Motor Protection Relay SPAM 150 C

The document describes a numerical multi-function motor protection relay for medium and large AC motors. It has features like contactor and circuit breaker control, remote communication, self-supervision, and is registered for off-shore and marine use. It provides various motor protections like thermal overload, stall, overcurrent, earth fault, phase sequence, and undercurrent.

Uploaded by

J
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views31 pages

Motor Protection Relay SPAM 150 C

The document describes a numerical multi-function motor protection relay for medium and large AC motors. It has features like contactor and circuit breaker control, remote communication, self-supervision, and is registered for off-shore and marine use. It provides various motor protections like thermal overload, stall, overcurrent, earth fault, phase sequence, and undercurrent.

Uploaded by

J
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 31

Motor Protection Relay SPAM 150 C

Features
• Numerical multi-function motor
protection relay
• Protection of medium-sized and
3I >>
large ac motors 2
3
I
f n = 50Hz I n = 1A 5A (I ) I I I Io IRF
5 L1 L2 L3

• Contactor and circuit-breaker 60Hz I n = 1A 5A (I o )

controlled ac motor drives SPAM 150 C


I /I n
80...265V œ
~ NO
• Remote communication via t 6 x [ s] RESET

18...80V œ NC U aux p [ %] ST EP

a [ %]
i [ %]

serial interface SPCJ 4D34


kc
Is /I n
t s [ s]
REGISTERS OPER.IND.
I >> / I n

• Extensive self-supervision including 0 0 0 0 0 t >> [ s]

I o [ % I n]

> a t o [ s]
1 I /I n 1
auto-diagnosis 2
L1

I L2 / I n 2 > t I [% I L ]
t [ s]
3 I L3 / I n 3 i+ t si + EINH I < [% I ]
t < [ s]
4 I o [ % I n] 4 I >>
• Application references in all extremes 5 I [ %I L ] 5 I
t s i [ s]
t s [ s/h]
6 I t [ %I s 2 t s ]
2
6 I 2t PROGRAM

of climate 7 m[ %] 7 I o
SGF

8 [ %] 8 I< SGB
9 t i [ min] 9 EXT.TRIP
• Registered for use in off-shore SGR 1
SGR 2
TRIP

and marine application

0093A

0094A
RS 641 Ser.No. SPCJ 4D34

• Rigid aluminium relay case to IP 54

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 1 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Protection units
THREE-PHASE THERMAL TRIP
OVERLOAD PROTECTION
49
IL 1

STALL PROTECTION WITH


SPEED SWITCH INPUT FOR 14
DRIVES WITH LIMITED te-TIME SIGNAL 1

IL 2
THERMAL STRESS SUPERVISION
OR THREE-PHASE DEFINITE TIME
4 8/
OVERCURRENT PROTECTION 51
PRIOR ALARM
OR SIGNAL 2
THREE-PHASE DEFINITE TIME
HIGH SET OVERCURRENT 50
PROTECTION

START O R
IL 3 DEFINITE TIME LOW-SET PRIOR ALARM
EARTH-FAULT PROTECTION 51 N

PHASE SEQUENCE PROTECTION


INVERSE TIME PHASE 46 RESTART
UNBALANCE PROTECTION ENABLE

lo
DEFINITE TIME UNDERCURRENT
PROTECTION 37
IRF

CUMULATIVE START-TIME
COUNTER FOR RESTART INHIBIT
CONTROL
INPUT BS SERIAL I/O
SERIAL COMMUNICATION PO RT

Toiminn.fh4

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 2 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Block diagram L1
L2
L3

-
0

Selector switches
shown in default - I

BUS
I 0 CONNECTION

positions +
MODULE Rx Tx

SPA-ZC_
+ +
Uaux
- (~)
CONTROL RESTART START PRIOR PRIOR ALARM SIGNAL 1 TRIP SERIAL
INPUT BS IRF ENABLE ALARM SIGNAL 2 PORT
+
63 1 23 4 5 6 7 8 9 25 26 27 11 10 62 61 70 71 72 74 75 77 78 80 81 68 69 65 66

5A
1A

5A
1A

5A
1A

1A
5A
~ + + + + + +

F E D C B A
+ -
U2 SPTU _ R2

SGR4/2
R TRIP
U3 SPTK 4E3
1 1 1 1 1
SGB/7
SGB/8

SGR2/1
SGR2/2
SGR2/3

SGR1/1

SGR1/3
SGR1/4
SGR1/5
SGR1/6
SGR1/7

SGR2/4
SGR2/5

SGR2/7
SGR2/8
SGR4/3

SGR1/2

SGR2/6
IRF SELF HOLD.
3 > i

SGR1/8
> a
>t
STAR T
SGB/1 I s>
STALL
I s2 x t s
SGB/2 RESTART RESTART
INHIBIT INHIBIT
ts>
I>>

I
SGB/3

Io>
SGB/4

I<

SGB/5

AM150blc.fh4
EXTERNAL TRIP
SGB/6 RELAY RESET I/O
SPAM 150 C U1 SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 3 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Special features
• Wide setting ranges, accurate digital settings,
high long-time stability of settings
• Flexible configuration of output relays and
external control input
• Recording of fault parameters at the moment
of relay operation
• Local man-machine communication via push-buttons
and digital display
• Powerful software support for parametrization and
supervision via PC
• High immunity to electrical and electromagnetic
interference
• Member of the SPACOM family and PYRAMID®, ABB´s
coordinated protection and control concept

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 4 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Area of application
• High-voltage or low-voltage circuit-breaker
controlled motors.
Full protection against different types of fault
• Contactor-controlled high-voltage and low-voltage
motors.
Operation inhibited at fault currents exceeding the
breaking capacity of
the contactor
• Motor drives with complicated start-up sequences.
Several methods for start-up supervision with restart
inhibit option
• Critical ExE motor drives with feed-back from motor
speed switch.
Motors with the permitted stall time shorter than the
normal start-up time

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 5 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Dimensions of relay case and panel cut-out
Flush mounting
250 142
216 34 129 ±1
30 186

162

139 ±1
136

Panel
cut-out

Semi-projecting mounting
a b

Raising frame a b

Mit100SC.FH4
SPA-ZX 111 176 74
SPA-ZX 112 136 114
SPA-ZX 113 96 154

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 6 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Readouts and operation indicators 3I >>
3
I
Indicators for readout of measured phase currents, I L1 I L2 I L3 I o IRF

doubling as phase-fault indicators

Indicator for readout of measured neutral current, I /I n


RE SET
t 6x [ s]

doubling as earth-fault indicator p [ %]


a [ %]
STEP

i [ %]
kc
I s /I n

Indicator for internal relay fault t s [ s]


I >> / I n
t >> [ s]
I o [% I n]
t o [ s]

Digital display for presentation of numerical parameters, I [% I L ]


t [ s]

i.e. settings, measured and recorded values including I < [% I ]


t < [ s]

start and operation indications, auto-diagnostic fault t si [ s]


t s [ s/h ]
PRO GRAM

messages, etc. SGF

SGB

SGR 1

Indicator showing that the main trip relay of the motor SGR 2
TRIP

protection relay has operated

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 7 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
3I >>
3
I

Motor full load current I 0.50...1.50xIn I L1 I L2 I L3 I o IRF

Maximum safe stall time t6x 2.0...120 s


I /I n
Thermal weighting factor p 20...100% t 6x [ s]
p [ %]
RE SET
STEP
a [ %]
i [ %]
kc
I s /I n
t s [ s]
I >> / I n
t >> [ s]
I o [% I n]
t o [ s]

Thermal prior alarm level a 0.50...1.00 x t


I [% I L ]
t [ s]
I < [% I ]
t < [ s]

Thermal restart inhibit level i 0.20...0.80 x t


t si [ s]
t s [ s/h ]
PRO GRAM
SGF

Cooling-time multiplier kc 1...64 x h SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 8 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
3I >>
3
I

Motor start current Is 1.0...10.0 x In I L1 I L2 I L3 I o IRF

Motor start up time t6x 0.3...80 s


I /I n
t 6x [ s] RE SET
p [ %] STEP
a [ %]
i [ %]
kc
I s /I n
t s [ s]
• Operation principles: Is & ts or ls2 x ts I >> / I n
t >> [ s]
I o [% I n]
t o [ s]

• The operation of the start-up supervision unit can be I [% I L ]


t [ s]

inhibited by a motor speed switch connected to the I < [% I ]


t < [ s]

control input of the relay t si [ s]


t s [ s/h ]
PRO GRAM
SGF

SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 9 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
3I >>
3
I
I I I I o IRF
Start current I>> 0.5...20.0 x In or infinite L1 L2 L3

Operate time t>> 0.04...30.0 s


I /I n
t 6x [ s] RE SET
p [ %] STEP
a [ %]
i [ %]
kc
I s /I n
t s [ s]

• The start current setting can be automatically doubled I >> / I n


t >> [ s]

during a motor start-up I o [% I n]


t o [ s]
I [% I L ]
t [ s]
I < [% I ]
t < [ s]
t si [ s]
t s [ s/h ]
PRO GRAM
SGF

SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 10 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
3I >>
3
I

Start current I0> 0.01...1.00 x In I L1 I L2 I L3 I o IRF

Operate time t0> 0.05...30 s


I /I n
t 6x [ s] RE SET
p [ %] STEP
a [ %]
i [ %]
kc
I s /I n
t s [ s]

• In contactor-controlled drives, the earth-fault unit can be I >> / I n


t >> [ s]
I o [% I n]
inhibited at phase current levels above 4, 6 or 8 times In t o [ s]
I [% I L ]
t [ s]
I < [% I ]
t < [ s]
t si [ s]
t s [ s/h ]
PRO GRAM
SGF

SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 11 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
3I >>
3
I

Start current I 0.1...0.40 x IL or infinite I L1 I L2 I L3 I o IRF

Operate time t at 0.1 x IL 20...120 s


I /I n
t 6x [ s] RE SET
p [ %] STEP
a [ %]
i [ %]
kc

• Inverse time operation characteristic


I s /I n
t s [ s]
I >> / I n
t >> [ s]
I o [% I n]

• The unbalance unit and the incorrect phase sequence t o [ s]


I [% I L ]

protection unit can be set out of operation separately t [ s]


I < [% I ]
t < [ s]
t si [ s]
t s [ s/h ]
PRO GRAM
SGF

SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 12 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
3I >>
3
I
I I I I o IRF
Start current I< 0.30...0.80 x I or infinite L1 L2 L3

Operate time t< 2...600 s


I /I n
t 6x [ s] RE SET
p [ %] STEP
a [ %]
i [ %]
kc
I s /I n
t s [ s]

• The operation of the undercurrent unit is inhibited at motor I >> / I n


t >> [ s]

standstill, i.e. at load current values below 0.12 x I I o [% I n]


t o [ s]
I [% I L ]
t [ s]
I < [% I ]
t < [ s]
t si [ s]
t s [ s/h ]
PRO GRAM
SGF

SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 13 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
3I >>
3
I
I I I I o IRF
Maximum accumulated start-up time tsi 5...500 s L1 L2 L3

Countdown rate tsi of accum. start-up time 2...250


s/h I /I n
RE SET
t 6x [ s]
p [ %] STEP
a [ %]
i [ %]
kc

• Any attempt to restart the motor is prevented when the I s /I n


t s [ s]
I >> / I n
accumulated start-up time exceeds the set t >> [ s]
I o [% I n]

maximum accumulated start-up time tsi permitted t o [ s]


I [% I L ]
t [ s]
I < [% I ]
t < [ s]
t si [ s]
t s [ s/h ]
PRO GRAM
SGF

SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 14 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Switchgroup settings 3I >>
3
I
I L1 I L2 I L3 I o IRF

Switchgroup SGF for selection of required optional


functions in various applications
I /I n
t 6x [ s] RE SET
p [ %] STEP

Switchgroup SGB for routing of blocking signals and kc


a [ %]
i [ %]

selection of the latching function for the trip relay I s /I n


t s [ s]
I >> / I n
t >> [ s]
I o [% I n]
t o [ s]

Switchgroup SGR1 and SGR2 for confIuguration of the I [% I L ]


t [ s]
I < [% I ]
output relays t < [ s]
t si [ s]
t s [ s/h ]
PRO GRAM
SGF

SGB

SGR 1
SGR 2
TRIP

0 094A
SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 15 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Push-button operations 3I >>
3
Use the RESET/STEP push-button to: I
I L1 I L2 I L3 I o IRF
- reset operation indicators
- step forward or backward in main menus or submenus
- scroll set values in the setting mode
I /I n
t 6x [ s] RE SET
p [ %] STEP

Use the PROGRAM push-button to: kc


a [ %]
i [ %]

- enter a submenu from the main menu I s /I n


t s [ s]
I >> / I n
- enter the setting mode of an adjustable parameter t >> [ s]
I o [% I n]

- control the cursor in the setting mode or t o [ s]


I [% I L ]

- control the selected output in the test mode t [ s]


I < [% I ]
t < [ s]
t si [ s]
Use both push-buttons simultaneously to: t s [ s/h ]
PRO GRAM
SGF
- make a complete relay reset, i.e. clear memorized values SGB
and release latched output relays SGR 1
SGR 2
- store a new setting value TRIP

0 094A
- test an output relay SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 16 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Flexible configuration of output relays
RESTART START PRIOR PRIOR ALARM
IRF ENABLE ALARM SIGNAL 2 SIGNAL 1 TRIP
70 71 72 74 75 77 78 80 81 68 69 65 66

+ + + + + +

F E D C B A

SGR4/2
R TRIP

1 1 1 1 1
SGB/7
SGB/8

SGR2/1
SGR2/2
SGR2/3

SGR1/3
SGR1/4
SGR1/5
SGR1/6
SGR1/7

SGR2/4

SGR2/7
SGR2/8
SGR4/3

SGR1/1
SGR1/2

SGR2/5
SGR2/6
IRF SELF HOLD.
3 > i

SGR1/8
> a
> t
START

STALL
I s>
2
Is x ts
RESTART RESTART
INHIBIT INHIBIT
ts>
I>>

Io>

I<

Relconf.fh4
EXTERNAL TRIP

RELAY RESET I/O U1 SPCJ 4D34

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 17 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Comprehensive post-fault analysis
DATA REGISTERED DURING THE LATEST EVENT (n) DATA REGISTERED DURING THE PREVIOUS EVENT (n-1)
Latest memorized, event (n) Duration of latest 2 Previous event (n-1) 3 Duration of previous
1 final value of phase current IL1 1
value of phase L1 activation of unit I>
activation of unit I>

Latest memorized, event (n) Duration of latest 2 Previous event (n-1) 3


Duration of previous
2 1 activation of unit I>>
final value of phase current IL2 activation of unit I>> value of phase L2

Latest memorized, event (n) Duration of latest Previous event (n-1) 3 Duration of previous
3 1 2 activation of unit I<
final value of phase current IL3 activation of unit I< value of phase L3

Latest memorized, event (n) 1 Duration of latest 2 Previous event (n-1) Duration of previous
4 final value of neutral current Io activation of unit Io value of current Io 3
activation of unit Io

Latest memorized, event (n) Duration of latest Previous event (n-1) 3 Duration of previous
5 1 2
value of unbalance I activation of unit I
final value of unbalance I / IL activation of unit I

Latest memorized, event (n) Motor start-up 2 Previous event (n-1) 3 Motor star t-up
6 1 count at event (n-1)
final value of star t-up stress count at event (n) value of star t-up stress

Latest memorized, event (n) Thermal level before 2 Thermal level after 3
Thermal level before
7 final value of thermal level m
1
the latest event (n) the prior event ( n-1 ) the prior event ( n-1 )

8 Actual value m of the 1 Actual value of the


thermal capacity used phase unbalance I

Vika_ana.fh4
Approximate time ti before Actual value ts of the 2 Start-up time ts of the Counter for number
9 1 3
a restart attempt is enabled start-up time counter latest motor start-up of service hours

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 18 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Serial communication features
When the relays is connected to a control data
communicator the following parameters can be accessed:
• Actual measured values can be read
• Analogue setting values and switchgroup settings can
be read and, if necessary, changed using a password
• Recorded fault parameters can be read and erased
• Status information of output relays, etc. can be read
• Spontaneous reporting of selected events to an event
recorder or a printer

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 19 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
High immunity to electrical interference
• Galvanically isolated electronic circuits
• Protection by enclosure of relay case to IP 54
• High immunity to electrical interference:
Insulation test to IEC 60255-5 2 kV, 50 Hz, 1 min
Impulse test to IEC 60255-5 5 kV, 1.2/50 s, 0.5 J
High frequency test to IEC 60255-22
- common mode, class III 2.5 kV, 1 MHz, 400 bursts/s
- differential mode, class III 1.0 kV, 1 MHz, 400 bursts/s
Fast transient test to IEC 60255-22 4 kV, 5/50 ms
Electrostatic discharge test to IEC 60255-22-2 8 kV/6 kV
Electromagnetic field test to IEC 60801-3 10 V/m, 150 kHz...1000 MHz
Magnetic field test to IEC 60521 400 A/m

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 20 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Continuous self-supervision
Test object Check contents Execution frequency
Memory
- RAM Rotating “one” One byte per 10 ms
- ROM Checksum
- EEPROM Write and read of
reference voltage

Microprocessor Watch-dog Every 5 ms


A/D converter, Measuring of Once a minute and always
reference voltage before tripping

MUX and amplifiers


Settings Checking for
correct value Once a minute
Man-machine display Visual inspection Only on connection of supply voltage
DG/DC converter Measurement of
supply voltages Once a minute
Output amplifiers Feedback from
and trip relay coil output relays Once a minute
Program execution Watch-dog Every 5 ms
Watch-dog Auto-reset and IRF relay

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 21 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Push-button operation guide
MAIN MENU SUBMENU SETTING MODE
REV. STEP 0.5 s
STEP 0,5 s PROGRAM 1 s PROGRAM 5 s PROGRAM 5 s
FWD. STEP 1 s

Normal status, display off

First measuring value

REV. STEP 0.5 s


INCREASE VALUE
Last measuring value STEP 0.5 s
FWD. STEP 1 s

1 Main setting 1 0 0 0
Actual setting value 1 value for stage 1

MOVE FIGURE OR DECIMAL POINT


2 Second setting
Actual setting value 2 value for stage 1 CURSOR WITH THE PROGRAM BUTTON 1 s

STORE THE NEW SETTING BY PRESSING


3 STEP AND PROGRAM BUTTONS
SIMULTANEOUSLY AFTER THE VALUE
HAS BEEN SET AND THE WHOLE

Painiket.fh4
Memorized values etc.
DISPLAY IS BLINKING

NOTE ! In most menu charts the submenus have been drawn in a horizontal direction
in order to ge all main and submenu positions shown in the same chart.

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 22 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Settings of switchgroup SGF

Default pr.
No inhibit
Def.time

Setting
Is2 x ts

8 xI
4xI
6xI

Yes
No
SGF
1 High-set O/C protection in use 1 0 1 x 1=
2 High O/C setting doubled during startup 1 0 1 x 2=
3 E/F protection inhibited 0 1 0 1 0 x 4=
4 for phase currents above: 0 0 1 1 0 x 8=
5 Phase unbalance protection in use 1 0 1 x 16 =
6 Phase reversal protection in use 1 0 1 x 32 =
7 Startup super vision 0 1 1 x 64 =

SGFr yhma.fh4
8 Underload protection in use 1 0 0 x 128 =
Checksum
(default = 115 )

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 23 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Control signal switchgroup SGB

Default pr.

Setting
Yes
No
SGB
1 Signal BS used as motor speed switch 1 0 0 x 1=
2 Motor restar t inhibited by signal BS 1 0 0 x 2=
3 Phase unbalance unit blocked by signal BS 1 0 0 x 4=
4 Earth-fault unit blocked by signal BS 1 0 0 x 8=
5 External trip order from signal BS 1 0 0 x 16 =
6 External relay reset via signal BS 1 0 0 x 32 =
7 Latching tripping signal TS2 for l>>,lo, l 1 0 0 x 64 =
8 Internal tripping signal always latched 1 0 0 x 128 =
Checksum =
(default = 000)

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 24 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Output relay configuration switchgroup SGR1

Default pr.

Setting
Yes
No
SGR1
1 Thermal prior alarm linked to SS2 1 0 1 x 1=
2 Thermal trip signal linked to SS2 1 0 0 x 2=
Stall protection trip signal linked to SS2 1 0 0 x 4=
3
4 l>> trip signal linked to SS2 1 0 0 x 8 =
5 l trip signal linked to SS2 1 0 0 x 16 =
6 Io> trip signal linked to SS2 1 0 0 x 32 =
7 l< trip signal linked to SS2 1 0 0 x 64 =
8 lo> trip signal linked to TS2 1 0 1 x 128 =
Checksum
(default = 129)

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 25 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Output relay configuration switchgroup SGR2

Default pr.

Setting
Yes
No
SGR2
1 Thermal prior alarm linked to SS1 1 0 0 x 1=
2 Motor startup information linked to SS1 1 0 1 x 2=
3 l>> start output linked to SS1 1 0 0 x 4=
4 Thermal trip signal linked to SS3 1 0 1 x 8=
5 Stall protection trip signal linked to SS3 1 0 1 x 16 =
6 l trip signal linked to SS3 1 0 1 x 32 =
7 lo> trip signal linked to SS3 1 0 1 x 64 =
8 U< trip signal linked to SS3 1 0 1 x 128 =
Checksum
(default = 250)

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 26 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Behaviour of thermal unit at two cold starts
A Thermal capacity curve taking into account
the hot spot behaviour at heavy overload
B Thermal history curve following % Thermal Capacity
curve A at a rate of p% 100

C Rapid increases in thermal capacity 80


available when hot spots are levelled out F H
60 C

Kylmakay.fh4
D Cooling down when the motor is I
K
A
running at normal load 40 E G

E Restart enabled when the thermal 20 B


level falls below the set inhibit level D
t
F The thermal capacity is used according
First startup Running Second startup Motor running at normal load
to this curve during the second start-up
G The thermal background curve follows curve F with a rate p%
H Rapid increase in available thermal capacity due to hot spot levelling
I When the motor runs at normal current, the curves decline to the normal heat level
K The restart enable is activated when the thermal level goes below the set inhibit level

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 27 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Behaviour of thermal unit at a hot start
A Thermal capacity curve taking into
account the hot spot behaviour at
heavy overload
B Thermal history curve following Thermal Capacity
gcurve A at a rate of p% 100
A C
80
C Rapid increase in thermal capacity B
D F

available when hot spots are 60


H

levelled out G
40

Mootlamp.fh4
E
D Cooling down at standstill at a rate 20
decreased by a factor kc
t
E Restart enabled when the thermal Overload leading Cooling down at standstill, time in minutes. Restart at I = Is Motor running,
level falls below the set inhibit level to a thermal trip. for time t = t
s
time in minutes.

F The thermal capacity is used at this rate during start-up


G The thermal background curve follows curve F with a rate p%
H When the motor runs at normal current level, the curves decline to the
normal heat level

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 28 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Thermal unit equations % Thermal Capacity
100
Heating during overload: A C
80 D
A = (l / (1.05 x l ))2 x (1-e -t/ ) x 100% B

Lampyht.fh4
2 -t/ ) x p% 60
B = (l / (1.05 x l )) x (1-e

Cooling at normal load or during standstill:


When the current falls below 1.0 x l , the thermal curve A is linearly
brought down to the level of the thermal history curve B as shown in curve part C.
This corresponds to the levelling out of the hot spots in the motor.
Thereafter the cooling follows the lower curve with a time constant
equal to the heating time constant as long as the motor is running at normal load or idling.
For a motor at standstill, i.e. when the current is below 12% of l , the cooling can be expressed as:
Q=Q02 x e -t/kc x , where Q0 is the initial thermal level and kc is the cooling time multiplier.
In the equations above, the heating time constant can be substituted by 32 x t6x.
The thermal unit is supervised twice a second in the relay, giving a maximum trip time
resolution of 0.5 s.

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 29 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Thermal trip curves
t/ s t/s t/s t/s
4000 4 000 4000 4000
3000 3 000 3000 3000

2000 2 000 2000 2000

1000 1 000 1000 1000

500 500 500 500


400 400 400 400
300 300 300 300

200 200 200 200

100 100 100 100


t [s]
6x

50 50 t6x [s] 50 50
40 120 40 40 40
120 t6x [s]
30 30 30 30
120
20 60 20 20 20
60

60
30
10 10 30 10 10
20 t [s]
20 30 6x
5 15 5 5 5
15
4 4 4 20 4 120
10 15
3 3 10 3 3

2 2 2 10 2 60
5 5

T h er mc ur. FH4
1.05 1 .05 1.0 5 2.5 5 1.05 2.5 5 10 15 20 30
1 2. 5 1 2.5 1 1
1 2 3 4 5 6 8 10 l/l 1 2 3 4 5 6 8 10 l/l 1 2 3 4 5 6 8 10 l/l 1 2 3 4 5 6 8 10 l/l
Cold curve; prior load = 0 Hot curve; prior load = 1.0 x l Hot curve; prior load = 1.0 x l Hot curve; prior load = 1.0 x l
p = 20...100% p = 20% p = 50% p = 100%

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 30 (31) EN 09.2000
Motor Protection Relay SPAM 150 C
Operate time of unbalance unit
120

100

t 80
s

60

50

40
t
s
30

120

20 100

80

60

10

40
8

20
4

Op_times.FH4
1
10 20 30 40 50 60 70 80 90 100
I/ IL [%]

ABB Automation
ABB Substation Automation Oy
spam150Cb.ppt 1MRS750224-MPR p 31 (31) EN 09.2000