0% found this document useful (0 votes)
199 views

Manual Design Bioseptic

This document provides guidelines for estimating population equivalents and waste water volumes and biochemical oxygen demand (BOD) for sizing waste water purifiers for different types of buildings. It includes formulas and calculation units for population equivalents for various assembly halls, residential buildings, accommodation facilities, medical facilities, shops, and amusement facilities. The population equivalents are used to determine appropriate waste water volume and BOD levels for joint treatment of waste water from different types of buildings.

Uploaded by

sigitbambang
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
199 views

Manual Design Bioseptic

This document provides guidelines for estimating population equivalents and waste water volumes and biochemical oxygen demand (BOD) for sizing waste water purifiers for different types of buildings. It includes formulas and calculation units for population equivalents for various assembly halls, residential buildings, accommodation facilities, medical facilities, shops, and amusement facilities. The population equivalents are used to determine appropriate waste water volume and BOD levels for joint treatment of waste water from different types of buildings.

Uploaded by

sigitbambang
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

Estimation of Population for Waste Water Purifier of Buildings

(JIS A 3302 - 2000)

Table 1
Population equivalent Guide line (ministry of
Construction Japan 1996)
No Building Use Waste water volume and BOD
(Joint treatment)
Formula Calculation unit Volume BOD
Pubic, hall, moving theater, n = 0.08 A n : PE 16 150
a
entertainment hall A : Area (m2) (L/m2-D) (mg/L)
Stadium, race track, speedboat course n = 16 C n : PE 2,400 260
1 Assembly hall b
C : total no.of toilets (L/units-D) (mg/L)
Gymnasium, admission stands n = 0.065 A n : PE 10 260
c
A : Area (m2) (L/m2-D) (mg/L)
A < 130 m2 n=5 n : PE 200 200
a house
130 m2 <=130 m2 n=7 A : Area (m2) (L/p - D) (mg/L)
n : PE 10 200
If n <=3.5 in one house, n (L/m2-D) (mg/L)
shall be 3.5, or if one
house made up by one
b apartment n = 0.05 A
room, n shall be 2. And if
2 Residential
more than 6 person will
live in one house, n shall
be 8
n : PE 14 140
c lodge, dormitory n = 0.07 A
A : Total Area (m2) (L/m2-D) (mg/L)
dormitory, army camp, home for the n : PE 200 200
d n=P
aged, nursing home P : person who occupy (L/m2-D) (mg/L)
a have wedding n : PE 30 200
hall or n = 0.15 A A : total area (m2) (L/m2-D) (mg/L)
banquet hall
hotel
no wedding n : PE 30 200
hall, or no n = 0.075 A A : total area (m2) (L/m2-D) (mg/L)
3 accommodation
banquet hall 1,000 50
n : PE
b motel n=5R R : no. of rooms (L/room-D) (mg/L)
n=P n : PE 200 200
c
lodge, training camp, youth hostel P : person who occupy (L/m2-D) (mg/L)
with kitchen <300 beds n = 8 B 300 beds < with kitchen
or washing >= 300 n=11.43(B- 1,000 and washing
a hospital, clinic, machine for beds 300)+2,400 (L/bed-D) equipment
4 medical hospital for infection business n : PE 320 (mg/L)
without kitchen <300 beds n = 8 B B : no. of beds 300 beds < without kitchen
or washing >= 300 n=11.43(B- 1,000 and washing
machine for beds 300)+2,400 (L/bed-D) equipment
business 320 (mg/L)
b clinic, doctor's office n = 0.19 A n : PE 25 300
A : total area (m2) (L/m2-D) (mg/L)
a shop, market n = 0.075 A 15 (L/m2-D) 150 (mg/L)
b department store n = 0.15 A 30 (L/m2-D) 150 (mg/L)
5 shop in general n = 0.72 A n : PE A:total area (m2) 130 220
c restaurant (L/m2-D) (mg/L)
high loading n = 2.04 A 260 450
(L/m2-D) (mg/L)
low loading n = 0.55 A 110 150
(L/m2-D) (mg/L)
6 amusement a Billiard saloon, table tennis club n = 0.075 A n : PE 15 (L/m2-D) 150 (mg/L)
b Pachinko game shop n = 0.11 A A : area (m2) 22 (L/m2-D) 150 (mg/L)
c Igo club, mah-jong club n = 0.15 A 30 (L/m2-D) 150 (mg/L)
d discotheque club n = 0.05 A 100 (L/m2-D) 150 (mg/L)
e golf practice range n = 0.25 S n : PE 50(L/box-D) 150 (mg/L)
S : no.of batter box
f bowling center n = 2.50L n : PE 500(L/lane-D) 150 (mg/L)
L : no. of lane
g Batting center n = 0.20S n : PE 40 (L/box - D) 150 (mg/L)
S : batter box
night n : PE 100(L/court-D) 150 (mg/L)
h Tennis club operation n = 3S S : no.of court
no night n : PE 400(L/court-D)
operation n = 2S S : no.of court
i amusement park, bathing beach n = 16C n : PE 2400(L/place-D) 260 (mg/L)
C : total no.toilet
general part n=3,60P
toilet sightseeing part n=3,83P
a service area 820 (L/units.D)

7 Car Park
toilet
a service area no kiosk n=2,55P n = PE 820 (L/units.D)
general part n=2,66P p = total no of car
kiosk
sightseeing part n=2,81P
7 Car Park n = PE
C = no. of toilet ( feces )
b car park, garage n=( 20C + 120 U ) /8 X t U = no.of toilet ( Urinal ) 170 (L/units.D)
t = occupied hour/day
t = 0,4 - 2,0
n = PE
c gas station n=20
per one station
nursary scholl, kindergarden n = PE 50 (L/p.D) 180 ( mg/L )
a n=0,20P
primary scholl,middle scholl P = no of person
8 School b high scholl, university, other scholl. n=0,25P 60 (L/p.D) 180 ( mg/L )
n = PE 16 (L/p.D) 150 ( mg/L )
c library n=0,08A
A = total area ( m2 )
with kitchen n=0,075A n = PE 15 (L/p.D) 300 ( mg/L )
9 Office a office
with out kotchen n= 0,06A A = total area ( m2 ) 15 (L/p.D) 150 ( mg/L )
with kitchen n=0,75 P n = PE 100 (L/p.D) 150 ( mg/L )
10 a factory, work shop, institute, laboratory.
Working Place with out kotchen n=0,30P P = no of person 60 (L/p.D) 150 ( mg/L )
a market n= 0,02A n = PE 4,20 (L/p.D) 200 ( mg/L )
b public bath n= 0,17A A = total area ( m2 ) 33 (L/p.D) 50 ( mg/L )
11 Other Facilities d public lavatory n= 16C n = PE
P<100,000 n=0,008P n = PE
c Station bus terminal
100,000<P<200,000 n=0,0010P P = no of passenger
RESEARCH AND DEVELOPMENT
ON BUILDING SANITATION SYSTEM
JAPAN - INDONESIA

DESIGN CRITERIA

NO ITEM Indonesia Standard Japan Standard


DISCHARGE BOD LOAD DISCHARGE BOD LOAD
(l/p/day) (g/p/day) (l/p/day) (g/p/day)

1 TOILET 10 10.5 50 13

2 KITCHEN 30 30 21

3 WASHING 50 19.5 40 4

4 BATH 70 80 2

TOTAL 160 30 200 40

NOTE:
DATA SOURCE 1994: NATIONAL URBAN DEVELOPMENT CORPORATION
MINISTRY OF CONSTRUCTION INFRASTRUCTURE DEVELOPMENT INSTITUTE JAPAN
National Regulation of
Effluent Standard of Domestic Waste Water Treatment
NO. 112 , 2003 Year

NO INDICATOR UNIT MAX.

1 PH mg/l 6--9

2 BOD mg/l 100

3 TSS mg/l 100

4 OIL & GREASE mg/l 10

Date : 10 July 2003


Ministry of Indonesia Environment

Nabiel Makarim,MPA,MSM
eatment
DKI Jakarta Regulation of
Effluent Standard of Domestic Waste Water Treatment
NO. ………………………

NO INDICATOR UNIT MAX.

1 PH mg/l 6--9
2 Organic (KMnO4) mg/l 85
3 TSS mg/l 50
4 Ammonia mg/l 10
5 Oil & Grease mg/l 10
6 Blue Metilen mg/l 2
7 COD mg/l 80
8 BOD mg/l 50

Date : …………………..
GOVERNOR OF DKI JAKARTA

SUTIYOSO
IPLC
PERMIT LIECENCE OF DOMESTIC WASTE WATER
NO. 30 , 1999 YEAR

1 SUBMISSION LETTER TO BAPEDALDA (BPLHD)

2 ATTACHMENT:
A. FORM DATA
B. FLOWCHART
C. NOTARIAT LICIENCE COMPANY
D. BUILDING LICIENCE (IMB)
E. BUILDING SYSTEM LICIENCE (IPB)
F. LICIENCE OF HO (UNDANG-UNDANG GANGGUAN)
G. DOMESTIC WASTE WATER DESIGN
H. UKL/UPL DOCUMENT
I. TEST LABORATORY
J. LETTER OF

3 VALIDATION FOR 5 YEARS

Jakarta, 19 April 1999


GOVERNOR OF DKI JAKARTA

SUTIYOSO

You might also like