Sleeperwall 1
Sleeperwall 1
Geometry
Wall is assumed fully drained
Geometry (Height must be a multiple of the sleeper)
Retaining height (ht) = 1200 mm
Post centres (cts) = 1800 mm
Upright = S (T)imber,(S)teel,(B)oth
Risk class = B (A),(B),(C) - Moderate damage and loss of service - Table 1.1
Backfill type = 1 Class(1), Class(2), (U)ncontrolled, (I)n-situ - Table 5.1(A)
Surcharge Min. = 5.0 kPa min. (Table 4.1) Additional upright Overturning
Water Ht (hw) = 0.0 mm (Drained) Overturning (Ma) = 0.00 kNm
Surcharge (s) = 5.0 kPa Thrust (Va) = 0.00 kN
Load factor = 1.50
Long term LL factor (Ψlo) = 0.40
Earth factor = 1.25 (1.25) Ma* = 0.00 kNm
Live load factor = 1.50 (1.50 - 0.0 for stabilising effect) Va* = 0.00 kN
Stabilising = 0.80 AS4678 - Appendix J (Moment/Thrust about top wall)
Double Sleepers at layer = 0 (Single layer sleepers) Critical layer for design = 6
Total layers = 6 Critical layer centroid depth = 1100 mm
w*= 2.26 kN/m
M*/Φn = 0.92 kNm Area (A) = 19109 mm²
Description = 100mm x 200mm F5 Treated* Section modulus (Zy) = 309 x10³mm³
Design depth (dD) = 97 mm Stiffness (Iy) = 15.0 x10⁶mm⁴
Design width (dW) = 197 mm Modulus of elasticity (E) = 6900 MPa
M* = 7.50 kNm
øMr = 1.25*cf*.*dia*d² = 30.24 kNm OK (0.25)
Deflection Limits
Sleeper
δDL lim. = Span/ 150 = 12mm or mm δDL lim. = 12 mm
Ψs.δLL lim. = Span/ 150 = 12mm or mm Ψs.δLL lim. = 12 mm
δTot. lim. = Span/ 150 = 12mm or mm δTot. lim. = 12 mm
Upright
δDL lim. = Height/ 150 = 8mm or mm δDL lim. = 8 mm
Ψs.δLL lim. = Height/ 150 = 8mm or mm Ψs.δLL lim. = 8 mm
δTot. lim. = Height/ 150 = 8mm or mm δTot. lim. = 8 mm
Notes:
Additional overturning:
Manually enter for fence loading or
partial surcharge. Provide thrust and moment
about top of the wall (= retaining height).
Set factors to 1:
Factor is 1 = N (Y)es,(N)o
k4 factor:
Partial seasoning factor
Refer Cl 2.4.2.2 & 2.4.2.3 for more information.
k6 factor:
Refer Cl 2.4.3 if designing structures near coastal
regions of Queensland north of 25°S and all other
regions north of 16°S