FC Calc
FC Calc
Details of Generator
Rating : 1675KVA
Voltage : 11Kv, 50 Hz
Sub transient Reactance : X” d = 0.087 pu
The fault current at the terminals of the generator is limited by the subtransient
reactance of the generator. The fault currenT will increase at the 11KV busbars,
when the generators are paralleled. Again at the busbar, the cable impedance
will act in series with generator subtransient reactance to restrict the fault current.
We are assuming that at the most 5 Nos. Generators can be paralleled at the
worst scenario.
We have chosen 25KA for 3 Sec the busbar rating of 11Kv switchboard. Hence
we are safe and within limits.
If we add cable impedance in series, the fault current will come down.
NOTE;
1) LOWER THE RATING,HIGHER WILL BE THE VALUE OF REACTANCES
2) IT IS UNLIKELY THAT MORE THAN 4 GENERATORS WILL BE IN
PARALLEL
3) IF NGR IS IN PLACE FAULT CURRENT WILL BE FURTHER
RESTRICTED
4) IT IS ASSUMED GENSETS WILL NOT BE SYNCHRONISED WITH GRID