-of-Plane Design Flexural Capacity of Unfilled GFRG Panel
Ribs parallel to span _—Ribs perpendicular to span
Deslpu Moment 1.4 kNm/m 0.59 kNm/m.
Capacity, Mag - J
Filled GFRG Panels
When the cavities are filled with concrete, some enhancement in strength can be
expected, provided the ribs are aligned parallel to the span. However, full composite
action of GFRG and concrete cannot be mobilized on account of bond slip at the
inferface. A conservative estimate of the moment capacity can be arrived at by
ignoring the contribution of GFRG and considering the action of the concrete beams
occupying the cellular cavities (230 mm wide and 94 mm deep), spaced at 250 mm
intervals. Accordingly, considering modulus of rupture of concrete as 0.7\//, and
applying a partial safety factor of 1.5, the design moment capacity can be derived as
follows
My =[(0 71120) x(230%94" /6)x10 “Vousxo. 250) = 2.83 kNm/m
Further enhancement in capacity is possible by embedding and anchoring reinforcing
bars in the middle of the cavities, and designing the reinforced concrete beam
elements in accordance with requirements of IS 456-2000. This is demonstrated, by
means of an example in section 8.1.
8.1 GFRG Wall Panel Resistance against Wind Loading
The external walls of the building are subjected to wind pressures. It is necessary to
check the flexural resistance of the GFRGwallpanel against such loading. One waybending action of the panel (full height of 3m) can be assumed conservatively, with
simply supported end conditions and a pressure coefficient of unity.
Unfilled GFRG Panels
From Table 8.1, design moment capacity, Mug =1.4kNm/m
).6(V2)° x3? x(1/8) x 1.5
Equating this moment to the design moment capacity of the panel,
0.6 (V,)? x 3? (1/8) x 1.5 = 1.4.x 1000Nm/m
Design bending moment in the panel due to wind load =
=> V, = 37.2 m/s. (max. safe wind speed for unfilled panel)
Filled GFRG Panels
If the wind speedV.exceeds the above limit, the panel needs to be filled with
concrete and suitably reinforced, as required. In the absence of any reinforcement,
considering filling with concrete of minimum M20 grade,
0.6(V.) x3? x(1/8)x1.5 = 2.83 x 1000 Nm/m.
=, =52.9m/s.
The capacity can be further enhanced by providing one or two rebars in the middle
of each cavity. However, as the bar location is close to the centroidal axis of the
section, the enhancement in capacity may not be significant, for out-of-plane
bending (unlike in-plane bending).
For example, providing 210 mm dia bar (Fe 415 grade steel) at the centre of each
cal
filled with M20 concrete and designing as a reinforced concrete beam section
as per IS 456: 2000.
Effective depth,d = (124-2 15)/2
As = (78.5 1000) /250
47mm
314 mm?/m
Neutral axis depth, x,, assuming the section to be under reinforced
= (0.87 x 415 x 314) / (0.36 x 20 x 1000) = 15.7 mm
< 0.48 x 47 = 22.6 mm (under reinforced)
Mus = (0.87 x 314x 415 x (47 0.42 x 15.7)
= 4,58 x 1000 Nm/m24
Equating the above value to the design bending moment in the panel due to wind
load,
0.6(V.)° 3? x(1/8)x1.5 = 4.58 x 1000 Nm/m
=, =67.3 m/s.
In the case of tall buildings, special care shall be taken to ensure that the panels have
the desired flexural strength to resist the prescribed design wind speeds (as per IS
875 part 3), including the enhancement in wind speed with height.9. SHEAR STRENGTH
The unit shear strength capacity of the 124 mm thick, 3.0 m high GFRGpanel is given
Table 9.1. The ultimate design shear strength of a GFRGpanel is given by the unit
shear capacity in Table 9.1 multiplied by the length of the panel??""4),
Table 9.1 Shear Strength of GFRG Panel as Vertical Walls
Application Design Shear Capacity, V4 (kN/m)
Untled GFRG panel aa
{FRG panelled with 20 MPa concrete =]
GFRG panel partially filled with 20 MPa
442567
concrete ad
(where,1) is defined asin Eq. 5.3)
In a multi-storeyed construction, using GFRG wall panels as load bearing
construction, different walls will be subjected to different shear forces, at any storey
level under consideration. Longer walls, which are stiffer, will attract more lateral
shear. The maximum length of an individual shear wall segment may be limited to
3.5 m in the finite element model used for analysis under factored loads. The
average value of factored shear force calculated for all walls in any one direction at
any storey level shall not exceed the value indicated in Table 9.1. In few walls, some
local increase (up to 20 percent) in shear capacity may be permited, provided the
average value for all walls (combined) is within the prescribed limit. Double walls
may be provided, if there is a higher demand for shear strength.
In wall construction for multi-storeyed buildings, all cavities should be filled with
concrete (of grade not less than M20) and reinforced appropriately. The design of
such reinforcement
discussed in the Chapter 10. The rebars shall be provided for
the full height in filled GFRG panels. In any case, for both filled and unfilled GFRG
wall panels at the interface with foundation plinth beam, starter bars should be
provided in each cell embedded in concrete (of strength not less than 20 MPa) for a
depth of 450 mm for adequate shear transfer.
2526
10. IN-PLANE BENDING CAPACITY
10.1 Introduction
GFRG panels can be used not only as load bearing walls, but also as walls transferring
lateral loads, resisting axial force (P), lateral in-plane shear force (V) and in-plane
bending moment (M). Invariably, such wall panels shall be filled with concrete and
reinforced with steel.
The in-plane bending capacity of the walls depends on its length, the reinforcement
provided, as well as the level of axial load and lateral shear. The design in-plane
bending capacity (M,g) and its relationship with the design axial load capacity (Pus) is
usually described by means of a Pys - Mus interaction diagram. The values of Mus
increase with the length of the wall. However, experimental studies of GFRG panels
subjected to lateral loading have shown that failure is initiated by vertical cracking
caused by shear failure of the GFRG skin", Following such vertical cracking, the wall
segments separated by the vertical cracks tend to behave independently, although
their deformations at the top and bottom are governed by the corresponding
deformations in the connecting floor diaphragm. Hence, for all practical purposes,
the in-plane bending capacity is limited by the corresponding shear capacity. Longer
shear walls tend to attract larger lateral loads and will form vertical shear cracks in
the middle region, causing a further redistribution of forces, and possible further
vertical shear cracking.
Hence, under factored lateral loads (earthquake or wind), it is recommended that in
the finite element model, the long walls are suitably segmented such that no
segment exceeds 3.5 m in length. Also, while modelling, care should be taken to
consider T, Land | shaped flanged sections as being made up of separate rectangular
segments with no shear transfer between them.
Tests have shown that providing two vertical bars in each cavity generates improved
performance than a single bar”), At the end of this chapter, axial load ~ moment
interaction diagrams (design charts), for various wall lengths, varying from 1.0 m to
3.5m with increments of 0.25 m, for various bar diameters (8 to 18 mm) of Fe 415
and Fe 500 grade steel, M20 and M25 grade concrete, are furnished for convenientuse in the design office. The basis for generating these design charts is explained in
Section 10.2.
10.2 Basic Design Procedure for P,g- Mug Interaction Diagram Generation
Generation of the interaction diagram of a typical GFRGbuildingpanel is based on a
simplified procedure, which is a modified version of the ‘lower bound solution’,
originally proposed by Wu (2009). Certain assumptions are made to develop the
approximate interaction curve from the principles of mechanics.
The cross section of a typical GFRG panel infilled with concrete and reinforcement
bars in each cell is shown in Fig. 10.1a. The behaviour of theGFRG panel infilled with
concrete depends on the bond between the concrete and the GFRG panel. This is
reflected in the variation of normal strain (in the vertical direction) along the length
of the wall, as shown in Fig. 10.1. If there is no bond, there would not be any
interaction between them, resulting in small strain with multiple neutral axes, as
shown in Fig. 10.1b. If it is assumed that the concrete cores are fully bonded to the
GFRG panel, then the “plane section remain plane” assumption is valid for the entire
section and the strain profile will be a straight line with a single neutral axis, as
shown in Fig. 10.1c. This behaviour is similar to a reinforced concrete flexural wall
However, the limited bond between the concrete cores and the GFRG panel is
difficult to quantify. The probable strain profile is likely to be as shown in Fig. 10.14.
linear ‘lower bound’ assumption of strain profile can be assumed with the ultimate
compressive strain (£,), as shown in Fig. 10.1d. The value of ¢., is limited by the out-
of plane buckling strength of the panel and includes enhancement due to strain
gradient for short wall lengths.
27Reinforeement bys GFRG panel Coneee
Strain profile for full |
interaction
‘Average noflinear stain
profile for fartial
Stl profile op lower frmemection
ound soluon |
(d) Strain profile- partial interaction case
OD
Fig. 10.1 Strain Profiles for Nil, Full and Partial Interaction between GFRG panel and Concrete
10.2 .1 Distribution of Strain at Ultimate limit state
Fig. 10.2 depicts how the value «,, is to be computed depending on the location of
the neutral axis x, (from the extreme compression location), which in turn depends
on the eccentricity of loading, e= M,,/P.,.
Case 1: Pure compression (x,->0)
Under pure compression, (¢>0, x, >),<., is limited to:
(10.1)where p is the compressive stress of the wall at the axial buckling load (to be taken
as 1360/1.5 = 907 kN/m, refer table 5.2) and E is the effective Young’s modulus of
the composite wall given by
Fedct Eo Ae (10.2)
Act,
where Ac and Ag are the areas of the concrete and the GFRG panel, respectively; and
F, = 5000/7, (in MPa) and Ez are the values of elastic modulus of concrete and the
GFRG panel (refer table 5.1) respectively. Typical values of E using M20 and M25
grades of concrete are 17860 MPa and 19500 MPa respectively.
D
Edge 1 [SSR EES Cen eas] Edgez] t= 124
i Pivot point
e=0,x,=0
(case 1)
Ey = (1+ ale
Eu = (1405 Qe
fe—_——De nto, —___| __}
Fig. 10.2 Recommended strain profile for design
Case 2: Pure bending (xu= kumi
For the extreme case of pure in-plane bending (¢—> 0, x, =X, nu, , an enhancement
over é,. is proposed as follows:
Ex = B(14) (10.3)
(10.4)
0.8(2-D) : for 1s D<2.0m
where ale
0 : for D> 2.0m
Case 3: Neutral axis at edge of section (x,= D)
For the case, x, =D, the value of ¢., shall be taken as:
299 (1+0.5a) (10.5)
Case 4: Neutral axis outside section (x,>D)
When the neutral axis lies outside the section (x, > D), the maximum compressive
strain ¢., =6,,. can be calculated by linear interpolation. The point of intersection of
the two limiting strain profiles, corresponding to x, = D and x, = , acts like a ‘pivot’
point through which all strain profiles pass when x, >D, as shown in Figure 10.2. The
values of the maximum compressive strain at edge 1, eaux, and strain at edge 2,
Eqw2are accordingly given by:
for x,>D (10.6)
for x.>D (10.7)
1
where, -of2 ) (10.8)
1+05a
Case 4: Neutral axis inside section (x,
pDIkN/m; =0kNm/m
where Dis in m.Nala
Fig.10.3 Typical Py ~ My interaction curve
Between points A and B:x, > D
(10.10)
(10.11)
(10.12)
Between points B and C:x,,,
fy,
ote
b) Stress variationFig. 10.5 Stress and strain variation across cross section after steel yields
The resultant compressive force (F,), the resultand tesile force (F,), and the
values of P_and M,. can be calculated from Fig.10.5, as follows.
pa lite)pts, (9.16)
F,=05f,a, x (9.17
where, (9.18)
(9.19)
(9.20)
(9.21)
(9.22)
where Xp is the distance from the right side of the panel, as shown in Fig.10.5,
through which the resultant of forces Frrand Facts.
10.2.3 Design Charts
Design interaction curves of GFRG panels fully infilled wi
reinforced concrete (with
‘two reinforcement bars in each cavity) for 1.0m to 3.5m with intervals of 0.25m, are
shown in Figs 10.6 to 10.16.
For low/medium rise buildings, all cavities need not be infilled with reinforced
concrete. In general, for low rise (up to 3 storeyed) GFRG houses/buildings, it is
recommended that not more than three cavities may be provided in between the
infilled ones, and those cavities may be suitably filled with concrete or alternative
materials such as mixture of quarry dust and grout, sound insulating materials, etc.
Since the lateral forces due to earthquake are lesser in low/medium rise buildings,
the infilled cavities may be reinforced with a single reinforcing bar, as per the design
requirement. Design interaction curves of GFRG panels partially/fully infilled
concrete and reinforced with a single bar are given in
‘igs 10.17 to 10.40. The
application of these curves are demonstrated in Chapter 14,1050
z —27-8mm
200 —27-10mm
750
z=
© 450
300
1.0 m wide
4150 -|M20 concrete
Fe4is
~ Fe 500
0
0 25 50 75 100 125 150 175
M, (kN-m)
(a) using M20 concrete
1200
Seis) —2v-8mm
1050 —27-10mm
—27-12mm
900 —2v-16mm
—27-18mm
750
z
= 600
e
450
300 1.0m wide
M25 concrete
oon Feais
7 Fe S00
0 3s 50 7s 100-1250 180175200
™, (kN-m)
(b) using M25 concrete
Fig. 10.6 Design P,-M, plots for 1.0 m wide GFRG panel with two bars in each cavity1200
Baaeeees — 2.8mm
1050 2-10 mm
212mm
900 —2Y-16mm
—2y-18mm
750
z
= 600
“d
450
300 11.25 m wide
M20 concrete
150 Fe 415
Fe 500
°
0 25 50 75 100 125 150 175 200 225, 250
™, (kN-m)
{a) using M20 concrete
1350
1200
1050
900
z 750
e 600
450
1.25 m wide
M25 concrete
Fe ais
Fe 500
300
150
0 25 50 oEy 100 125 150 175 200 225 250 275
‘M,, (kN-m)
(b) using M25 concrete
10.7 Design P,-M, plots for 1.25 m wide GFRG panel with two bars in each cavity
351500 +
‘asd —2-8mm
—27-10mm
1200 212mm
1050 —27.16mm
—27.18mm
_ 900
z
3 750
=
609
450
300 1.50 m wide
M20 concrete
150 Fe ais
2====" Fe 500 a
° |
0 25 50 75 100 125 150 175 200 225 250 275 300
™M, (kN-m)
(a) using M20 concrete
1650
—2)-8mm
a —27-10mm
1350 2.2mm
216mm
aad —2y-18mm
1050
J 200
a 750
600
450
1.50 m wide
300 | M25 concrete
150 Fe 41s
~-->>" Fe 500
°
© 25 SO 75 100 125 150 175 200 225 250 275 300 325
M, (kN-m)
(b) using M25 concrete
Fig. 10.8 Design P,-M, plots for 1.50 m wide GFRG panel with two bars in each cavity1800
1500
2100
1800
1500
-1200
= 500
00
300
278mm
2710 mm
272mm
27-16 mm
2718 mm
1.75 m wide
M20 concrete
Fe ais
Fe 500
50
100 150 200 250 300 350
1M, (kN-m)
{a) using M20 concrete
1.75 m wide
M25 concrete
Fe ais
Fe 500
Sees] 2mm
—21-10mm
—2¥-12mm
276mm
—2V-18mm
50
100180200250, 300350400
M,(kN-m)
(b) using M25 concrete
Fig. 10.9 Design P,-M, plots for 1.75 m wide GFRG panel with two bars in each cavity
372100
—2V-amm
1800 — 210mm
—2)-12mm
2-16 mm
i508) —2V-18mm
= 1200
2
* 900
600
2.0m wide
300 M20 concrete
Fe 415
~---~ Fe 500
°
° so 100» 150-200-250 300380400
(M,(kN-m)
(a) using M20 concrete
2100
1800
1500
120
* 900
600
2.0m wide
goo M25 concrete
Fe ais
~---~- Fe 500
°
0 50 100150. 200-250-300 380400450
M, (kN-m)
(b) using M25 concrete
Fig. 10.10 Design P,-M, plots for 2.0 m wide GFRG panel with two bars in each cavity2100
Aaa] 272mm
1800 —2Y-10mm
—2y12mm
—27-16mm
=e 218mm
g10
© 900
600 fa
2.25 m wide
M20 concrete
300
Fe 415
Fe 500
°
0 50 100-150-200 250-300-350 400450500
M, (kN-m)
(a) using M20 concrete
2400 ee
SSS) 2.8mm
2100 —2y-10mm
212mm
1800 —27-16mm
218mm
1500
=z
= 1200
=
900
600 12.25 m wide
M25 concrete
20 Feais
Fe 500
ot
0 50 100 150 200 250 300 350 400 450 500 550
1M, ({kN-m)
(b) using M25 concrete
Fig. 10.11 Design P,-M, plots for 2.25 m wide GFRG panel with two bars in each
cavity2400
278mm
—27-10mm
2000 27-122 mm
216mm
Sa 218mm
z
21200
<
800
2.50 m wide
400 M20 concrete
Fe ais
Fe 500
° |
o 100 200 300 400 500 600
™, (kN-m)
(a) using M20 concrete
2800
—2v.8mm
—27-10mm
—27-122mm
—2¥-16mm
2000 —27-18mm
=1600
z
©1200
800 +
2.50 m wide
M25 concrete
Feais
Fe 500
° 100 200 300 400 500 600 700
™,{kN-m)
(b) using M25 concrete
Fig. 10.12 Design P,-M, plots for 2.50 m wide GFRG panel with two bars in each
cavity[Eales View ale aisle Se ses)
(ae gm
2400 210mm
212mm
2000 —2y-16mm
218mm
= 1600
z
a 1200
800
2.75 m wide
M20 concrete
4
Pe Feais
ooo7 Fe 500
°
© 100-200-300 400-500 600700800
1M, (kN-m)
(a) using M20 concrete
3200
Soe an
2800 + 21-10
—2V-12mm
ciate —2v-16 mm
—21-18mm
2000 +
E 1600 |
=
1200 4
800 12.75 m wide
M25 concrete
400 Fe 415
~ Fe 500
°
0 100» 200 300 400«S S00. 600-700» 800
'M, (kN-m)
(b) using M25 concrete
Fig. 10.13 Design P,-M, plots for 2.75 m wide GFRG panel with two bars in each
cavity
412800
2400
2000
1600
P, (KN)
3.0 m wide
4q0 {M20 concrete
Feais
Fe 500
0 100-200» «300400 500 600.700» 800900
M, (kN-m)
{a) using M20 concrete
3200
aa aaa)
et —2y-10mm
an —2V-12mm
—2"-16mm
2000 —2r-18mm
z
© 1600
=
3200
800 [3.0m wide
M25 concrete
ana! Fe ais
Fe 500
op Pa
© 100-200-300 400 500 600-700-800 900 1000
M,, (kN-m)
(b) using M25 concrete
Fig. 10.14 Design P,-M, plots for 3.0 m wide GFRG panel with two bars in each cavity3200
2800
2400
2000
1600
P, (kN)
1200
800 73.25 m wide
M20 concrete
Feais
Fe 500
400
—27-8mm
—2v-10mm
—2V-12mm
—2V-16 mm
2-18 mm
0 100-200
3600
3200
2800
2400
(KN)
00 13.25 m wide
M25 concrete
Fe ais
Fe 500
400
300
400 500 600 700
M, (kN-m)
{a) using M20 concrete
800 900 1000
—2)-8mm
—2V-10mm
—2V-12mm
—2v-16 mm
27-18 mm
0 100 200
300
400 500 600 700 800
™M, (kN-m)
(b) using M25 concrete
900 1000 1100
Fig. 10.15 Design P,-M, plots for 3.25 m wide GFRG panel with two bars in each
cavity3800 ae
ton
—2710mm
3000 2.2mm
—2y-16mm
2500 218mm
= 2000
=
© 1500
1000
3.50 m wide
120 concrete
500
Fe ais
~Fe 500
o
° 200 400 600 800 1000 1200
1m, (kN-m)
(a) using M20 concrete
4000
3500
oa —27.18mm
2500
=
© 2000
=
1500
1000 3.50 m wide
M25 concrete
oe Fe 415,
Fe 500
°
° 200 400 600 goo 100012001400
1M, (KN-)
(b) using M25 concrete
Fig. 10.16 Design P,-M, plots for 3.50 m wide GFRG panel with two bars in each
cavity200 —Temm
1100 10mm
—v12mm
1000 —v16mm
900 118mm
800
700
600
500
400
300 11.25 mwide
M20 concrete
Fe 415}
+ Fe 500
P, (kN)
200
100
0 2 40 60 80 100 120 140 160 180 200
M, (kN-m)
Fig. 10.17Design P,-M, plots for 1.25 m wide GFRG panel with all cavities infilled
with M20 concrete and alternative cavitiesreinforced with single bar
800
750
700
650
600
550
500
450
400
350
300
250
200 17.25 m wide
150 720 concrete
ao Fe 4i5|
am Fe 500
oF
© 10 20 30 40 50 60 70 80 90 100 110 120 130 140
M, (kN-m)
a=
110mm
=3/5 —y-12mm
16mm
18mm
P, (KN)
Fig. 10.18Design P,-M, plots for 1.25 m wide GFRG panel with alternative cavities
infilled with M20 concrete and reinforced with single bar1800
a
110mm,
a n=. —Y-l2mm
1800 —Y.16mm
18mm
1200
(KN)
800
600
400 1.75 m wide
M20 concrete!
200 Fe ais
Fe 500
°
° 40-80 = 120 160-200-240 280320
™M, (kN-m)
Fig. 10.19Design P,-M, plots for 1.75 m wide GFRG panel with all cavities infilled
with M20 concrete and alternative cavities reinforced with single bar
3100
1000
900
800
700
600
500
400
300
P, (kN)
200 +120 concrete|
0 20 40 60 80 100 120 140 160 180 200
MM, (kN-m)
Fig. 10.20Design P,-M, plots for 1.75 m wide GFRG panel with alternative cavities
infilled with M20 concrete and reinforced with single bar2200
a
2000 —V10mm
12mm
1800 116mm
1600 18mm
1400
= 1200
1000
800
£00 13.25 m wide
400. M20 concrete
200 Fe Als
Fe 500
i e
0 40 80 120 160 200 240 280 320 360 400 440 480
M, (kN-m)
Fig. 10.21Design P,-M, plots for 2.25 m wide GFRG panel with all cavities infilled
with M20 concrete and alternative cavities reinforced with single bar
a —Ysnm |
—V-10mm
1200 = 5/9 ——y-12mm
—V16mm
—V-18mm
1000
gm
= 600
400
2.25 m wide
200 -|M20 concrete
Feais
===: Fe 500
°
0 40 80 120 160 = 200280280
1M, (kN-m)
Fig. 10.22Design P,-M, plots for 2.25 m wide GFRG panel with altern:
infilled with M20 concrete and reinforced with single bar
cavities2800
2400
2000
P, (KN)
2.75 m wide
M20 concrete|
0 100 200 300 400 500 600 700
Fig. 10.23 Design P,-M, plots for 2.75 m wide GFRG panel with all cavities infilled
with M20 concrete and alternative cavities reinforced with single bar
1600
oo
n=6/11
1400
16 mm
1200 8mm
1000
2 200
=
600
400 12.75 m wide
M20 concrete
Fe ais
Fe500
200
0 40 80 120 160 200 240 280 320 360 400 440
M, (kN-m)
Fig. 10.24Design P,-M, plots for 2.75 m wide GFRG panel with alternative cavities
infilled with M20 concrete and reinforced with single barP, (kN)
800 13.25 m wide
20 concrete|
Feais
Fe 500
0 100 200 300 400 s00 600 700 800 900 1000
m, (kN-m)
Fig. 10.25Design P,-M, plots for 3.25 m wide GFRG panel with all cavities infilled
ies reinforced with single bar
(KN)
3.25 m wide
Fe4is
~~ Fe 500
© 50 100 150 200 250 300 350 400 450 500 550 600
M, (kN-m)
Fig. 10.26Design P,-M, plots for 3.25 m wide GFRG panel with alternative cavities
infilled with M20 concrete and reinforced with single bar1000
800
— 600
z
=
400
1.0 m wide
200 | |M20 concrete
Fe 415
Fe 500}
i 3
o 20 40 60 80 100 120 © 140
™, (kN-m)
Fig. 10.27Design P,-M, plots for 1.0 m wide GFRG panel with all cavities infilled with
M20 concrete andend cavities reinforced with single bar
550
500
450
350
300
250
P, (kN)
200
150 4[1.0 m wide
M20 concrete|
Feais
~- Fe 500
100
50
ov @ ££ Oo Se oS DM fb wf
M, (kN-m)
Fig. 10.28Design P,-M, plots for 1.0 m wide GFRG panel with end cavities only
infilled with M20 concrete and reinforced with single bar1600
1400
1200
1000
800
PAKN)
600
1.75 m wide
400 + M20 concrete
Fe als
Fe 500
200
© 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320
M, (kN-m)
Fig. 10.29Design P,-M, plots for 1.75 m wide GFRG panel with all cavities infilled
with M20 concrete andevery third cavityreinforced with single bar
900
=o — en
an 20mm
n=3/7 —¥a2mm
y6mm
0 —Y-18mm
600
= 500
& 400
300
200 [175m wide
M20 concrete
100 Fe 415
o [oo Feso0]
0 82 8640 «| 820060
M, (kN-m)
Fig. 10.30Design P,-M, plots for 1.75 m wide GFRG panel with every third cavity
filled with M20 concrete and reinforced with single baron ame
ne
joan
in
i
i
om
1000
800
600 |2.50m wide
Fp ouedl
= Fe 415.
=~ Fe 500
P. (KN)
200
© 40 80 120 160 200 240 280 320 360 400 440 480 520 560
™, (kN-m)
Fig. 10.31Design P,-M, plots for 2.50 m wide GFRG panel with all cavities infilled
with M20 concrete andevery third cavityreinforced with single bar
1200
1000
800
600
(KN)
2.50 m wide
200 {M20 concrete|
Fe ais
Fe500
° 40 80 120, 160 «= 200 240,280
M, (kN-m)
Fig. 10.32Design P,-M, plots for 2.50 m wide GFRG panel with every third cavity
infilled with M20 concrete and reinforced with single bar
523200
eo SSS) vem
110mm
2800 net —ya2mm
1.6mm
2400
2000
:
2 1600
=
3200
800 13.25 m wide
M20 concrete
Fe 415
bE Fe 500
400
© 100 200 300 400 S00 600 700 800 900 1000
M, (kN-m)
Fig. 10.33Design P,-M, plots for 3.25 m wide GFRG panel with all cavities infilled
with M20 concrete andevery third cavityreinforced with single bar
1600
so)
1400 n=5/13- —y.12 mm
16mm
1200
1000
= 800
a
600
400 {3.25 m wide
M20 concrete|
Fe 41s
= Fe 500
200 4
0 50 100150 200» 250-300-350 400450
1M, (kN-m)
Fig. 10.34Design P,-M, plots for 3.25 m wide GFRG panel with every third cavities
infilled with M20 concrete and reinforced with single bar1200 eT
1100 —V10mm
12mm
seat —Y-16mm
900 118mm
800
700
600
500
400
300
200
100
P, (kN)
1.25 m wide
M20 concrete|
Fe 415
Fe 500
0 2 4 60 80 100 120 140 160 180 200
M, (kN-m)
Fig. 10.35Design P,-M, plots for 1.25 m wide GFRG panel with all cavities infilled
with M20 concrete andend cavities reinforced with single bar
600
550
500
450
400
350
300
250
200
150 41.25 m wide
100 -|M20 concrete!
Fe ais
Fe 500|
(kN)
50
0 10 2 3 4 So 60 70 80 90 100
M, (kN-m)
Fig. 10.36Design P,-M, plots for 1.25 m wide GFRG panel with end cavities infilled
with M20 concreteand reinforced with single baran em
2000 ve 10mm
12mm
1800 116mm
—V.18mm
1600
1400
1200
1000
800
600 {2.25 m wide
400 {M20 concrete|
Fe ais
Fe 500
P,, (kN)
200
© 40 80 120 160 200 240 280 320 360 400 440 480
M1, (kN-m)
Fig. 10.37Design P,-M, plots for 2.25 m wide GFRG panel with all cavities infilled
with M20 concrete andevery fourth cavityreinforced with single bar
900
Soo oss as
=3/9. 12mm
"16mm
800
700
600
500
P, (kN)
490
300
290 225m wide
M20 concrete|
100 Fe ais
Fe 500
°
0 2 40 60 8 100 120 140 160 180 200
M, (kN-m)
Fig. 10.38Design P,-M, plots for 2.25 m wide GFRG panel with every fourth cavity
infilled with M20 concrete and reinforced with single bar
553200
SSS SSeS
—V-10mm
2800
2400
2000
11600
(KN)
1200
300 [325m wide
M20 concrete
Fe ais
Fe 500
0 100 200 300 400 500 600 700 800 900 1000
M,(kN-m)
Fig. 10.39Design P,-M, plots for 3.25 m wide GFRG panel with all cavities infilled
with M20 concrete andevery fourth cavityreinforced with single bar
1400
=r
rr): YS
1200 n=4/13, —y12mm
16mm
50 18mm
z
= 600
400
3.25 m wide
M20 conerete
200
Fe ais
-----+ Fe 500
°
0 50 100150, 200250 300350400
M, (kN-m)
Fig. 10.40Design P,-M, plots for 3.25 m wide GFRG panel with every fourth cavity
infilled with M20 concrete and reinforced with single bar11. DESIGN OF LINTEL
GFRGpanels above window and door cut-outs can be used as lintels to support
superimposed loads. These design guidelines are based on simply supported
conditions. For lintels that are actually framed above an opening, to limit creep
deflection, they may be treated as simply supported.
ribs
250 mm. 1
1
t
unfilled i
lintel i D
|
i
i
span
(a)
20 MPa or above concrete filling ribs reinforcing bar
oe ! |
i
use j
i
i D
i
i
v i
som i
A 350mm !
<> span
(b)
Fig. 11.1 Details of lintels
Note: To maintain a continuous concrete compression zone, the top 150 mm of
connecting ribs must be removed.
11.1 Unfilled Lintels
The design moment capacities of unfilled lintels are given in Fig.11.2°), Shear
strength checks are not required for beams with aspect ratios (D/L) less than 0.Design moment capacity, M, (kNm)
300 400 00 600 700 800
Depth of lintel (mm)
Fig. 11.2 Design moment capacity of unfilled lintel
The displacement of lintels can be calculated with the flexural rigidity €/ provided in
Fig. 11.3.
Note: Due to the variable influence of the connecting ribs, Elvaries with both depth
and span of the lintel.250
200
£1x10"9(N/mm?)
50
° os 1 1s 2 25 3 35
‘Span of lintel (m)
Fig. 11.3 Elastic ri
ity of unfilled lintels
11.2 Concrete Filled Lintels
Flexural strength
The flexural strength of lintels shall be calculated in accordance with 1S:456-2000
based upon the cross-section shown in Fig. 11.4.
94mm
<>
reinforcement bar
Fig. 11.4 Lintel cross ~ section for flexural strength calculation
‘Shear strength
The typical shear failure mode for concrete filled lintels is illustrated Fig.11.5.
The ultimate design shear strength at any shear plane is Vig = 25KN.
This lintel ultimate shear strength is applicable for all values of depthD.ee
i) {
concrete D
50 mm|
RA pein) reinforcing bar QQ
Fig. 11.5Typical shear failure mode in lintel
11.3 Design Example:
A3 metre long simply supported lintel filled with 25 MPa concrete carries design
UDL of 14 kN/m. It is reinforced with Fe415 steel. Design the lintel cross-section.
Let the overall depth be 300 m. Assume that the lintel is reinforced with 16mm
meter bar with a clear cover of 30mm.
0.0035 OASha
— ee
FY Loss
1¥-16
—or i
Fig. 13.6 Stress and strain variation in lintel
The effective depth, d = 300-30-8= 262mm.
Design shear force, Vi= (3/2 -0.262) x 14
= 17.4 KN < 25.0 KN shear strength. O.K.
Depth of neutral axis assuming section as under reinforced
tg «8 0.87 fy Ax / (0.36 fir b)"
(0.87 x 415 x 201) / (0.36 x 25 x 94)
85.8 mm < (0.48 x 262 = 126 mm)
Hence, the section is under reinforced.
Moment of resistance, Mur =
Design bending moment, M, =
Hence the section is safe.
0.87 f, Ase (d-0.42 xu)
0.87 x 415 x 201 (262 -0.42 x 85.8) x10°
16.4 kNm
wP/8 = 14 x 37/8 = 15.8 kNm