Droop Control Method For Load Share and Voltage Regulation
Droop Control Method For Load Share and Voltage Regulation
Abstract When the line impedance is considered in the mitigated significantly. The proposed droop control only
microgrid, the accuracy of load sharing will decrease. In changes the detection point of the feedback signal, thus it is
this paper, the impact of line impedance on the accuracy of easy to be implemented. The PSCAD/EMTDC simulation
load sharing is analyzed. A robust droop control for a high- results show the effectiveness of the proposed robust droop
voltage microgrid is proposed based on the signal detection control concept in load sharing and voltage regulation with
on the high-voltage side of the coupling transformer. For a highly accuracy.
high-voltage microgrid, the equivalent impedance of cou-
pling transformer connecting distributed generator with the Keywords Microgrid, High-voltage, Coupling
grid is usually the dominate factor. Compared with the transformer, Droop control, Accreted load sharing, Voltage
conventional droop control strategy, the proposed control regulation
method in this paper detects the feedback signal from the
high-voltage side of the coupling transformer. The impact
of line impedance on the load sharing accuracy can be
1 Introduction
CrossCheck date: 17 November 2015
In order to address the environmental pollution and
Received: 11 October 2015 / Accepted: 22 December 2015 / Published
online: 19 January 2016
energy crisis, many distributed generations (DGs), e.g., solar
Ó The Author(s) 2016. This article is published with open access at energy, wind energy, microturbines, and fuel cells are widely
Springerlink.com used. These DGs are connected to the utility grid via
& Shanglin MO inverters, which are also known as the microgrid [1, 2]. The
[email protected] operation mode of the microgrid can be switched between
Zhikang SHUAI grid-connected and islanded mode flexibly [3]. A necessary
[email protected] problem for parallel-operated DGs in a microgrid is how to
Jun WANG avoid the circulating current among them. One of the key
[email protected] techniques is to use droop control [4, 5], which has been
Z. John SHEN widely used in conventional synchronous generators [6] and
[email protected] uninterruptible power supply (UPS) [7]. Its advantage is that
Wei TIAN each DG is able to be operated independently without any
[email protected] critical communication.
Yan FENG Although the droop control is widely used as a wire-
[email protected] less control strategy for load sharing, it has some draw-
1 backs that limit its application. For instance, the load
National Power Transformation and Control Engineering
Technology Research Center, Hunan University, Changsha sharing accuracy is degraded if the per-unit impedances
410082, China (the output impedance and the line impedance) of each
2
Electrical and Computer Engineering, Illinois Institute of DG are unbalanced [8]. Usually, P-f and Q-V droop
Technology, Chicago, IL 60616, USA control are used when the equivalent impedance which
123
Droop control method for load share and voltage regulation in high-voltage microgrids 77
connecting DGs to the gird is inductive in a microgrid the performance of the proposed control concept and the
[9]. The active power can be shared accurately using P-f design consideration of robust droop control gain are pre-
droop control since it is just based on the frequency of sented in Section 4. The PSCAD simulation results are
the microgrid. However, the DG voltage output in Q-V given in Section 5, followed by conclusions in Section 6.
droop control is different with the voltage at the point of
common coupling (PCC) because of the different line
impedances. Thus the accuracy of reactive power sharing 2 Impacts of line impedance on load sharing
using Q-V droop control is usually substantially affected in microgrids
by the equivalent impedance of DG and line impedance
[10]. Figure 1 shows a general scheme of a microgrid which
In order to enhance the accuracy of reactive power consists of sets of microsource and energy storage, dis-
sharing, the droop control gains are necessary to be opti- tributed loads and electric power interfaces inverter con-
mized [11, 12]. However, there are still inherent tradeoff nected to the step-up coupling transformer. Besides, the
between the load sharing accuracy and voltage regulation. microgrid can be connected to the utility grid operating in
Therefore, these methods are only valid for the microgrid grid-connection mode if the switch STS is turned on. When
with short distribution lines where the line impedance is the utility grid is not present, the DG units should be able to
negligible. Recently, the virtual reactor or integral unit to share the total power demanded together.
adjust the equivalent impedance of DGs is added to the Figure 2 shows the equivalent high-voltage side circuit
conventional droop control loop [13, 14]. However, the line of the microgrid. Ei\hi (i = 1,2,_) is the voltage output of
impedance is still unknown even the equivalent impedance DGi; Pi and Qi are the active and reactive power flowing
of DGs can be established. Thus, the line impedances are into loads generated by DGi, respectively; V\h is the AC
detected or calculated in some literatures [15, 16] in order common bus voltage; Zi\ui is the equivalent
to mitigate their influence. However, it is quite complicated impedance.
to implement. In some cases, the external communication The current output of each DG is
is still adopted [17]. However, the reliability and stability Ei cos dig V þ jEi sin dig
of microgrids will be affected substantially by the com- Ii ¼ ð1Þ
Ri þ jXi
munication system. The complicated communication sys-
tem would also increase the difficulties significantly in where Xi and Ri are the equivalent inductive and resistive
design and implementation of large scale microgrids. component, respectively; dig is the phase difference
Reference [8] proposed a robust droop control and the between Ei and V; dig ¼ hi h:
robustness of the voltage output and load sharing accu- The active power and reactive power output of each DG
racy could be enhanced obviously. However, it is only are calculated as
suitable for the centralized microgrid with communication
equipment. Besides, a virtual impedance unit added in
control loop should be bigger enough so that the effect of
line impedance can be omitted, which is complex and
limited to its application. Nowadays, the high-voltage Grid
large scale microgrid for campus and island are most
likely to be developed [18, 19]. In these kinds of Line
Loads
microgrids, DGs are always connected to the utility grid …
123
78 Zhikang SHUAI et al.
(
E1∠θ1 E2 ∠θ 2 … Ei ∠θ i E1 ¼ E 2 ¼ . . . ¼ E i
m1 m2 mi ð7Þ
¼ ¼ ... ¼
X1 X2 Xi
Z1∠ϕ1 Z 2 ∠ϕ2 Z i ∠ϕi Due to the unpredictable and unchangeable of the micro-
grid parameters, (7) is almost impossible to be satisfied,
P1 + jQ1 P2 + jQ2 Pi + jQi especially the per-unit impedance. Therefore, how to
achieve accurate reactive power sharing is one of the key
AC common bus V ∠θ topics in microgrids.
For the inverter-interfaced high-voltage microgrid, DGs
Fig. 2 Equivalent circuit of a high-voltage microgrid connected to a
common bus are always connected to the utility grid through a step-up
coupling transformer. Thus, a simplified and general topol-
ogy of a typical high-voltage microgrid system with paral-
leled DGs is shown in Fig. 3. Lsi and Csi are inductor and
Xi Ei V Ri VðEi Vcos dig Þ capacitor of the LC filter, respectively. Vfi is the voltage of
Pi ¼ sin dig þ
Zi Zi Zi Zi the inverter output port. KTi is the voltage ratio of trans-
ð2Þ
Ri Ei V Xi VðEi Vcos dig Þ former; VTi and iTi are the output voltage and current at the
Qi ¼ sin dig þ
Zi Zi Zi Zi high-voltage side of transformer Ti, respectively; Vi and ii are
In high-voltage power systems, the inductive reactance the output voltage and current at the low-voltage side of
Xi is much larger than resistive component Ri which means transformer Ti, respectively; XLi is the equivalent impedance
cosdig 0 and sindig dig , so (2) can be simplified as of Line i. In additional, the fundamental frequency element
of Vfi is equal to Ei. Therefore, the output impedances Xi is
Ei V
Pi ¼ dig 2
Xi xkTi Lsi þ XTi þ XLi ð8Þ
Xi
ð3Þ
V where XTi is the transformer equivalent impedance in the
Qi ¼ ðEi VÞ
Xi high-voltage side of step-up coupling transformer.
Equation (3) is the theoretical basis of traditional P-f and Besides, coupling transformers are usually used for
Q-V droop control. Accordingly, the frequency and voltage high-voltage microgrids. Hence, compared with a low-
output of DGs can be regulated as voltage microgrid, the impact of the coupling transformer
in the high-voltage microgrid should be considered when
xi ¼ x ni Pi deal with the influence of line impedance. Especially for a
ð4Þ
Ei ¼ E m i Q i large-capacity transformer, the inductive component of the
short circuit impedance is usually larger than the resistive
where xi and x and are the frequency output and the rated
component. The short-circuit reactance XT of the trans-
frequency of DGi; E* is the rated voltage of high-voltage
former is calculated [21].
microgrid; ni and mi are the frequency droop gain and
voltage droop gain, respectively. Vs VN2
XT ¼ ð9Þ
With the traditional and normal droop control strategy, 100 SN
when the microgrid operates in steady state, it will share where SN and VN are the apparent power and rated voltage
the same frequency with utility grid. Thus, the frequency of the transformer; Vs is the percentage of short-circuit
and active power of DGi can be described as voltage.
x1 ¼ x2 ¼ . . . ¼ xi It is noted that the inductive component XT of the
ð5Þ
n 1 P1 ¼ n2 P2 ¼ . . . ¼ ni Pi transformer with large capacity in a high-voltage microgrid
system is bigger enough so that the line impedance could
However, the reactive power Qi mainly depends on Ei, V
and the line impedance Zi [20]. V can be expressed as
Lsi 1: kTi X Ti X Li
Vfi Vi / ii VTi / iTi Pi / Qi
V ¼ ðE1 \h1 ; . . .; Ei \hi ; R1 þ jX1 ; . . .; Ri þ jXi Þ ð6Þ Inverter V
Csi
As can be seen from (6), the accurate reactive power
DG i
sharing is difficult to be implemented with the conventional
droop control scheme unless the impedance of distribution Fig. 3 A simplified and general topology of a typical high-voltage
lines is strictly the same as (7). microgrid system
123
Droop control method for load share and voltage regulation in high-voltage microgrids 79
123
80 Zhikang SHUAI et al.
1.2
According to the conservation of energy theorem, it is
noted that the system must satisfy 0.8
8
> Pn
0.4
>
> Qdesried Si ¼ Qload Si New proposed trategy
>
>
>
<P n
i¼1 0
Traditional droop strategy
DQi ¼ 0 ð20Þ -0.4
>
> i¼1 0 2 4 6
>
> Pn
>
> t (s)
: Qi ¼ Qload
i¼1 (c) AC common bus voltage
According to (19) and (20), (21) can be achieved through Fig. 5 Comparison between new robust droop control and conven-
accumulating and simplifying. tional droop control
1 0.2 ? j0.15 8.156 50 0.47 120 0.5 20 380 V/ 2.5 9 10-6 1.36 9 10-3 116 ? j80
10 kV
2 0.4 ? j0.3 8.156 50 0.47 120 1.0 10 380 V/ 1.25 9 10-6 6.8 9 10-4
10 kV
123
Droop control method for load share and voltage regulation in high-voltage microgrids 81
X X
Based on the power flow calculation, voltage drop DVLi can V ¼ E meq Qload ð32Þ
be calculated as where meq is the equivalent droop coefficient of V versus
Pi RLi þ Qi XLi reactive power Qload.
DVLi ¼ ð28Þ Based on (20), (31) and (32), (33) can be obtained.
V
meq
where RLi and XLi are the resistive and inductive part of Qi ¼ Qload ð33Þ
meqi
line impedance, respectively.
123
82 Zhikang SHUAI et al.
P
n
1 k32i Ke ðXL1 kXL2 Þ
where meq ¼ 1 meqi . qi ð1Þi i ¼ 1; 2 ð35Þ
i¼1 ð1 þ kÞmi E
Substitute (33) into (30), then
! Equation (35) shows that the larger difference between
Ke S Xn
1 meq XLj meq XLi
qi ¼ m ð34Þ kXL2 and XL1 is, the larger |qi| will be, and |qi| will be zero
m i Si E j¼1
m j meqj meqi when XL1 = kXL2. In addition, it should also be noted that
the value of qx may be positive or negative, e.g., q1 [ 0
Naturally, (34) can be utilized as the mathematic model to and q2 \ 0 when XL1 [ kXL2, q2 [ 0 and q1 \ 0 when
analyze the power sharing performance of the proposed XL1 [ kXL2. qi [ 0 represents that the reactive power
control strategy. Noted that qi only depends on the line output of inverter i exceeds the desired power output, i.e.,
impedance XLi and Ke, and it has no difference with Qi [ Qdesired, and the DG is on the risk of overload.
reactive power output Qload or active power output Pload Whereas, it indicates that the reactive power output of DGi
when parameters mi, Si, S and E* are constant. is less than the desired output, e.g., Qi \ Qdesired, and the
Assume that the sum of inverter n = 2 in the high- DGi is on the condition of under-load.
voltage microgrid system, and then the ratio coefficient of Taking the absolute value of the both sides of (35) and
capacity of DG2 to that of DG1 is k. At the same time, the (36) can be obtained.
parameter m1 is set to k times as much as m2. Accordingly,
Si/S is equal to ki-1/(1 ? k), and (34) can be simplified as k32i Ke jXL1 kXL2 j
j qi j ð36Þ
ð1 þ kÞmi E
300 According to (35), Ke can be represented as
Reactive power (kVar)
Q2
ð1 þ kÞmi E jqi j
Ke ð37Þ
200 k32i jXL1 kXL2 j
Q1
200
Q1
5 Simulation validation
123
Droop control method for load share and voltage regulation in high-voltage microgrids 83
Table 2 Systems parameters and reactive power supplied by DG with different line impedance
ZLB(X) ZL1/ZL2 (X) XL1 2XL2 ðXÞ Q1/Q2 (kVar) q1/q2
connected the AC common bus simultaneously. Simulation robust droop control system, Q2_2 = 1.22 9 105 kVar is
process finishes at t = 6 s. nearly equal to 2Q1_2 = 2.66 9 105 kVar, which means
that reactive power sharing has be improved much when
5.1 Comparison between proposed robust droop the proposed control scheme is adopted.
control and conventional droop control As shown in Fig. 5c, the AC common bus voltage with
the proposed droop control can be maintained around the
The simulations are carried out with the conventional rated voltage, but the voltage with traditional droop
voltage droop coefficients divided by Ke = 5 so that the control is only about 3/4 of the rated voltage, which
equivalent voltage droop coefficient is the same as the one agrees with the analysis of (5) in Section 3. In a word, the
in the proposed controller. Expecting that the voltage droop tradeoff between the load sharing accuracy and voltage
could be comparable with the one achieved with the pro- regulation can be restrained successfully as that in [8], but
posed robust droop scheme. The line impedances it is easier to be implemented with the proposed droop
ZL1 = j0.9425 X, ZL2 = j0.314 X. control.
Figure 5 shows the simulation results of both the pro-
posed new robust droop control and the conventional droop 5.2 Performance of proposed robust droop control
control. Pi_2 and Qi_2 are the active and reactive power of with load variations
DGi and Vg_2 is the AC common bus voltage when the new
robust droop control is applied. Pi and Qi are the active In the section, the influence of load changes on load
power and reactive power of DGi and Vg is the AC com- sharing is analyzed. The line impedances are assumed as
mon bus voltage when the conventional droop control is ZL1 = 0.9425 X and ZL2 = 0.314 X, and the robust coef-
applied. ficient Ke is set to 5. The simulation results are shown in
In Fig. 5a, when the simulation is in steady state at Fig. 6.
about t = 2 s, the active power output of DGs with dif- At t = 1 s, the load with 3/4 rated power is connected to
ferent droop controls are that P2_2 = 2P1_2 = 3.9 9 102 the microgrid. At t = 3 s, the load decreases to 1/4 rated
kW and P2 = 2P1 = 2.5 9 102 kW, which indicates that power. At t = 4.5 s, the load increases to the rated power.
the active power sharing among DGs could be achieved From Fig. 6a, b, it can be seen that the ratio of active or
either through the proposed droop control or the conven- reactive power output of DG1 to that of DG2 is about 1/2
tional droop control. However, the proposed robust droop whatever the active power or reactive power load changes.
control can supply higher power. It can be seen from Fig. 6c, the AC common bus voltage is
In Fig. 5b, it can be seen that Q1 = 1.9 9 102 kVar, always maintained at the rated value. Thus, it can be
Q2 = 2.5 9 102 kVar, the reactive power sharing is unable concluded that the variation of active or reactive load has
to be achieved with the conventional droop control due to little influence on the load sharing performance with the
the mismatched line impedances. However, in the proposed proposed droop control.
123
84 Zhikang SHUAI et al.
1.0
its desired power. On the contrary, q1 \ 0 and q2 [ 0
when XL1 2XL2 [ 0, and the reactive power output of
0.8
DG1 is less than its desired power and the reactive power Ke=1 Ke=0.2
output of DG2 is larger than its desired power.
0.6
2) The smaller the absolute value of XL1 2XL2 is, the
more accurate the load sharing among DGs will be. In
0.4
another word, the closer to zero XL1 2XL2 is, the 0 1 2 3
smaller q1 t (s)
(c) AC common bus voltage
and q2 are, and the better of the load sharing performance
among DGs would be as result. Fig. 8 Power sharing and AC common bus voltage
123
Droop control method for load share and voltage regulation in high-voltage microgrids 85
123
86 Zhikang SHUAI et al.
Proceedings of the IEEE Power & Energy Society general interests include power semiconductor devices and their applications
meeting, San Diego, 22–26 July 2012, 2 pp in power electronics systems.
[19] Yang H, Zhao RX, Xin HH et al (2013) Development and
research status of island power systems. Trans China Electrotech Z. John SHEN received B.S. from Tsinghua University, China, in
Soc 28(11):95–102 (in Chinese) 1987, and M.S. and Ph.D. degrees from Rensselaer Polytechnic
[20] Lee CT, Chu CC, Cheng PT (2010) A new droop control method Institute, Troy, NY, in 1991 and 1994, respectively, all in electrical
for the autonomous operation of distributed energy resource engineering. Between 1994 and 1999, he held a variety of positions
interface converters. In: Proceedings of the 2010 IEEE energy including Senior Principal Staff Scientist with Motorola. He was on
conversion congress and exposition (ECCE’10), Atlanta, 12–16 faculty of the University of Michigan-Dearborn between 1999 and
Sept 2010, pp 702–709 2004, and the University of Central Florida between 2004 and 2012.
[21] He YZ, Wen ZY (2002) Electric power system analysis. In: He joined the Illinois Institute of Technology in 2013 as the Grainger
Huazhong University of Sicience and Technology Press, Wuhan, Chair Professor in Electrical and Power Engineering. He has also held
27 pp (in Chinese) a courtesy professorship with Hunan University, China since 2007;
and with Zhejiang University, China since 2013. His research
interests include power electronics, power semiconductor devices
Zhikang SHUAI received the B.S. and Ph.D. degree from the and ICs, automotive electronics, renewable and alternative energy
College of Electrical and Information Engineering, Hunan University, systems, and electronics manufacturing. He has published over 150
China, in 2005 and 2011, respectively, all in electrical engineering. journal and conference articles, and holds 13 issued and several
He joined Hunan University as an Assistant Professor from 2009 to pending U.S. patents in these areas. He is a recipient of the 2012 IEEE
2012, an Associate Professor in 2013, and has been a Professor since Region 3 Outstanding Engineer Award, the 2003 NSF CAREER
2014. His current research interests include power quality control, Award, the 2006 IEEE Transaction Paper Award from IEEE Society
power electronics, and microgrid stability. Dr. SHUAI is a recipient of Power Electronics, the 2003 IEEE Best Automotive Electronics
of the 2010 National Scientific and Technological Awards of China, Paper Award from IEEE Society of Vehicular Technology, and the
the 2012 Hunan Technological Invention Awards of China, the 2007 1996 Motorola Science and Technology Award. He has been an
Scientific and Technological Awards from the National Mechanical active volunteer in the IEEE Power Electronics Society (PELS), and
Industry Association of China. has served as VP of Products 2009–2012, Associate Editor and Guest
Editor in Chief of the IEEE Transactions on Power Electronics,
Shanglin MO received the B.S. from the College of Electric technical program chair and general chair of several major IEEE
Engineering and Automation, Chongqing University of Posts and conferences.
Telecommunications, Chongqing, China, in 2013. He is currently
pursuing the M.S. degree in Electric Engineering at the College of Wei TIAN received the B.S. degree in mathematics from Shandong
Electrical and Information Engineering, Hunan University, China. His University, China, in 2001, the M.S. degree in system engineering
research interests include power electronics and microgrid stability. from Xi’an Jiaotong University, China, in 2004, and the Ph.D. degree
in electrical engineering from the Illinois Institute of Technology,
Jun WANG received the B.S. degree at Huazhong University of Chicago, IL, USA, in 2011. He is a Visiting Scientist at the Robert W.
Science and Technology, Wuhan, China in 2000. He received the Galvin Center for Electricity Initiative at the Illinois Institute of
M.S. degree in Institute of Semiconductors, Chinese Academy of Technology. His research interests include power system restructur-
Sciences, Beijing, China in 2003. He received the M.E. degree at ing, long-range planning, renewable energy integration and
University of South Carolina, Columbia, SC, USA in 2005, and the microgrid.
Ph.D. degree at North Carolina State University, Raleigh, NC, USA in
2010 respectively, all in Electrical Engineering. He then worked as a Yan FENG received the B.S. degree from the College of Electrical
device design engineer at Texas Instruments, Inc. in Bethlehem, PA, and Information Engineering, Hunan University, Changsha, China, in
USA between 2010 and 2013. He became a professor in the College 2014. She is currently pursuing the M.S. degree in Electrical
of Electrical and Information Engineering at Hunan University in Engineering at the College of Electrical and Information Engineering,
2014. He has authored and coauthored more than 30 journal and Hunan University, Changsha, China. Her research interests include
conference publications and holds 2 issued U.S. patents. His research power electronics and microgrid stability.
123