Anchor Block and Thrust Block Design and Stability Check

The document provides design details for an anchor block and thrust block for a penstock pipe. It includes input data on pipe dimensions, water levels, soil properties, and forces acting on the block. Calculations are shown for volume of the anchor block segments, weight of soil and pipe, and moments due to dead load, pipe weight, water pressure, and forces in the bend under normal operating conditions. The results will be used to check stability of the anchor block.

Uploaded by

Engr AtaUllah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views

Anchor Block and Thrust Block Design and Stability Check

The document provides design details for an anchor block and thrust block for a penstock pipe. It includes input data on pipe dimensions, water levels, soil properties, and forces acting on the block. Calculations are shown for volume of the anchor block segments, weight of soil and pipe, and moments due to dead load, pipe weight, water pressure, and forces in the bend under normal operating conditions. The results will be used to check stability of the anchor block.

Uploaded by

Engr AtaUllah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Design, Procurement and Construction of 84 MW Sheet No.

Gorkin-Matiltan Hydropower Project Designed AuH


Doc. No. GMHP-BK-C-PS-CA-003 R 00 Checked MHF

Component Penstock Date 21-Mar-18


Description Penstock Anchor Block and Thrust Block Design - AB-1

Data Input:
Anchor Block or Thrust Block Type (AB, TB) AB
Anchor Block or Thrust Block Number 1
Inside dia. of Penstock Pipe D1 3.25 m
Thickness of the pipe t 14 mm
Outside dia of penstock pipe D2 3.278 m
Normal operating level in the Surge Tank ZNormal 2296 m (amsl)
Maximum surge level in the Surge Tank ZMax.Surge 2325 m (amsl)
Level at centre of the penstock at downstream end of A.Block ZA.Block 2215.399 m (amsl)
Design Head at the centre of the Anchor Block - Normal Condition HD-Normal 80.6 m
Design Head at the centre of the Anchor Block - Emergency condition HD-Emergency 109.6 m
Design Discharge for power Generation Q= 42 m3/s
Upper Pipe length -Supported by Anchor Block L1 15 m
Upper Pipe length -Supported by Anchor Block L2 15 m
horizental angle of upper pipe α1 = 0 deg
horizental angle of lower pipe with upper pipe α2 = 45 deg
Unit weight of Steel g Steel 77.5 kN/m
3

Unit weigh of water g Water 9.81 kN/m3


Unit weight of concrete g Concrete 24 kN/m3
Height of soil over penstock (cover over the Penstock) Scover 1.5 m
Unit weight of the backfill soil (cover over the Penstock) g Soil 19 kN/m3
Friction coefficient between concrete and foundation soil mConc-soil 0.6
Weight of Pipe per unite length WPipe 11.13 kN/m
Weight of water contained in pipe per unit length WWater 81.38 kN/m
wieght of soil over penstock WSoil 93.42 KN/m
Velocity of water in the pipe Velocity 5.06 m/s
Sectional internal area of the pipe APipe 8.30 m2
Allowable Bearing Capacity of of the foundation soil - in Normal Conditions q allowable 215 kN/m2
( Ref: GMHP-BK-C-GE-Gr-004 Geotechnical Design Report )
2
Ultimate Bearing Capacity of the foundation soil - in Emergency Conditions q Ultimate 430 kN/m
Weight of Soil over the Upper Pipe to be included in the Analysis No
Weight of Soil over the Lower Pipe to be included in the Analysis Yes

Sheet No.: 34
Forces Acting on the Anchor Block:
1) Weight of Pipe shell per meter
Wst1 = Wst2 = π*D*t*γs 11.13 kN/m
2) Weight of water in pipe per meter
2
WW1 = WW2 = (π*D /4)*γs 81.38 kN/m

3) Weight of Soil Cover over pipe

Weight of soil over upper pipe per meter 0.0 kN/m


Weight of soil over lower pipe per meter 93.4 kN/m

4) Vertical Downward Thrust due to weight of pipe , water and soil cover-Stabilising Forces
a) for Upper pipe
WUpper = (WS1+WW1)x l1 1387.6 kN
b) for lower pipe
WLower = (WS2+WW2)x l2 2789.0 kN

5) Weight of Soil Over Foundation


WSF 2758.8

6) Resultant force of water pressure acting at the bending point of pipe

Normal condition
Horizental Component P1A1Cosα1 - P2A2Cosα2 - rQ(V2Cosα2-V1Cosα1) Fx 1983.5 kN
Vertical Component P2A2Sinα2 -P1A1Sinα1-rQ(V1sinα1-V2sinα2) FZ 4788.6 kN
Resultant Force R 5183.1 kN
Angle with x Axis Ø 67.5 Deg

Emergency/ Sudden ShutDown Condition


Horizental Component P1A1Cosα1 - P2A2Cosα2 - rQ(V2Cosα2-V1Cosα1) Fx 2674.7 kN
Vertical Component P2A2Sinα2 -P1A1Sinα1-rQ(V1sinα1-V2sinα2) FZ 6457.4 kN
Sheet No.: 35
Resultant Force R 6989.4 kN
Angle with x Axis Ø 67.5 Deg
Anchor Block Shape:
No. of Segments/Steps in the Anchor Block 3.00
Anchor Block Upstream End Height Hups 5.50 m
Anchor Block Downstream End Height Hdwn 5.50 m
Width of Step -1 B1 1.70 m
Width of Step - 2 B2 2.00 m
Width of Step - 3 B3 2.50 m
Width of Step - 4 B4 0.00 m
Width of Step - 5 B5 0.00 m
Height of Step - I H1 1.00 m
Height of Step -2 H2 1.30 m
Height of Step -3 H3 0.00 m
Height of Step -4 H4 0.00 m
Length of the Anchor Block LA 6.20 m
Width of the block WA 5.00 m
Length of Foundaion LF 8 m
Width of Foundation WF 7 m
Height of foundation (typical) HF 0.80 m

Total Length of the A.Block HT 6.613 m


Average Height of the block Havg 5.50 m
3
Total volume VT 170.50 m

Deduct pipe volume


Pipe length in the block PL 6.613 m
Pipe Area (using External Dia) PA 8.44 m2
Pipe volume PV 55.808 m3
Total Anchor Block Volume Vnet 114.69 m3

STABILITY ANALYSIS:

Sheet No.: 36
Normal Conditions:
Force and Moment calculation of dead load of the Block
Volume Weight Lever Arm about Moment,kN-mabout
segment
m3 kN TOE CENTRE TOE CENTRE
1 28.1 675.5 6.35 -2.25 4290 -1520
2 36.4 873.5 4.5 -0.4 3931 -349
3 50.15 1203.5 2.25 1.85 2708 2227
4 0.00 0.0 0.00 0.00 0 0
5 0.00 0.0 0 0 0 0
Foundation 45.9 1102.1 4.1 0 4519 0
WSF1 145.2 2758.80 4.1 0 11311 0
Total 305.8 6613 26758 357

Force due to Pipe Shell, Weight of Water and weight of soil cover
segment Foundation Load, kN Lever Arm about Moment, kN-m (about)
TOE CENTRE TOE CENTRE
Vertical

Upper Pipe 1388 8.20 -4.10 11378.4 -5689.20


Lower Pipe 2789 0.00 4.10 0.0 11434.71
In Block 612 4.10 0.00 2508.1 0
Total 4788 13887 5745.51

Forces due to Water in the Bend


Normal Condition:
Foundation Load, kN Lever Arm about Toe Moment, kN-m
Load Type
Horizental Vertical Hor. Vertical Hor. Vertical
Water. Pre Resultant at Bend 1983.5 4788.6 3.550 4.10 7041.4 19633.16
Total 1983.5 4788.6 7041.4 19633.2

Emergency/ Sudden ShutDown Condition :


Foundation Load, kN Lever Arm about Toe Moment, kN-m
Load Type
Horizental Vertical Hor. Vertical Hor. Vertical
Water. Pre Resultant at Bend 2674.7 6457.4 3.550 4.10 9495.3 26475.31
Total 2674.7 6457.4 9495.3 26475.3

A. Sliding Check:
1- Normal Conditions
Total Sliding Forces Fsliding 1983 kN
Sheet No.: 37
Total Resistance Forces Fresisting Vertical x m Fresisting 3968 kN

Factor of Safety 2.00 >1.5, OK

2-Emergency/ Sudden ShutDown Condition


Total Sliding Forces Fsliding 2675 kN
Total Resistance Forces Fresisting Vertical x m Fresisting 2967 kN

Factor of Safety 1.11 >1.1, OK

B. Safety Against Overturning


1- Normal Conditions
Total overturning bending moment MOverturning 26675 kN
Total Resisting Bending Moment MResisting 40645 kN

Factor of Safety 1.52 >1.5, OK


Location of the Resultant B/6 (m) = 1.37 e (m) 0.14 e<B/6, OK

2- Emergency/ Sudden ShutDown Condition


Total overturning bending moment MOverturning 35971 kN
Total Resisting Bending Moment MResisting 40645 kN

Factor of Safety 1.13 >1.1, OK


Location of the Resultant B/4 (m) = 1.550 e (m) 0.69 e<B/4, OK

C. Check Against Bearing Capacity

a. Anchor Block
Area of the Anchor Block Foundation A 57.4 m2
Section Modulus of the Anchor Block Foundation S 78.4 m3

1- Normal Conditions
Total moment at centre of the foundation M 7399 kN-m
Total vertical load at centre of the foundation V 2437 kN

2
Bearing Pressure at TOE of the Anchor Block Pr-TOE 136.8 kN/m
Bearing Pressure at HEEL of the Anchor Block Pr-HEEL -51.9 kN/m2
OK <B.C
Sheet No.: 38
Bearing Pressure- Rectangular P-Rec 44.0 kN/m2
Allowable Bearing Capacity 215 kN/m2
Ratio of allowable B.Capacity to Applied B. pressure B.C/B.p 1.57

2- Emergency/ Sudden ShutDown Condition


Total moment at centre of the foundation M 9852 kN
Total vertical load at centre of the foundation V 768 kN

Bearing Pressure at TOE of the Anchor Block Pr-TOE 139.0 kN/m2


Bearing Pressure at HEEL of the Anchor Block Pr-HEEL -112.2 kN/m2
OK <B.C
2
Bearing Pressure- Rectangular P-Rec 13.9 kN/m
Allowable Bearing Capacity 430 kN/m2
Ratio of allowable B.Capacity to Applied B. pressure B.C/B.p 3.09

b. Supported pipe
2
Bearing Area under Supported pipe 49.2 m

Total Vertical Load at the base of upper pipe 1387.6 kN


Total Vertical Load at the base of lower pipe 2789.0 kN
2
Bearing Pressure - Upper Pipe 28.2 kN/m
Bearing Pressure - Lower Pipe 56.7 kN/m2
Allowable Bearing Capacity 215.0
Ratio of allowable B.Capacity to Applied B. pressure B.C/B.p 3.79
OK

Sheet No.: 39