Conductor Stringing Chart - 1
Conductor Stringing Chart - 1
s
Section- DL-2 TO DL-01
Section #21 from structure #8 to structure #9, start set #3 'TOP X LEFT NEAR', end set #3 'C-R'
Cable 'h:\pls cadd files\cable\aaac yew-midal', Ruling span (m) 188.852
Sagging data: Catenary (m) 1889.88, Horiz. Tension (N) 25891 Condition I Temperature (deg C) 35
Results below for condition 'Initial RS'
Calculations done using actual span lengths and vertical projections
Span Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Left Span
Length Span Span Span Span Span Span Span Span Span Span Span Span Span Span Span Span Span Struct Vertical
Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
0 C 5 C 10 C 15 C 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C 75 C 80 C
(m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m)
188.9 1.50 1.60 1.70 1.82 1.94 2.07 2.22 2.36 2.52 2.68 2.84 3.00 3.17 3.33 3.49 3.66 3.82 8 -5.51
Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz
Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension
0 C 5 C 10 C 15 C 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C 75 C 80 C
(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N)
40821 38325 35955 33669 31509 29517 27610 25891 24299 22853 21555 20383 19316 18376 17509 16736 16038