Large Generator Protection en
Large Generator Protection en
Protection of Medium-
Sized and Large Generators
with SIPROTEC 7UM6
n 1. Introduction
Medium-sized and large generators make a major
contribution to power generation. They carry the
basic load and ensure the stability of an energy
system.
The task of electrical protection in these systems is
to detect deviations from the normal condition
and to react according to the protection concept
and the setting. Based on experience with larger
power station units, cost-effective protection con-
cepts can also be implemented with SIPROTEC
relays for medium-sized generators.
The scope of protection must be in reasonable re-
lation to the total system costs and the importance
of the system.
n 2. Basic connections
In medium-sized and large power stations the
generators are operated exclusively in unit
connection.
In the unit connection the generator is linked to
the busbar of the higher voltage level via a trans-
former. In the case of several parallel units, the
generators are electrically isolated by the trans-
formers. A circuit-breaker can be connected be- Fig. 1 SIPROTEC generator protection
tween the generator and the transformer
(see Figs. 2 and 3).
Generator data
Rated voltage UN 15.75 kV ± 5 %
Rated apparent power (40 °C cold gas) SN 327 MVA
Circuit-breaker cos ϕ 0.8
Rated active power PN 261.6 MW
Rated current IN 12 kA
Rated frequency fN 50 Hz
Maximum overexcitation (U/f)max % from the manufacturer’s overexcitation characteristic
Permissible overexcitation duration t (U/f)max from the manufacturer’s overexcitation characteristic
Synchronous longitudinal reactance xd 264.6 %
(for drum rotor generators: xd = xq)
Transient reactance xd1 29.2 %
Maximum exciter voltage Uexc-min 77 V
Maximum continuous permissible inverse current Imax prim / IN 10 %
Thermal continuous permissible primary current Imax / IN 1.2
2
Asymmetry factor (I2) K = (I2/IN) t 20 s
As described in the manual, the protection has Parameter Setting options Setting
three characteristics which can be set independ-
Pickup value of the 0.10 to 20.0 A 1.20 A
ently: overcurrent pickup
n Zone (instantaneous zone Z1) with the setting Pickup voltage of the 10.0 to 125.0 V 75.0 V
parameters undervoltage seal-in
ZONE Z1 reactance = reach, Seal-in time of the 0.1 to 60.0 s 10.0 s
ZONE1 T1 = 0 or short delay if necessary. undervoltage seal-in
n Overreach zone Z1B, controlled externally by a Trip time of the end time stage 0.1 to 60.0 s 3.0 s
binary input with the setting parameters
Impedance zone Z1 0.05 to 130.0 Ω 7.28 Ω
OVERR. Z1B reactance = reach,
OVERR. T1B T1B = 0 or short delay if necessary. Trip time zone Z1 0 to 60.0 s; ∞ 0.30 s
n 2nd zone (Zone Z2) with the setting parameters Impedance overreach stage Z1B 0.05 to 65.0 Ω 11.44 Ω
ZONE Z2 reactance = reach, Trip time overreach stage Z1B 0 to 60.0 s; ∞ 8.00 s
ZONE2 T2 T2 should be chosen so high that it
is above the grading time of the system protec- Impedance zone Z2 0.05 to 65.0 Ω 11.44 Ω
tion. Trip time Z2 0 to 60.0 s; ∞ 8.00 s
n Undirected final stage with the setting parame- Table 9 Parameter overview for the impedance protection
ters T END T END must be chosen such that
the second or third stage of the series-connected 4.7 Overvoltage protection (ANSI 59)
power system distance protection is overreached. This protection prevents insulation faults as a
Since it can be assumed that the impedance pro- result of high voltage. Optionally the maximum
tection measures into the generator transformer, phase-to-phase voltages or phase-to-earth volt-
it must be ensured that the parameterization ages (in low-voltage generators) can be evaluated.
selec- tion sufficiently considers the control range In the phase-to-phase voltages, the measuring re-
of the transformer. For ZONE Z1, a reach of sult is independent of the zero point displace-
about 70 % of the zone to be protected is therefore ments resulting from earth-faults. The protection
normally chosen (i.e. about 70 % of the trans- function is designed in two stages.
former reactance) without or with only slight de- The setting of the limit values and delay times of
lay (i.e. = 0 s to 0.50 s). the overvoltage protection depends on the speed
For ZONE Z2, the reach could be set to about at which the voltage regulator can regulate volt-
100 % of the transformer reactance or a system age fluctuations. The protection may not interve-
impedance additionally. The corresponding time ne in the regulating process of the voltage regula-
stage ZONE2 T2 must be chosen so that it tor when it is operating trouble-free. The two-
overgrades the system protection relays of the fol- stage characteristic must therefore always be
lowing lines. above the voltage time characteristic of the regu-
lating process.
The following settings apply for the configuration
example (without activation of the out-of-step Setting instructions
block): The long-time stage U> and T U> should inter-
vene in the case of steady-state overvoltages. It is
set to about 110 to 115 % UN and to 1.5 to 5 s,
depending on the regulator speed. In the event of
a full load disconnection of the generator, the
voltage first rises according to the transient volt-
age and is reduced to its rated value by the voltage
regulator afterwards. The U>> stage is generally
set as a short-time stage so that the transient pro-
cess in full load shutdown does not lead to trip-
ping. About 130 % UN – with a delay T U>> ran-
ging from zero to 0.5 s – are usual (for example)
for U>>.
Monitoring of the rotor earth circuit for interrup- in generators with high earth capacitances – e.g.
tion takes place by evaluating the current during large hydroelectric generators – is enabled. Angle
polarity reversals. faults due to the earthing or star-point trans-
former are detected during commissioning and
Setting instructions (1 to 3 Hz protection) corrected in the algorithm. The protection func-
Since the protection calculates the resistive rotor tion has a warning and trip stage. In addition, the
earth resistance directly from the values of applied measuring circuit is monitored and a failure of the
voltage, series resistance and flowing earth-current,
the limit values for the alarm stage (RE WARN) and 20 Hz generator detected. Regardless of the earth
the trip stage (RE TRIP) can be set immediately as resistance calculation, the protection function ad-
resistance values. In most cases the preset values ditionally evaluates the r.m.s. value of the current.
(RE WARN = 40 kΩ and RE TRIP = 5 kΩ) are suffi- Another stage is available for earth-faults in which
cient. Depending on the insulation resistance and the displacement voltage and thus the fault cur-
coolant, these values can be changed. It is impor- rent exceed a certain value.
tant to pay attention to an adequate margin be-
Taking the following parameters into considera-
tween the setting value and the actual insulation
tion, the following settings for the application
resistance. As a result of possible disturbances due
example apply.
to the exciter device, the setting for the alarm stage
is finally determined during the primary tests. n Load resistance on the earthing transformer
The delay is usually set for the alarm stage (T RE RL = 4.63 Ω
WARN) to about 10 s, and for the trip stage (T RE n Transformation ratio, voltage divider
TRIP) to a short time of about 1 s. üKl = 200 / 5
The set times are additional time delays which do n Transformation ratio, voltage divider
not include the operating times (measuring time, üdivider = 2 / 5
dropout time) of the protection function. n Transformation ratio, earthing transformer
ütransf = 15.75: 3 / 0.5 kV
Parameter Setting options Default *)
Parameter Setting Setting
Pickup value of the 5 to 80 kΩ 40 kΩ
options
alarm stage
Pickup value of the 20 to 700 Ω 193 Ω
Pickup value of the 1 to 10 kΩ 5 kΩ
alarm stage SES 100 %
trip stage
Pickup value of the 20 to 700 Ω 48 Ω
Delay time of the 0 to 60 s; ∞ 10 s
trip stage SES 100 %
alarm stage
Delay time of the alarm stage 0 to 60 s; ∞ 10 s
Delay time of the 0 to 60 s; ∞ 1s
SES 100 %
trip stage
Table 13 Parameter overview for the rotor earth-fault Delay time of the trip stage 0 to 60 s; ∞ 1s
protection SES 100 %
Pickup value 100 % I>> 0.02 to 1.5 A 0.27 A
Monitoring threshold for 0.3 to 15 V 1V
4.12 100 % stator earth-fault protection with 20 Hz voltage
20 Hz injection (ANSI 64 G (100 %))
Monitoring threshold for 5 to 40 mA 10 mA
The injection of a 20 Hz voltage for detection of 20 Hz current
faults in the star point or close to the star point of
Angle correction for I SES 60 ° 0°
generators has proven a safe and reliable method.
Unlike the 3rd harmonic criterion (see page 12, Transition resistance Rps 0 to 700 Ω 0Ω
Catalog SIP 6.1), it is independent of the genera- Parallel load resistance 20 to 700 Ω; ∞ ∞Ω
tor properties and the operating method. Mea- Table 14 Parameter overview for the 100 % stator earth-fault
surement at system standstill is still possible. This protection
protection function is designed so that it detects
earth-faults both in the whole generator (real
100 %) and in all galvanically connected system
components. The protection relay detects the in-
jected 20 Hz voltage and the flowing 20 Hz cur-
rent. Disturbance variables such as stator earth
capacitances are eliminated, and the ohmic fault
resistance is determined by a mathematical model.
As a result, high sensitivity is ensured and the use
n 7. Summary
Beginning with the recommendations for protec-
tion functions [1], it has been described that effi-
cient concepts can be created with modern
SIPROTEC relays in medium-sized generators,
despite the need to consider cost factors. The mul-
tifunctional, numerical SIPROTEC relays enable a
greater functional scope than the previous single
relays. Self-monitoring substantially improves the
availability of the protection relays.
For further information about the function range
and setting, the 7UM62 manual is recommended,
Fig. 8 Connection diagram of 7UM6 chapter 2 of which has been compiled as an appli-
cation manual.
n 8. References
Herrmann, H.-J.: “Digitale Schutztechnik”
(Digital Protection Technology).
Basic principles, software, examples of
implementation.
VDE-Verlag GmbH, Berlin 1997,
ISBN 3-8007-1850-2.
Herrmann, H.-J.: “Elektrischer Schutz von
Kleinkraftwerken” (Electrical Protection of Small
Power Stations).“Elektrizitätswirtschaft Jg. 97”
(Electricity Industry Year 97) (1998) Issue 24
Manual
7UM62 Multifunction Generator, Motor and
Transformer Protection Relay