Premium Processors Implementation Manual
Premium Processors Implementation Manual
TSX 57/PCX 57
Processors
Implementation Manual
Volume 1
June 2006 eng
35011052 03
2 35011052 03 June 2006
Document Set
Document Set
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 445
General points This manual is meant to be used by people who are qualified in the technology
needed to work with and maintain the products described therein. It contains the
required information which is adequate to conform with the proper use of the
products. However, those who wish to make more "advanced" use of our products
may find it necessary to consult our nearest distributor in order to obtain additional
information.
The manual's contents are not binding and in no way restrict or infringe on the
clauses of the guarantee.
User Only qualified persons are authorized to use, work with or maintain these products.
qualifications The interference of non-qualified persons or failure to observe the security setpoints
contained in this manual, or attached to the devices, can endanger the safety of
such persons, or irretrievably damage the equipment. The following persons can be
designated as "qualified persons":
z at application design level, design office personnel who are familiar with
automation security concepts (e.g., a design engineer, etc.),
z as far as the use of the devices is concerned, people who are familiar with the
installation, connection and starting of automatic devices (for example, a fitter or
cable installer during the installation phase, an operating technician, etc.)
z as far as operating is concerned, persons familiar with using and managing
automatic devices (for example an operator, etc.)
z as far as preventive or corrective maintenance is concerned, persons trained and
qualified in regulating or repairing automatic devices (for example an operating
technician, an after-sales service technician, etc.).
Electrical and Details of the electrical and thermal characteristics of the devices can be found in
thermal the associated technical manuals (operating manuals, service instructions).
properties
At a Glance
Document Scope This manual describes the installation of the Premium range of PLCs and their main
accessories:
It is made up of 6 sections:
z 1 General introduction to a TSX P57 PLC station and a PCX 57 PLC station,
z 2 Standard and extendable TSX RKY racks ,
z 3 TSX P57 Premium Processors,
z 4 PCX 57 Atrium Processors,
z 5 TSX PSY power supply modules,
z 6 Process and AS-i Power Supplies.
Validity Note The updated version of this manual takes the new processors into account.
User Comments We welcome your comments about this document. You can reach us by e-mail at
[email protected]
I
At a Glance
Aim of this Part The Part gives a general introduction to the Premium TSX P57 PLC station and the
Atrium PCX 57 PLC station.
Aim of this This Chapter gives a general introduction to TSX P57 and PCX 57 PLC stations.
Chapter
General Premium TSX P57 automated platform processors manage the entire PLC station,
which is made up of "Discrete" input/output modules, analog input/output modules
and application-specific modules. These can be distributed over one or several
racks connected to the X Bus or the field bus.
5 6
1 2 3 4
General Atrium PCX 57 coprocessors are built into a PC and manage an entire PLC station
composed of the same input/output modules as the Premium processors (i.e.
"Discrete", analog, application and communication modules). These modules can
be distributed over one or more racks connected to the X Bus.
4
3
Aim of this The aim of this Chapter is to provide an overview of the different components which
Chapter may make up a PLC station.
General points Each PLC station is provided with a processor, chosen according to:
z its integration type: integration on rack or integration in a PC,
z the processing power necessary: number of discrete I/Os, analog I/Os, etc.,
z memory capacity,
z processing type: sequential or sequential + process control.
See TSX P57 Premium processors, p. 143.
Processor Illustration
Double format processors with on-board
Ethernet:
z TSX P57 2623,
z TSX P57 2823,
z TSX P57 3623/3623A,
z TSX P57 4823/4823A.
General points Installed on the ISA bus of an industrial or office PC running in a Windows 95 or NT
environment, they are used to control a PLC station.
Also, installation of a communication driver enables transparent communication
between the host PC and the processor, without the need for another programming
terminal.
There are two types of sequential Atrium PCX 57 processor that can be integrated
in a PC:
z PCX 57 203,
z PCX 57.353.
Examples The following illustration shows the standard 6-position TSX RKY rack:
The following illustration shows the extendable 12-position TSX RKY rack:
X Bus
General points Each rack requires a power supply module (See TSX PSY supply modules, p. 323)
defined according to the distributed network (alternating or direct current) and the
power required for the rack.
There are two types of modules:
z standard format power supply module,
z double format power supply module.
Illustration The following illustration shows the two formats for TSX PSY power supply modules:
General introduction to Process and AS-i TSX SUP and TSX 1021/1051 power
supply modules
Process power A wide range of power supply units and modules is offered to meet your needs in
supply modules the best possible way. Controlled by Premium TSX/PCX PLCs and designed to
supply the peripherals of an automation system with 24 VDC, they can all be
mounted on a Telequick AM1-PA mounting board and some can be mounted on a
AM1-DP200 / DE 200 central DIN rail.
SeeProcess and AS-i supply, p. 389.
Illustration The following illustration shows the various types of TSX SUP and TSX 1021/1051
process power supply modules:
24 VDC / 10A
AS-i power They are designed to supply 30 VDC to components connected to the AS-i field bus.
supply module
Illustration:
General This module allows the extension of two bus segments from the rack supporting the
processor, up to a maximum distance of 250 meters. Each extended segment is
able to support racks distributed along the X Bus to a maximum length of 100
meters.
See X-Bus extension module, p. 125.
Discrete inputs/ A wide range of discrete input/output modules (Installation Manual Volume 2) are
outputs available to meet your needs in the best possible way. These modules differ from
one another in their:
Characteristics Description
modularity 8, 16, 28, 32 or 64 channels.
type of inputs z modules with direct current inputs (24VDC,
48VDC),
z modules with alternating current inputs
(24VAC, 48VAC, 110VAC, 240VAC).
type of outputs z modules with relay outputs,
z modules with direct current (24VDC / 0.1A -
0.5A - 2A, 48VDC / 0.25A - 1A) static outputs,
z modules with alternating current (24VAC /
130VAC / 1A, 48VAC / 240 VAC / 2A) static
outputs.
type of connectors screw terminal blocks and HE10 connectors
allow the connection of sensors and pre-
actuators via the TELEFAST 2 prewiring system.
Illustration:
HE10 connector Screw terminal block
connector
Analog inputs/ The range of analog input and output modules (Installation Manual Volume 5) can
outputs meet your main needs. These modules differ from one another in their:
Characteristics Description
modularity 4, 8, 16 channels.
performance and range of signals offered voltage/current, thermoelectric couple, multi-
range (thermoelectric couple, heat probe,
voltage/current).
type of connectors screw terminal blocks or 25-pin SUB D
connectors allow the connection of the
sensors via the TELEFAST 2 prewiring
system.
General points Premium and Atrium PLCs offer main counting functions (down-counting, up-
counting, up/down counting) from the application-specific "counting" modules
("Installing the Counting Module", Premium and Atrium using PL7, Counter
modules, User manual).
General points Using the application-specific "axis control" modules (Installation Manual Volume 3),
Premium PLCs can be used to manage movement control applications, driven by
servomotors and with an analog value speed setpoint (+/- 10V).
Five modules are offered:
Module characteristics
2-channel module allows controlled positioning with two
independent, linear, limited axes.
2-channel module allows controlled positioning with two
independent, circular, infinite axes.
4-channel module allows controlled positioning with four
independent, linear, limited axes.
4-channel module allows controlled positioning with four
independent, circular axes.
3-channel module allows positioning on 2 or 3 synchronized
axes (linear interpolation).
3-channel module
General points Using application-specific "step by step command" modules (Installation Manual
Volume 3), Premium and Atrium PLCs can be used to manage movement control
modules, controlled by translators with a frequency speed setpoint.
1-channel 2-channel
General points Different modes of communication (Installation Manual Volume 4)can be used with
Premium PLCs:
z TSX processor communication on the terminal port:
these have two terminal ports (TER) and (AUX), a non-insulated RS 485 serial
link, UNI-TELWAY or character mode protocol.
These terminal ports can be used to connect:
z a programming terminal and/or an operator dialog console (UNI-TELWAY
master mode),
z the station to a multipoint UNITELWAY link (master or slave UNI-TELWAY
mode),
z a printer or a terminal in character mode.
Note: the communication protocol, as defined in the configuration, is identical for
both ports.
z PSX processor communication on the terminal port:
these have one terminal port (TER), a non-insulated RS 485 serial link,
UNI-TELWAY or character mode protocol.
As with TSX processors, these can be used to connect:
z a programming terminal or an operator dialog console (UNI-TELWAY master
mode),
z the station to a multipoint UNITELWAY link (master or slave UNI-TELWAY
mode),
z a printer or a terminal in character mode.
z Master FIPIO communication, built-in to some processors,
TSX P57x53 and PCX P57 353 processors feature as standard a master FIPIO
link, used to provide remote operation (maximum 15 kms) of devices such as:
- discrete I/Os,
- analog I/Os,
- speed drives,
- operation and supervising stations,
- devices,
- etc.
z Communication by means of PCMCIA cards which can be built into the
processor or the application-specific communication module
TSX SCY 21601: the processors and the application-specific communication
module TSX SCY 21601 have a slot which is used for accommodating an
extended type III PCMCIA communication card,
PCMCIA cards PCMCIA type III format communication cards (See TSX P57 processors:
diagnostics, p. 171).
Illustration Description
FIPIO link on PCX processors.
Communication by means of
PCMCIA cards which can be
built in to the processor or the
module.
Illustration Description
Communication via
application-specific module
TSX SCY 21601:
z 1: built-in communication
channel,
z 2: slot for PCMCIA card.
Communication via
application-specific module
TSX ETY 110.
General points This is a module which is used to connect an AS-i bus to a Premium TSX/PCX PLC
station.
This master module (Installation Manual Volume 4) manages and coordinates bus
access. It transmits data to all slaves and receives data from them.
General Using the TSX ISPY 101 and TSX ISPY 101 application-specific "weighing" modules
("Hardware installation of the weighing module", Premium and Atrium using
PL7 Pro, Weighing module, User manual), Premium PLCs can be used to manage
weighing applications: dosage, multi-product dosage, grading, flow control, weight
totalizer, etc.
This module offers a measurement input for a maximum of 8 sensors, 2 rapid
discrete outputs and a serial link for a displayed report.
General Depending on the rack modularity (4, 6, 8 or 12 positions), one, two or three
ventilation modules can be installed above each rack to help cool the different
modules by forced convection.
General points These are modules (Installation Manual Volume 2) with built-in safety device,
designed to control machine emergency stop circuits with the utmost safety.
These modules are used to cover safety functions up to category 4 according to the
EN 954-1 standard.
Aim of this This Chapter gives a general introduction to the different configurations which are
Chapter possible for TSX and PCX PLC stations.
General points The choice of rack (standard or extendable) and processor type defines the
maximum capacities of a Premium PLC station.
z the TSX P57 stations are composed of TSX P57 103 and 153 single format
processors and TSX P57 203/253/2623/2823/303/303A/353/353A/3623/3623A/
453/453A/4823/4823A double format processors.
100 m max
Station with standard rack: or,
1 rack, 6, 8 or 12 positions. 4 racks 4, 6 or 8
positions,
maximum length of
X Bus: 100 meters
Remote X bus
X Bus
≤ 250 meters
≤ 100m
X Bus
≤ 100m
Processor
Remote X bus X Bus
General points By selecting the PCX 57 203 or 353 processor type, you set the maximum capacities
of a Premium PCX PLC station.
This type of station, with the processor integrated in a PC, will be controlled with
extendable racks.
X1
X2
PC Station with extendable racks:
2 racks 12 positions or,
4 racks 4, 6 or 8 positions,
maximum length of X Bus (X1+X2): 100
meters.
X Bus
≤ 100 m
PCX 57353
X1
X2
≤ 100m ≤ 250m-X1
PCX 57353
≤ 100m ≤250m-X1
Aim of this This chapter deals with the operating standards and conditions of Premium and
Chapter Atrium PLCs.
General Premium and Atrium PLCs have been developed to conform to the principal national
and international standards for industrial electronic PLC equipment.
z Programmable PLCs: specific requirements: functional characteristics,
resistance, safety etc.
IEC 61131-2, CSA 22.2 N° 142, UL 508
z Merchant navy requirements of the major international organisations:
ABS, BV, DNV, GL, LROS, RINA, RRS, CCS etc.
z Adhering to European Directives:
Low Voltage: 73/23/EEC amendment 93/68/EEC
Electromagnetic Compatibility: 89/336/EEC amendments 92/31/EEC and 93/68/
EEC
z Electric qualities and self-extinguishability of insulating materials: UL 746C, UL
94
z Danger Zones Cl1 Div2 CSA 22.2 N° 213
"THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2,
GROUPS A, B, C AND D OR NON-HAZARDOUS LOCATIONS ONLY"
WARNING: "EXPLOSION HAZARD - DO NOT DISCONNECT WHILE CIRCUIT
IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS"
Legend
*: Tests required by EC directives
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
Legend
Un: Nominal Voltage Nf: Nominal Frequency Ud: Power-on detection level
*: Tests required by EC directives
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
Legend
SM: Serial mode CM: Common Mode WM: Wire Mode
*: Tests required by EC directives
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
Legend
(1) This test is carried out outside the casing, with the devices secured to a metallic
grill and wired as shown in the TSX DG KBL• Manual.
*: Tests required by EC directives
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
Legend
E.O: Device open E.F: Device closed Hr: Relative Humidity
Legend
rf: Resonance Frequency Q: Amplification Coefficient
General points PLCs in the Premium and Atrium range meet AP (all-climate processing) processing
requirements.
Premium PLCs have an IP20 protection index. They can thus be installed without a
protection casing in restricted-access areas which do not exceed Pollution Degree
2 (control room free of machines or any activity creating dust).
The Atrium card is designed for integration into a host PC. The host device must
therefore conform to the IP20 protection index.
Note: For a rack to conform to the IP20 protection index, the unoccupied module
slots must be protected by a TSX RKA 02 protection cover.
Subject of this This part concerns TSX RKY.. standard and extendable racks
Part
General points TSX RKY racks form the base unit of Premium PLCs.
These racks serve the following functions:
z Mechanical function:
they are used to mount a set of modules for a PLC station (i.e. supply modules,
processors, discrete/analog input/output modules, application-specific modules).
They can be mounted in cabinets, machine frames or on panels.
z Electrical function:
the racks have a built-in bus, called X-Bus, which distributes:
z the required supply for each module on the same rack,
z service signals and data for the whole PLC station when this is made up of
several racks.
Note: Two families of racks are offered in several modularities (4, 6, 8 and 12
positions):
z standard racks,
z extendable racks.
Standard racks They are used to make up a PLC station which is limited to a single rack.
This table presents the different standard racks:
Designation Illustration
TSX RKY 6 6-position rack
Extendable racks They are used to make up a PLC station which can have:
z a maximum of 8 TSX RKY 12 EX racks,
z a maximum of 16 TSX RKY 4EX/6EX/8EX racks.
These racks are distributed on a bus called X-Bus, whose maximum length is limited
to 100 meters.
A bus extension cable assures rack-to-rack bus continuity.
For applications which require a greater distance, a X-Bus extension module allows
the extension of two X-Bus segments from the rack which is supporting the
processor to a maximum distance of 250 meters.
Designation Illustration
TSX RKY 8EX 8-position rack
At a Glance They are used to make up a PLC station which is limited to a single rack.
6
8
7 5
6 2
Description The following table describes the different elements of a standard rack.
Number Description
1 Metal sheet which:
z supports the X-Bus electronic card, and protects against EMI and ESD interference.
z supports the modules,
z maintains the rack’s physical rigidity.
At a Glance They are used to form a PLC station which can be made up of several racks.
6 2
Description The following table describes the different elements of an extendable rack.
Number Description
1 Metal sheet which:
z supports the X-Bus electronic card, and protects against EMI and ESD
interference.
z supports the modules,
z maintains the rack’s physical rigidity.
Installing Racks
Introduction When mounting TSX RKY •• racks, certain installation rules must to be followed.
Rack Installation z 1 As the different modules (e.g. supply, processors, discrete I/O, etc.) are cooled
Rules: by natural convection, it is compulsory in order to facilitate ventilation (See
Description Ventilation module, p. 113) to install the different racks horizontally and
vertically.
z 2 If several racks are installed in the same cabinet, you are advised to comply
with the following advice on layout:
z leave at least 150 mm between two racks placed on top of each other, to allow
room for cable troughs and help air circulation.
z you are advised to install the devices which generate heat (eg transformers,
process supply, power contacts, etc.) above the racks,
z leave at least 100 mm on each side of a rack to allow room for cabling and to
help air circulation.
Note: If the hardware, other than the metal electrical cabinet, is installed in an area
with emissions limits between 30 MHz and 1GHz (as per EN 55022), you are
advised to use racks TSXRKY 8EX or TSXRKY6EX instead of TSXRKY8 and
TSXRKY6.
Overall Rack The following illustrations show the overall dimensions of TSX RKY •• racks.
Dimensions:
TSX RKY 4EX
Illustrations
165 mm (1)
151.5 mm
160 mm (1) 187.9 mm
200 mm (2)
TSX RKY 6/6EX
165 mm (1)
261.6 mm
335.3 mm
482.6 mm
The rules for installation (See Installing Racks, p. 78) are to be always followed,
whatever the type of mounting.
Mounting on 35 Fixing with four M6x25 screws + washers and AF1-CF56 1/4 turn sliding nuts.
mm wide DIN
mounting rail Diagram illustrating the mounting
4 fixing holes
(1)
(1) the diameter of the fixing holes must be sufficient to take M6 screws.
(1) The diameter of the fixing holes must be such as to allow M6 screws.
a and b see table.
Mounting on an Fix the rack using four M6x25 screws + washers and AF1-EA6 clips nuts.
AM1-PA
Telequick Plan of screw-holes (dimensions in mm):
mounting grid
Grounding racks Functional grounding of the racks is guaranteed by the back, which is made of metal.
This means that the PLCs can be guaranteed to conform to environmental norms;
assuming, however, that the racks are fixed to a metal support that is correctly
connected to ground. The different racks which can make up a TSX P57 PLC station
must be mounted either on the same support or on different supports, as long as the
latter are correctly interlinked.
For people’s safety, in every case, each rack’s grounding terminal must be linked to
the protective ground.
For this, use a green/yellow wire of with a minimum section of 2.5 mm2 and of the
shortest length possible.
Illustration:
support
connected
to the
ground
Note: The PLC’s internal 0V is linked to the ground connection. The ground
connection itself being linked to ground.
Aim of this This chapter describes the different functions of the TSX RKY.. standard and
Chapter extendable racks.
Introduction It is possible to build a PLC station with TSX P57 processor using:
z standard racks (See Standard racks, p. 71): TSX RKY 6/8/12,
z extendable racks (See Extendable racks, p. 72): TSX RKY 4EX/6EX/8EX/12EX.
Building using Standard racks can be used to build a TSX P57 PLC station limited to a single rack.
standard racks
Building using
extendable Extendable racks can be used to build a PLC station that contains a maximum of:
racks:
Station Number of racks
TSX RKY 4EX/
6EX/8EX/12EX For a TSX 57 10 station z 2 TSX RKY 12EX racks,
z 4 TSX RKY 4EX/6EX/8EX racks.
For a TSX 5720, 5730 or 5740 station z 8 TSX RKY 12EX racks,
z 16 TSX RKY 4EX/6EX/8EX racks.
Diagram
100 meters maximum
z (1) The same station can contain 4, 6, 8 and 12 position racks that are linked by
X Bus extension cables (See TSX CBY..0K X Bus extension cable (II ≥ 02),
p. 100) (labeled 1).
z (2)The X Bus must have a line termination (See Line terminator TSX TLYEX,
p. 105) (labeled 2) fitted at each end.
Note: The cumulative length of all the TSX CBY ..0K cables used in a PLC station
must never exceed 100 meters. For applications which require a distance of more
than 100 meters between racks, an extension module allows the extension of two
X bus segments from the rack supporting the processor, to a maximum distance of
250 meters, each X bus segment having a maximum distance of 100 meters.
X Bus extension Racks are connected by means of TSX CBY..0K X Bus extension cables which are
cable connected to the 9-pin SUB D connectors situated on the right and left of each
extendable rack.
Note: As the idea of in and out does not exist at the level of the 9-pin SUB D
connector, a cable can enter or leave using either the right or left-hand connector.
Line termination The two racks situated at the ends of the chain must always be fitted with a
TSX TL YEX line termination on the unused 9-pin SUB D connectors, labeled /A
and /B.
At a Glance It is possible to build a PLC station with PCX 57 processor using extendable racks:
TSX RKY 4EX/6EX/8EX/12EX.
Building using Extendable racks can be used to build a PLC station that contains a maximum of:
extendable racks
Station Number of racks
For a PCX 57 203 station z 8 TSX RKY 12EX racks,
z 16 TSX RKY 4EX/6EX/8EX racks.
Diagram:
TPCX 57 203
X1
PC
X2
z (1) The same station can contain 4, 6, 8 and 12 position racks that are linked by
X Bus extension cables (See TSX CBY..0K X Bus extension cable (II ≥ 02),
p. 100) (labeled 1).
z (2) The X Bus must have a line termination (See Line terminator TSX TLYEX,
p. 105) (labeled 2) fitted at each end.
Note: The cumulative length (X1+X2) of all the TSX CBY..0K cables used in a PLC
station must never exceed 100 meters. For applications which require a distance
of more than 100 meters between racks, an extension module allows the extension
of two X bus segments from the rack which is supporting the PCX 57 processor
virtually, to a maximum distance of 250 meters, each X bus segment having a
maximum distance of 100 meters.
X Bus extension Racks are connected by means of TSX CBY••0K X Bus extension cables which are
cable connected to the 9-pin SUB D connectors situated on the right and left of each
extendable rack and at the top of the front panel of the processor.
Note: As the idea of in and out does not exist at the level of the 9-pin SUB D
connector, a cable can enter or leave using either the right or left-hand connector.
Line termination At manufacture, the equivalent of the line terminator /A is built in to the processor
and, due to this, the processor forms a termination of the X bus. The extendable rack
located at the end of the chain therefore must always have a TSX TLY line
terminator, labeled /B on its unused 9-pin SUB D connector.
Note on the PCX By default, the PCX 57 processor is equipped to be mounted as the start of the X
57 processor bus, and thus, the line termination /A is built-in to it in the form of a removable
daughterboard.
Introduction Two cases can occur for PLC station rack addressing:
z PLC station built from a standard rack (See Standard racks, p. 71),
z PLC station built from extendable racks (See Extendable racks, p. 72).
Station built from The station is always limited to a single rack, thus the rack address is implicit and
a standard rack has a value of 0 (no microswitches).
Station built from For each station rack an address must be assigned. This address is coded using 4
extendable racks microswitches found on the rack.
Microswitches 1 to 3 are used to code the address of the rack on the X Bus X (0 to
7), microswitch 4 is used to code two racks (4, 6 or 8 positions) on the same address.
This latter functionality is managed by the PL7 Junior or PL7 Pro software version V
3.3 or above.
Rack addresses
Position of the
micro-switches
Assigning Address 0: this address is always assigned to the rack which supports:
addresses to z the TSX P57 processor physically,
different racks z the PCX 57 processor virtually.
This rack can be located in any position in the chain.
Addresses 1 to 7: they can be assigned in any order to all the other extendable
racks in the station.
Note: The rack address coding must be done before mounting the power supply
module.
CAUTION
Address conflict
If, through a mistake, two or more racks are unintentionally positioned
at the same address (other than address 0), then the racks concerned
as well as all their modules show a fault. Having correctly addressed the
racks with faulty addresses, it is necessary to switch off and then switch
on the racks concerned.
Failure to follow this precaution can result in injury or equipment
damage.
Illustration The following diagram shows the principle of addressing two racks at the same
address.
1 single rack
TSX RKY 12EX
on the same
address
2 single racks
TSX RKY 8EX
on the same
address
2 racks
TSX RKY 6EX
on the same
address
Micro-
switch 4 2 racks
TSX RKY 4EX
on the same
address
Module addresses
At a Glance For all standard and extendable racks, the module address is geographical and will
depend upon the position of the module on the rack. The address of each position
is indicated under each connector - the connector with address PS is always
dedicated to the rack power supply.
Module The address of a module will depend upon the position of microswitch 4:
addressing on z microswitch 4 in the ON position, the modules will have addresses (00 to x),
extendable racks according to the rack type,
z microswitch 4 in the OFF position, the modules will have addresses (08 to y),
according to the rack type. This functionality is only managed by the PL7 Junior
or PL7 Pro software version V 3.3 or above.
the following table shows the addresses in relation to the position of microswitch 4:
Position of microswitch 4 ON OFF
TSX RKY 4EX racks 00 to 02 08 to 10
TSX RKY 6EX racks 00 to 04 08 to 12
TSX RKY 8EX racks 00 to 06 08 to 14
TSX RKY 12EX racks 00 to 10 unusable
Illustration Diagram showing the module addresses on rack TSX RKY 8EX
Micro-switch 4 Module addresses
Note: The shaded addresses are only accessible using PL7 Junior or PL7 Pro
software version V 3.3 or above
Installation on a The rack with address 0 must have a power supply module and the processor
standard or module. Premium PLCs have two types of power supply (standard format or double
extendable rack format), the position of the processor will depend upon the type of power supply
with address 0 used.
and with a
Premium Using a standard format power supply module:
processor z the power supply module automatically occupies position PS,
z the single format processor module is installed in position 00 (preferred position)
or in position 01, if position 00 is unavailable.
Illustration
Illustration
Installation on an The PCX 57 processor, which is built in to the PC, occupies a virtual position on the
extendable rack rack with address 0. This virtual position should be unoccupied. Premium PLCs
with address 0 have two types of power supply (standard and double format), the unoccupied
and with an position will depend upon the type of power supply used.
Atrium
processor Using a standard format power supply module:
z the power supply module automatically occupies position PS,
z position 00, the virtual slot for the processor, must be unoccupied,
z the other modules are installed starting at position 01.
Illustration
Installation on an Each rack must be equipped with a power supply module, either standard or double
extendable rack format.
with address 1 to
7, regardless of Using a standard format power supply module:
processor type z the power supply module automatically occupies position PS,
z the other modules are installed starting from position 00.
Illustration
8
At a Glance
Aim of this The aim of this chapter is to show the different accessories which go with TSX RKY..
Chapter racks..
At a Glance These cables of predetermined length are used to chain TSX RKY..EX extendable
racks and to transport the different X Bus signals.
When a PCX 57 processor is used, they can also be used to connect the PC’s built-
in processor and the first rack in the station.
They are equipped at each end with male 9-pin SUB D connectors, which connect
to the female 9-pin SUB D connector on the extendable rack or the PCX 57
processor.
Important:
The cumulative length of all the cables used in a PLC station is limited to 100 meters.
CAUTION
Insertion and extraction
Different cable To suit different users, several cable lengths are available.
types available Summary table of different cable types
Product reference Lengths
TSX CBY 010K (II ≥ 02) 1 meter
TSX CBY 030K (II ≥ 02) 3 meters
TSX CBY 050K (II ≥ 02) 5 meters
TSX CBY 120K (II ≥ 02) 12 meters
TSX CBY 180K (II ≥ 02) 18 meters
TSX CBY 280K (II ≥ 02) 28 meters
TSX CBY 380K (II ≥ 02) 38 meters
TSX CBY 500K (II ≥ 02) 50 meters
TSX CBY 720K (II ≥ 02) 72 meters
TSX CBY 1000K (II ≥ 02) 100 meters
At a Glance For X Bus lengths less than 100 meters but different from those available as cables
with connectors, always use a TSX CBY 1000 cable.
This cable must have TSX CBY K9 connectors fitted at both ends by the user. The
assembly procedure is described in the instructions supplied with the cable and the
connectors.
For implementation of these cables the following elements are required:
z 1 TSX CBY 1000 cable,
z 1 set of two TSX CBY K9 9-pin connectors,
z 1 TSX CBY ACC10 kit.
1 TSX CBY 1000 This cable must include one 100-meter reel of cable and two testers to check the
cable, cable once the various connections have been made.
Illustration:
Reel Testers
1 set of two TSX For each connector this set must include:
CBY K9 9-pin z 1 connector body,
connectors z 1 set of contacts,
z 1 internal screening cap,
z 1 external screening cap,
z 1 ferrule,
z 1 plastic cover with 2 fixing screws.
Illustration:
Illustration:
Crimping tools
Introduction When extendable racks (See TSX RKY.. standard and extendable racks: functions,
p. 85) are used, the X Bus must be fitted with a line terminator at each end.
At a Glance A line terminator is made up of a 9-pin SUB D connector and a cover containing the
adaptation components. It is mounted on the 9-pin SUB D 9 connector belonging to
the extendable rack at the end of the line.
Illustration:
TSX TLYEX line terminations are sold in twos and marked A/ and /B. The bus must
be fitted with a terminator A/ at one end and a terminator /B at the other end in no
predefined (See Positioning of line terminators on a station using a Premium
processor, p. 106) order.
CAUTION
Insertion or extraction
Insertion or extraction of a line terminator must only be done with all the
station’s racks switched off.
Failure to follow this instruction can result in injury or equipment
damage.
Note: When a single extendable rack is used, a line terminator must always be
mounted on each of the rack’s 9-pin SUB D connectors.
At a Glance At manufacture, the equivalent of the line terminator /A is built in to the processor
and, due to this, the processor forms a termination of the X bus. The extendable rack
located at the end of the chain therefore must always have a TSX TLY EX line
terminator labeled /B fitted on its unused 9-pin SUB D connector.
Principle diagram:
PC PCX57
OK NOK
Special case.
When no devices are connected to the X Bus, the TSX TLYEX line terminator /B
must be installed on the X Bus connector of the PCX 57 processor.
Illustration:
OK NOK
PCX57
This cover is mounted and fixed on the rack like a module with a reduced depth.
Illustration
Labeling
Labeling of When the module is in place on the rack, it masks the address of the position, which
module is printed on the rack.
positions on the Due to this and in order to be able to identify the module’s position quickly, each rack
rack is delivered with a page of sticky labels which allow you to label the position of each
module.
This sticky label is stuck on the upper part of the module when it is in place on the
rack.
Label position
Page of labels:
PS 00 01 020 03 04 05 06
07 08 09 10 11 12 13 14
Rack labeling Each rack is delivered with a set of snap out labels so that for each rack you can
label:
z the address of the rack in the station,
z the network address of the station when the station is connected to a
communication network.
Therefore each rack has two slots where these addresses can be placed.
Illustration:
Network address
of the station
Rack address
in station
Summary Table This table shows the compatibility with the installed base in relation to old and new
references:
Configuration already in place with
rack(s)
Terminators YES YES YES YES
TSX TLYEX A/+/B
Details of incompatibilities:
1. Operation correct but incorrect detection of X bus break. Behavior of outputs not
guaranteed for bus break.
2. Correct operation for 50 instead of 100 meters. Correct detection of X bus break.
3. Incorrect bus adaptation, no guarantee of operation. The TLY and TLY A/B adapt
the signals in relation to 0V (wire in the X bus cable). The TLY EX A/B adapt the
signals in relation to the shielding.
4. Incorrect detection of duplicate address.
5. Operation correct but no detection of duplicate address.
6. Incorrect bus adaptation. TLY EX plugs required for correct operation when a
TSXRKY..EX. is used in the configuration.
Note: In a PLC station, the TSX TLY line terminator torque must be of the same
index.
•• corresponds to the product version.
9
At a Glance
Aim of this This Chapter deals with the ventilation module and its installation.
Chapter
At a Glance The ventilation modules which are installed above the TSX P57 PLC station racks
force air convection in order to make uniform the ambient temperature inside the
casing and thus eliminate the various hot spots which may exist.
Note: A temperature probe built into each module informs the user when the
ambient temperature has reached its maximum value.
ventilation module:
Use of ventilation The use of these modules is recommended in the following cases:
modules z Ambient temperature in the 25°C...60°C range: the life of the various
components of the Premium PLC is increased (MTBF increased by 25%).
z Ambient temperature in the 60°C...0.70°C range: the ambient temperature
being limited to 60°C without ventilation, forced ventilation makes it possible to
lower the temperature inside the modules by 10°C, which brings the internal
temperature of the modules back to the equivalent of 60°C at ambient
temperature.
Different module Three ventilation modules are available, adapted to the main supply networks:
types ventilation module with 24 VDC, 110 VAC or 220 VAC power supply.
According to the rack modularity (4, 6, 8 or 12 positions), 1, 2 or 3 ventilation
modules are to be fitted above each rack:
z 12-position racks TSX RKY 12/12EX: 3 ventilation modules,
z 8-position racks TSX RKY 8/8EX: 2 ventilation modules,
z 4 and 6-position racks TSX RKY 4EX/6/6EX: 1 ventilation module.
Illustration:
Table of labels This table gives you descriptions according to the labels:
Label Description
1 Terminal block for connecting:
z the module power supply,
z the supply for the temperature probe and the associated LED or pre-
actuator. Each terminal can receive one 1.5mm2 wire without a wire end
ferrule, or two 1mm2 wires with wire end ferrules.
2 Terminal for connecting the module to the ground.
3 Holes for fixing the module (M4 x 12 screws). If these modules are used with
Premium PLCs, the ventilation modules must be fixed on an AM1-ED ... 35
x 15 mounting rail .
4 Louvered slats which send air to the front.
Characteristics table:
Racks Number of positions a
TSX RKY 4EX 4 187.9 mm
TSX RKY 6/6EX 6 261.6 mm
TSX RKY 8/8EX 8 335.3 mm
TSX RKY 12/12EX 12 482.6 mm
General points The ventilation modules associated with Premium PLC’s must be mounted on 35mm
wide and 15mm deep mounting rails (type AM1-ED...) in order to compensate for the
thickness of the rack (See Mounting and fixing racks, p. 81).
Diagram:
Support
Mounting rail
35x15
Ventilation module
Premium PLC
6 position racks (TSX RKY 6/6EX) 8 position racks (TSX RKY 8/8EX)
12 position racks (TSX RKY 12/12EX) 4 position racks (TSX RKY 4EX)
a = 50 mm b = 30 mm
1 Installation or casing.
2 Trough or cable tray.
Note: If several ventilation modules of the same type are used, a common power
supply should be used for all ventilation modules.
Connecting the The temperature probe can be supplied either by direct or alternating current and
power supply to connected to a signaling LED, a PLC input, etc .
the temperature
probe Diagram:
Note: If several ventilation modules are used, the probe contacts are set up in
series.
Illustration:
Ventilation module 1
Ventilation module 2
Ventilation module 3
10
At a Glance
Aim of this The aim of this Chapter is to introduce the X-Bus extension module and its
Chapter installation.
General The Premium PLC X-Bus makes it possible to connect 8 racks with 12 positions
(TSX RKY 12EX) or 16 racks with 4, 6 or 8 positions (TSX RKY 4EX/6EX/8EX),
distributed along a maximum length of 100 meters.
If applications require greater distances between racks, the X-Bus extension module
(TSX REY 200) makes it possible to greatly increase this distance whilst maintaining
the characteristics and performance which are inherent in a PLC station which is
only made up of a single X-Bus segment without extension module.
Example of Illustration:
topology Remote X bus segment Main X bus segment
X bus
Remote X Bus
≤ 100m
TSX REY 200
Master ≤ 250m
slave
TSX REY 200
X
≤100m
≤ 100m
Introduction There are several different cases when installing an X Bus extension module:
z installation of a master module on the TSX P57 station,
z installation of a master module on the PCX 57 station,
z installation of a slave module.
Constraint:
the 00 position of rack with address 0 is prohibited to all modules including the
processor module, only a double format power supply is allowed to occupy this
position.
The table below indicates the various scenarios according to the format of the power
supply module and the processor:
Scenario Illustration
Rack with address 0 with single format power
supply module and processor:
z power supply module in position PS,
z processor must be in position 01,
z position 00 is always unoccupied,
z TSX REY 200 module in one of the available
positions in the rack.
Rack with address 0 with double format power
supply module and single format processor:
z power supply module in positions PS and 00,
z processor must be in position 01,
z TSX REY 200 module in one of the available
positions in the rack.
Scenario Illustration
Rack with address 0 with double format power
supply module and processor:
z power supply module in positions PS and 00,
z processor must be in positions 01 and 02,
z TSX REY 200 module in one of the available
positions in the rack.
Installing a As with a TSX P57 station, the master module must be installed:
master module z on the rack which supports the processor virtually (rack with address 0), this rack
on a being located on the main X Bus segment,
PCX 57 station z in any position on this rack apart from the position dedicated to the power supply
module and that which is virtually occupied by the processor.
Constraint:
The 00 position of the rack with address 0 is prohibited to all modules, only a double
format power supply module is allowed to occupy this position. The virtual position
of the processor (unoccupied position) must always be position 01.
The table below indicates the various scenarios according to the format of the power
supply module and the processor:
Scenario Illustration
Rack with address 0 with single format power
supply:
z power supply module in position PS,
z virtual position of the processor must be position 01
(position always unoccupied),
z position 00 is always unoccupied,
z TSX REY 200 module in one of the available
positions in the rack.
Rack with address 0 with double format power
supply module:
z power supply module in position PS,
z virtual position of the processor must be position 01
(position always unoccupied),
z TSX REY 200 module in one of the available
positions in the rack.
Installation of a The slave module can be installed on one of the racks of the bus extension segment
slave module and in any position on this rack apart from the one which is dedicated to the power
supply module.
The table below indicates the various scenarios according to the format of the power
supply module and the processor:
Scenario Illustration
Rack with address 0 with single format power
supply:
z power supply module in position PS,
z TSX REY 200 module in one of the available
positions in the rack.
Note: If 2 racks are declared at address 0, the master module must be located on
the rack supporting the "low" module addresses, as indicated in the figure below.
"Low" module addresses:
z addresses 0 to 6 on TSX RKY 8EX,
z addresses 0 to 4 on TSX RKY 6EX,
z addresses 0 to 2 on rack TSX RKY 4EX.
Micro-
switch 4
located on the rack
Note: If two racks are declared at address 0, the rack supporting the "high" address
modules cannot receive a slave extension module.
"High" address modules:
z addresses 8 to 14 on rack TSX RKY 8EX,
z addresses 8 to 12 on rack TSX RKY 6EX,
z addresses 8 to 10 on rack TSX RKY 4EX.
General points The figure below summarizes the maximum distances authorized for the different X-
Bus segments and X-Bus extensions:
z for each X-Bus segment (X1, X2 or X3): maximum length 100 meters,
z for each X-Bus extension (XD1 or XD2): maximum length 250 meters.
Illustration:
Main X-Bus segment (X1) Main X-Bus segment (X2)
≤ 100m
TSX REY 200
Slave
Processor
XD2 X-Bus
Remote X-Bus ≤ 250m
≤ 100m
Taking this into account, the maximum distance possible between the processor and
the remote modules is 350 meters.
This distance of 350 meters is only possible for single discrete input/output modules.
The following illustrations indicate the restrictions in relation to module type.
X-Bus
≤ 100m
X-Bus
≤ 100m
≤ 175 m
Communication
modules
CAUTION
Extension prohibited
Modules must be located on the main X-Bus segment.
Failure to follow this precaution can result in injury or equipment
damage.
Illustration:
Modules:
TSX SCY… communication
TSX ETY... network NO
TSX IBY…/TSX PBY field bus
Extension prohibited!
You must fit the cable with connectors at both ends. The procedure for mounting the
connectors on the cable is described in the instructions supplied with the set of
connectors TSX CBRT K5.
Connecting Illustration:
principles
Main X-Bus segment Remote X-Bus segment
Channel 0
Note: Each X-Bus segment must have a A/ and B/ line terminator (See Line
terminator TSX TLYEX, p. 105)at each end.
By signaling The TSX REY 200 module display panel, located on the front panel of the module,
LEDs is used for diagnostics on the extension system.
Legend:
On: on
Off: switched off
F: flashing
N/A: Not applicable
Legend:
On: on
Off: switched off
F: flashing
N/A: not determined
X Bus
Remote X Bus ≤ 250 m
≤ 100m
TSX REY 200
Master
TSX REY 200
Slave
X Bus
≤ 100m
≤ 100m
≤ 100m
Note: In every case, the length of X Bus extension segments is defined in relation
to the location of the processor. This maximum distance is 250 meters. In the
special case of the PCX 57 processor, when it is located in the PC, the extension
distance of the X Bus segments in relation to the rack with address 0, is equal to
250 meters minus the distance (X1) between the processor and rack with address
0. Main X Bus segment = (X1+X2) ≤ 100 meters.
General
CAUTION
Use of a module
All use of an X-Bus extension module (TSX REY 200) in an installation
makes management of the installation or the machine subject to all the
racks configured in the application being present.
In order to do this, an application check must be carried out to make
sure that all the application racks are present by testing the bit %MWxy
MOD 2 X6 (explicit exchanges) on at least one module on each rack.
This test allows the racks to be cleared of all incorrect declarations in
the rack addressing and, in particular, if two racks bear the same
address by mistake.
This test only comes into play after the installation has completely
restarted (switched on, installation modified, processor RESET,
configuration changed).
Failure to follow this precaution can result in injury or equipment
damage.
III
At a Glance
Subject of this The aim of this part is to describe the Premium TSX P57 processors and their
Part installation.
11
At a Glance
Aim of this The aim of this chapter is to introduce the TSX P57 processors.
Chapter
General introduction
Introduction A wide range of TSX P57 processors of different levels of performance and
specifications are available to meet your various requirements.
General points TSX P57 sequential processors can be integrated into TSX RKY... racks (See
Standard and extendable TSX RKY racks, p. 70).
Note: processors from families 20, 30 and 40 have built-in process control
functions.
Functions Premium TSX P57 processors manage a complete PLC station which is made up of:
z discrete input/output modules,
z analog input/output modules,
z application-specific modules (i.e. counting, axis control, step by step control,
communication, etc.),
which can be distributed over one or more racks connected to the X Bus.
The application is designed using PL7 Junior or PL7 Pro running Windows. This
offers:
z four programming languages: Grafcet, Ladder, Structured Text and List,
z a multitask software structure: Master, Fast, Event processing,
z a change function for programs being executed,
z etc.
Table of TSX P57 All processors in the TSX P57 range can be found in the following table.
processors
Type Physical Maximum Maximum Built-in master Built-in Ethernet link
format number of memory size FIPIO link
discrete I/Os
TSX P57 103 Single 512 96K16 - -
TSX P57 153 Single 512 96K16 X -
TSX P57 203 Double 1024 208K16 - -
TSX P57 253 Double 1024 224K16 X -
TSX P57 2623 Double 1024 208K16 - X
TSX P57 2823 Double 1024 224K16 X X
TSX P57 303/303A Double 1024 464K16 - -
TSX P57 353/353A Double 1024 480K16 X -
TSX P57 3623/3623A Double 1024 464K16 - X
TSX P57 453/453A Double 2048 688K16 X -
TSX P57 4823/4823A Double 2048 688K16 X X
Legend:
X available.
- : unavailable.
Illustration These diagrams label the different components of a TSX P57 processor module
(standard or double):
9
1
2
3
4
8
5
Real-time clock
At a Glance Each processor (TSX P57 or PCX 57) has a savable real-time clock which manages:
z the current date and time,
z the date and time of when the application last stopped.
The date and time are managed even when the processor is switched off, on
condition that:
z the TSX P57 processor is mounted on the rack with its power supply module in
place and is equipped with a back-up battery,
z the PCX 57 processor is equipped with a back-up battery.
Current date and the processor keeps the current date and time up to date in the system words
time %SW49 to %SW53. This data is coded in BCD.
System words Most significant byte Least significant byte
%SW49 00 Days of the week from 1 to 7
(1 for Monday and 7 for Sunday)
%SW50 Seconds (0 to 59) 00
%SW51 Hours (0 to 23) Minutes (0 to 59)
%SW52 Month (1 to 12) Days of the month (1 to 31)
%SW53 Century (0 to 99) Year (0 to 99)
Note: the processor does not automatically manage the change between winter
and summer time.
The date and The date and time of when the application last stopped are stored in BCD in the
time of when the system words %SW54 to %SW58.
application last
System words Most significant byte Least significant byte
stopped
%SW54 Seconds (0 to 59) 00
%SW55 Hours (0 to 23) Minutes (0 to 59)
%SW56 Month (1 to 12) Days of the month (1 to 31)
%SW57 Century (0 to 99) Year (0 to 99)
%SW58 Day of the week (from 1 to 7) Reason for the last application stop
12
At a Glance
Aim of this This Chapter deals with the installation of TSX P57 processor modules and the
Chapter PCMCIA extension card.
Introduction There are two scenarios for the positioning of a processor module on a rack:
z positioning a standard format processor module,
z positioning a double format processor module.
Positioning a A standard format processor module is always installed on the TSX RKY.. rack with
standard format address 0 and in position 00 or 01 according to whether the rack is equipped with a
processor standard or double format power supply module.
module
Rack with standard format power supply module: TSX PSY 2600/1610.
In this case, the processor module will be placed in position 00 (preferred position)
or position 01. If the latter, position 00 must be unoccupied.
Illustration
Rack with double format power supply module: TSX PSY 3610/5500/5520/
8500.
In this case, the processor will be placed in position 01, as the power supply module
occupies two positions (PS and 00).
Illustration
Positioning a A double format processor module is always installed on the TSX RKY.. rack with
double format address 0 and in positions 00 and 01 or 01 and 02 according to whether the rack is
processor equipped with a standard or double format power supply module.
module
Rack with standard format power supply module: TSX PSY 2600/1610.
In this case, the processor module will be installed in positions 00 and 01 (preferred
position) or in positions 01 and 02. If the latter, position 00 must be unoccupied.
Illustration
Rack with double format power supply module: TSX PSY 3610/5500/5520/
8500.
In this case, the processor will be placed in positions 01 and 02, as the power supply
module occupies two positions (PS and 00).
Illustration
Note: the rack on which the processor is installed always has address 0.
Introduction Mounting and removing processor modules is identical to mounting and removing
other modules apart from the fact that it must not be done when power is
switched on.
Note: when extracting/inserting modules with the power on, the terminal block or
HE10 connector must be disconnected. You must also take care to shut off the
sensor/preactuator supply if this is over 48V.
CAUTION
Install with power off
A processor module must always be mounted with the rack power
supply switched off.
Failure to follow this instruction can result in injury or equipment
damage.
Grounding Processor modules are grounded using metal plates at the rear of the module. When
modules the module is in place, these metal plates are in contact with the metal of the rack.
This ensures the link with the ground connection.
Illustration
Introduction A clip is needed to insert a PCMCIA memory card into its slot on the TSX P57
processor.
Position of the The following table describes the possible slots for the different types of PCMCIA
PCMCIA Cards in cards in the PLC processors:
the Processors
PCMCIA card Slot A (top) Slot B (bottom)
Standard: TSX Yes No
MRPP• and MFPP•
Application and Files: TSX MRPC• Yes No
and MCPC•
Data or Files: Yes Yes
TSX MRPF•
Mounting of the For TSX P57 1•3 to TSX P57 4•3 Premium PLCs, the memory cards (*) are
Card in the Clip mounted in the clip as follows:
Step Action Illustration
1 Place the end of the memory card
(opposite end to the connector)
between the arms of the clip.
The markers (in the form of a
triangle) on both the clip and the markers
card label must be facing same
way.
clip
(*) Note: this mounting procedure is only for TSX MRPF data or file-type cards. See
mounting procedure below.
Mounting of the For TSX P57 1•3 to TSX P57 4•3 Premium PLCs, the TSX MRP F• memory cards
TSX MRP F• Card inserted in slot B (bottom) are mounted in the extractor as follows:
in the Extractor
Step Action Illustration Illustration
Card with a PV ≤ 03 (1) Card with a PV > 03 (1)
1 Guide the memory card into the
extractor from an oblique angle,
placing the 2 pins on the card
into the 2 grooves on the
extractor.
pin pin
Click! Click!
Legend
(1) : the Product Version (PV) is shown on the label affixed to the PCMCIA card.
Mounting of the Carry out the following steps to install the memory card into the processor:
Memory Card in
Step Action
the PLC
1 Remove the protective cover by unlocking it and then pulling it forwards out of
the PLC.
2 Place the PCMCIA card fitted with its clip into the opened slot. Slide the whole
thing in until the card can go no further, then press the clip to connect the card.
Note: for TSX 57 1•3\2•3\3•3\4•3 processors, check that the mechanical locating
devices are positioned correctly:
z 1 edge on top,
z 2 edges at the bottom.
For TSX 57 5•3 processors, two guides ensure that the PCMCIA card is correctly
positioned in its slot.
Note: if the program contained in the PCMCIA memory card contains the RUN
AUTO option, the processor will automatically restart in RUN mode after the card
has been inserted.
General
CAUTION
Protective cover
The front panels of Premium PLC processors have removable covers
to prevent the accidental intrusion of objects which could damage the
connector. It is essential to leave the covers in place when no card is
inserted in these slots.
Failure to follow this instruction can result in injury or equipment
damage.
Inserting the cover or memory card with clip will cause the PLC to perform a cold
start.
CAUTION
RUN AUTO option
If the program contained in the PCMCIA memory card includes the
RUN AUTO option, the processor will automatically restart in RUN after
the card is inserted.
Failure to follow this instruction can result in injury or equipment
damage.
WARNING
Use of the write protection switch
It is essential that any modification of the position of the PCMCIA card
write protection switch be performed when the controller is powered
down.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
Product The following table shows the compatibility of the cards with the processors:
References for
Standard and
Flash Eprom
Extension
Memory Cards
References Type/Capacity Processor compatibility
TSX P57 1•3 TSX P57 2•3/2•23 TSX P57 3•3/3•3A/
PCX 57 2•3 3623/3623A
TSX P57 4•3/4•3A/
4823/4823A
PCX 57 353
TSX MRP P 128K (1) RAM/32K16 Yes Yes Yes
TSX MRP 032P
TSX MRP P 224K (1) RAM/64K16 Yes Yes Yes
TSX MRP 064P
TSX MRP C 448K (1) RAM/128K16 No Yes Yes
TSX MRP 0128P
TSX MRP C 001M (1) RAM/256K16 No Yes Yes
TSX MRP 0256P
TSX MRP C 003M (1) RAM/512K16 No Yes Yes
TSX MRP 0512P
TSX MFP P 128K (1) Flash Eprom/ Yes Yes Yes
TSX MFP 032P 32K16
TSX MFP P 224K (1) Flash Eprom/ Yes Yes Yes
TSX MFP 064P 64K16
TSX MFP P 384K (1) Flash Eprom/ No Yes Yes
TSX MFP 0128P 128K16
TSX MFP P 001M Flash Eprom/ No Yes Yes
256K16
Legend
TSX M•• • •••K new references to replace the old TSX M•P •••P type references.
Product The following table shows the compatibility of the cards with the processors:
References for
Backup
Extension
Memory Cards
References Type/Capacity Processor compatibility
TSX P57 103 TSX P57 2•3/2•23 TSX P57 3•3/3•3A/
PCX 57 2•3 3623/3623A
TSX P57 4•3/4•3A/
4823/4823A
PCX 57 353
TSX MFP B 096K (1) BACKUP/32K16 Yes Yes Yes
TSX MFP BAK032P
Legend
TSX MFP B 096K new references to replace the old TSX MFP BAK032P type references.
Application + In addition to the conventional application storage area (program + constants), these
Files Type memory cards also have a file area for archiving/restoring the data by program.
Memory Application examples:
Extension Cards
z automatic storage of application data and remote consultation by modem link,
z storage of manufacturing formulas.
WARNING
Use of the write protection switch
It is essential that any modification of the position of the PCMCIA card
write protection switch be performed when the controller is powered
down.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
Cards for Harsh Three cards have been developed especially for use in harsh environments. These
Environments are the TSX MRP C 001MC, TSX MRP C 003MC, TSX MRP C 007MC whose
characteristics are identical to the TSX MRP C 001M, TSX MRP C 003M,
TSX MRP C 007M.
Product The following table shows the compatibility of the cards with the processors:
References for
Application +
Files Extension
Memory Cards
References Technology Type/Capacity Processor compatibility
type Application File zone Symbol TSX P57 TSX P57 TSX P57 TSX P57
zone (RAM area 1•3 2•3/2•23 3•3/ 453/
type) (RAM 3•3A/ 453A/
type) 3623/ 4823/
3623A 4823A
TSX MRP C 448K (1) RAM 32K16 128K16 - yes yes yes yes
TSX MRP 232 P
TSX MRP C 384K (1) RAM 64K16 128K16 - yes yes yes yes
TSX MRP 264 P
TSX MRP C 768K (1) RAM 128K16 128K16 128K16 no yes yes yes
TSX MRP 2128 P
TSX MRP C 01M7 (1) RAM 256K16 640K16 128K16 no yes (2) yes yes
TSX MRP 3256 P (5x128K
16)
TSX MRP C 002M (1) RAM 384K16 640K16 - no yes (2) yes yes
TSX MRP 3384 P
TSX MRP C 003M (1) RAM 512K16 - 256K16 no yes (2) yes (3) yes
TSX MRP 0512 P
TSX MRPC 007M RAM 960K16 384K16 640K16 no no no yes (4)
TSX MCP C 224K (1) Flash 32K16 128K16 - yes yes yes yes
TSX MFP 232 P EPROM
TSX MCP C 224K (1) Flash Eprom 64K16 128K16 - yes yes yes yes
TSX MFP 264 P
Legend
TSX M•• C •••• new references to replace the old TSX M•P •••P type references.
(2) The usable application size is limited to 160K16 which conforms to the characteristics of this processor.
(3) The usable application size is limited to 384K16 which conforms to the characteristics of this processor, the size
of the symbol area is limited to 120K16.
(4) Reserved.
Note: For the TSX MRPC 007M, the 960K16 application area is divided into
2*480K16:
z 480K16 for the executable code,
z 480K16 for comments and graphic information.
File Type Memory Card: TSX MRP F 004M replaces card TSX MRP DS 2048 P
Compatibility The TSX MRP F 004M memory card must be used in one of the following
processors:
z TSX P57 203 and TSX P57 2623,
z TSX P57 253 and TSX P57 2823,
z TSX P57 303/303A and TSX P57 3623/3623A,
z TSX P57 353/353A,
z TSX P57 453/453A and TSX P57 4823/4823A.
Correspondence Table
At a Glance Depending on the type of memory card the characteristics are detailed:
z see Standard Memory Cards, p. 162,
z see Product References for Backup Extension Memory Cards, p. 164,
z see Application + Files Type Memory Cards, p. 165,
z see Standard Memory Cards, p. 162,
Table The following table gives the correspondence between the references of the old
cards and the new references, depending on the type of card:
Memory card type: Old reference New reference
Standard and Flash Eprom TSX MRP 032P TSX MRP P 128K
TSX MRP 064P TSX MRP P 224K
TSX MRP 0128P TSX MRP C 448K
TSX MRP 0256P TSX MRP C 001M
TSX MRP 0512P TSX MRP C 003M
TSX MFP 032P TSX MFP P 128K
TSX MFP 064P TSX MFP P 224K
TSX MFP 0128P TSX MFP P 384K
Backup TSX MFP BAK032P TSX MFP B 096K
Application + Files TSX MRP 232 P TSX MRP C 448K
TSX MRP 264 P TSX MRP C 384K
TSX MRP 2128 P TSX MRP C 768K
TSX MRP 3256 P TSX MRP C 01M7
TSX MRP 3384 P TSX MRP C 002M
TSX MRP 0512 P TSX MRP C 003M
TSX MRPC 007M TSX MRPC 007M
TSX MFP 232 P TSX MCP C 224K
TSX MFP 264 P TSX MCP C 224K
File TSX MRP DS 2048 P TSX MRP F 004M
13
At a Glance
Aim of this This Chapter deals with diagnostics for TSX P57 processors.
Chapter
Viewing
At a Glance There are five display LEDs on the front panel of the processor for a quick diagnostic
of the status of the PLC controller.
Illustration
LED on.
LED off.
inactive link.
inactive link.
Note:
z the FIP LED is only present on TSX P57 •53 and TSX P57 •823 processors.
Important
CAUTION
Replacing a processor
If the TSX P57 processor is being replaced by another processor which
is not blank (the processor has already been programmed and contains
an application), the power for all the PLC station’s control units must be
switched off.
Before restoring power to the control units, check that the processor
contains the required application.
Failure to follow this instruction can result in injury or equipment
damage.
At a Glance This battery, which is in the TSX PSY … power supply module (See Supply
modules: description, p. 328), ensures that the internal RAM memory of the
processor and the real-time clock are saved in case of a voltage power outage. It is
delivered in the same packaging as the power supply module and must be installed
by the user.
Illustration
Changing the The battery can be changed every year as a preventative measure or when the BAT
battery LED is lit.
To do this, use the same procedure as for installation, and carry out the following
steps:
Step Action
1 Open the access flap for the battery.
2 Remove the defective battery from its slot.
3 Put the new battery into place.
4 Close and lock the access flap.
Illustration
If there is a power outage while the battery is being changed, the processor ensures
the RAM memory is saved, as it has its own offline independent save function.
Note: so as not to forget to change the battery, you are advised to note the date of
the next change in the space provided on the inside of the flap.
Assuming that the processor was switched on previously, the guaranteed time
varies in the following way:
Ambient temperature when switching off 20°C 30°C 40°C 50°C
Backup time 2h 45mn 20mn 8mn
Changing the Battery of a RAM Memory PCMCIA Card on the TSX P57
Introduction Some RAM memory PCMCIA cards (TSX MRP etc.) have a single battery
(reference TSX BAT M01) which needs to be changed. The various memory card
references are found in a summary table (See Correspondence Table, p. 169).
Illustration
Write protection
Lock
Battery slot
6
Labels
Note: During operation, the processor’s ERR LED flashes if the PCMCIA card
battery is defective.
Introduction The TSX MRP DS 2048 P memory extension card must have a battery (product ref.
TSX BAT M01) in order to ensure data is saved.
3 Hold the PCMCIA card so you can access the battery slot. This is at the end of
the card without the connector.
4 Unlock the battery flap located at the edge of the card. To do this press the lock
towards the top of the card (the opposite direction to the write protection micro-
switch.
Step Action
5 Take off the battery flap. To do this, slightly rotate the socket as shown in the
diagram. Take the card out of its slot.
Battery slot
Lock
Write protection
Labels
Note: For the new card reference TSX MRP F 004M, (replacing card TSX MRP DS
2048 P),
z with PV lower than or equal to 03, see(Installation Manual Volume 1),
z with PV greater than or equal to 03, seeChanging the Batteries of a PCMCIA
Memory Card, p. 183,
Preventive This method is valid for all memory card versions and for all the PLCs using these
Method cards (i.e. Premium, Atrium). Change both batteries following the indications related
to the PCMCIA PV, how the PLC is used and the battery life (See Batterie Lifetimes
for the PCMCIA Memory Card, p. 187). The two batteries may be changed in any
order: the application will be saved by the memory card. Battery changing
procedure: see the instructions provided with the memory cards.
Note:
z Batteries should not be removed from their positions simultaneously. One
battery backs up the data and applications, whilst the other is being replaced.
z The memory card should never remain more than 24 hours without a main
battery in working state.
z To economize, auxiliary batteries may only be changed every 1.5 years which
is the standard battery life. In this case, for some memory cards, one must
remember to only change the auxiliary battery once every 3 times.
z The battery lives shown above are calculated for worst case scenarios: ambient
operating temperature around 60°C, and PLC only powered up 21% of total
annual time (i.e. 8 hours a day, with 30 days maintenance per year).
Predictive This maintenance method uses the %S67 and %S75 bits and the ERR diode on the
method Premium interface. This method implies that the auxiliary battery is changed every
18 months. It can only be implemented:
z on low or medium capacity PV06 RAM memory cards (see product version on the
card label), having the following storage capacity when used with a PL7 ≤ 768K
(TSX MRP P •••• K, TSX MCP C •••• K, TSX MRP C 448 K, TSX MRP C 768 K),
z providing the card is installed in the top PCMCIA slot on all the Premium
processors.
z providing the card is installed in the bottom PCMCIA slot on Premium
TSX P57 4•• and Premium TSX P57 5•• processors.
%S67 system bit (top slot card) or %S75 system bit (bottom slot card) on 1 or
flashing processor interface ERR diode indicate main battery low. The main battery
must be replaced within 8 days, as indicated in the instructions provided with the
memory cards.
Note:
If the PLC is to remain switched off or the memory card is removed for more than
8 days, and the main battery has exceeded its standard life, save the application
under PL7.
Procedure for the The following table shows the procedure for changing the main battery:
TSX BAT M02
Step Action Illustration
Battery:
1 Toggle the changeover
lever toward the
TSX BAT M03 (AUX)
battery in order to remove
the drawer of the main
battery.
Procedure for the The following table shows the procedure for changing the auxiliary battery:
TSX BAT M03
Step Action Illustration
Battery:
1 Toggle the changeover
lever toward the
TSX BAT M02 (MAIN)
battery in order to remove
the drawer of the battery.
Purpose The purpose of this document is to give detailed information about the lifetime of
batteries inside all PCMCIA memory cards. The estimation of these lifetimes are
based on data from component manufacturers.
Main Battery The table below presents the lifetime of main battery TSX BAT M01(PV1/2/3) for
Lifetime of PV1/2/ PCMCIA memory cards:
3 PCMCIA (in
Years)
PV1/2/3 For a 25°C PLC ambient temperature
100% powered up 92% PU (30d maint.) 66% PU (WE. 30d 33% PU (12h.WE. 30d
maint.) maint.)
Typical Min Typical Min Typical Min Typical Min
TSX MCP C 224K 7.10 7.10 6.71 5.58 5.77 3.36 4.82 2.20
TSX MCP C 512K 7.10 7.10 6.71 5.65 5.77 3.46 4.82 2.28
TSX MCP C 002M 7.10 7.10 6.29 3.82 4.66 1.57 3.45 0.88
TSX MRP P128K 7.10 7.10 6.71 5.58 5.77 3.36 4.82 2.20
TSX MRP P224K 7.10 7.10 6.71 5.65 5.77 3.46 4.82 2.28
TSX MRP P384K 7.10 7.10 6.71 4.99 5.77 2.60 4.82 1.59
TSX MRP C448K 7.10 7.10 6.29 4.65 4.66 2.24 3.45 1.33
TSX MRP C768K 7.10 7.10 6.29 4.65 4.66 2.24 3.45 1.33
TSX MRP C001M 7.10 7.10 5.91 3.95 3.91 1.66 2.68 0.94
TSX MRP C01M7 7.10 7.10 5.58 3.43 3.36 1.32 2.20 0.72
TSX MRP C002M 7.10 7.10 5.91 3.34 3.91 1.26 2.68 0.69
TSX MRP C003M 7.10 7.10 5.58 2.60 3.36 0.87 2.20 0.47
TSX MRP C007M 7.10 7.10 4.56 1.59 2.16 0.46 1.27 0.24
TSX MRP F004M 7.10 7.10 5.58 2.60 3.36 0.87 2.20 0.47
TSX MRP F008M 7.10 7.10 4.56 1.59 2.16 0.46 1.27 0.24
Main Battery The table below presents the lifetime of main battery TSX BAT M02 (PV4/5) for
Lifetime of PV4/5 PCMCIA memory cards:
PCMCIA (in
Years)
PV4/5 For a 25°C PLC ambient temperature
100% powered up 92% PU (30d maint.) 66% PU (WE. 30d 33% PU (12h.WE. 30d
maint.) maint.)
Typical Min Typical Min Typical Min Typical Min
TSX MCP C 224K 7.22 7.22 7.15 6.27 7.02 4.48 6.76 3.23
TSX MCP C 512K 7.22 7.22 7.15 6.33 7.02 4.59 6.76 3.35
TSX MCP C 002M 7.22 7.22 6.83 4.69 5.90 2.25 4.96 1.33
TSX MRP P128K 7.22 7.22 7.15 6.27 7.02 4.48 6.76 3.23
TSX MRP P224K 7.22 7.22 7.15 6.33 7.02 4.59 6.76 3.35
TSX MRP P384K 7.22 7.22 7.15 5.77 7.02 3.57 6.76 2.36
TSX MRP C448K 7.22 7.22 6.83 5.47 5.90 3.12 4.96 1.99
TSX MRP C768K 7.22 7.22 6.83 5.47 5.90 3.12 4.96 1.99
TSX MRP C001M 7.22 7.22 6.54 4.82 5.09 2.37 3.91 1.41
TSX MRP C01M7 7.22 7.22 6.27 4.30 4.48 1.91 3.23 1.10
TSX MRP C002M 7.22 7.22 6.54 4.20 5.09 1.83 3.91 1.04
TSX MRP C003M 7.22 7.22 6.27 3.41 4.48 1.29 3.23 0.71
TSX MRP C007M 7.22 7.22 5.39 2.21 3.02 0.70 1.91 0.37
TSX MRP F004M 7.22 7.22 6.27 3.41 4.48 1.29 3.23 0.71
TSX MRP F008M 7.22 7.22 5.39 2.21 3.02 0.70 1.91 0.37
Main Battery The table below presents the lifetime of main battery TSX BAT M02 (PV6) for
Lifetime of PV6 PCMCIA memory cards:
PCMCIA (in
Years)
PV6 For a 25°C PLC ambient temperature
100% powered up 92% PU (30d maint. 66% PU (WE. 30d 33% PU (12h.WE. 30d
maint. maint.
Typical Min Typical Min Typical Min Typical Min
TSX MCP C 224K 7.2 7.2 7.2 6.3 7.0 4.5 6.8 3.2
TSX MCP C 512K 7.2 7.2 7.2 6.5 7.0 5.1 6.8 3.9
TSX MCP C 002M 7.2 7.2 6.8 5.8 5.9 3.6 5.0 2.4
TSX MRP P128K 7.2 7.2 7.2 6.3 7.0 4.5 6.8 3.2
TSX MRP P224K 7.2 7.2 7.2 6.5 7.0 5.1 6.8 3.9
TSX MRP P384K 7.2 7.2 7.2 6.5 7.0 5.1 6.8 3.9
TSX MRP C448K 7.2 7.2 6.8 5.8 5.9 3.6 5.0 2.4
TSX MRP C768K 7.2 7.2 6.8 5.8 5.9 3.6 5.0 2.4
TSX MRP C001M 7.2 7.2 6.5 5.2 5.1 2.8 3.9 1.7
TSX MRP C01M7 7.2 7.2 6.3 4.7 4.5 2.3 3.2 1.4
TSX MRP C002M 7.2 7.2 6.5 5.2 5.1 2.8 3.9 1.7
TSX MRP C003M 7.2 7.2 6.3 4.7 4.5 2.3 3.2 1.4
TSX MRP C007M 7.2 7.2 5.4 3.5 3.0 1.3 1.9 0.7
TSX MRP F004M 7.2 7.2 6.3 4.7 4.5 2.3 3.2 1.4
TSX MRP F008M 7.2 7.2 5.4 3.5 3.0 1.3 1.9 0.7
Minimum In a powered down PLC, the minimum lifetime of the main battery is 6 months, in all
Lifetime of the PV6 PCMCIAs.
Main Battery, in a
Powered Down
PLC
Auxiliary Battery The auxiliary battery TSX BATM 03 is included in the PCMCIA product. Whatever
Lifetime the usage cases and ambient temperature, the lifetime of the auxiliary battery is:
z 5 years in PV1/2/3
z 1.7 years in PV4/5
z 5 years in PV6
General All processors have a RESET button on their front panel, which when pressed,
causes a cold start of the PLC, in RUN or in STOP mode (starting in RUN or in STOP
mode is defined at configuration), on the application contained in the memory card
(or in the internal RAM)…
RESET following As soon as a processor fault appears, the alarm relay on rack 0 (with TSX 57
a processor fault processor) is deactivated (open contact) and the module outputs switch to fallback
position or are maintained in the current state depending on the selection made in
configuration. Pressing the RESET button causes the PLC, forced into STOP, to
cold start.
Note: when the RESET button is pressed, and during the PLC cold start, the
terminal link is deactivated.
General The state LEDs situated on the processor enable the user to be informed about the
operating mode of the PLC but on possible errors.
Errors detected by the PLC concerned:
z circuits constituting the PLC and/or its modules: internal errors,
z the process controlled by the PLC or the cabling of the process: external errors,
z functioning of the application executed by the PLC: internal or external errors.
Error detection Detecting errors is carried out during start-up (autotest) or during functioning (this is
the case for most hardware errors), during exchanges with modules or during the
execution of a program instruction.
Certain "serious" errors require the PLC to be restarted, others are controlled by the
user who decides on the behavior to adopt according to the desired level of
application function.
There are three types of error:
z non blocking,
z blocking,
z processor or system error.
General This concerns an anomaly, provoked by an input/output error on the X bus, on the
FIPIO bus or by the execution of an instruction. It can be processed by the user
program and does not change the PLC state.
Non blocking The identification of a non blocking error linked to the inputs/outputs is signaled by:
errors linked to z the I/O state LED of the processor is lit,
inputs/outputs z the I/O state LEDs of the faulty modules are lit, (on X bus and FIPIO bus),
z the bits and error words associated to the channel:
z Inputs/Outputs on X bus:
%Ixy.i.ERR bit = 1 indicates a faulty channel (implicit exchanges),
%Mwxy.i.2 words indicate the type of channel error (explicit exchanges),
z Inputs/Outputs on FIPIO bus:
%I\p.2.c\m.v.ERR bit = 1 indicates a faulty channel (implicit exchanges),
%MW\p.2.c\m.v.2 words indicate the type of channel errors (explicit
exchanges),
z bits and error words associated with the module:
z Module on X bus:
%Ixy.MOD.ERR bit = 1 indicates a faulty channel (implicit exchanges),
%MWxy.MOD.2 words indicate the type of channel error (explicit exchanges),
z Module on FIPIO bus:
%I\p.2.c\0.MOD.ERR bit = 1 indicates a faulty channel (implicit exchanges),
%MW\p.2.c\0.MOD.2 words indicate the type of channel error (explicit
exchanges),
z system bits:
%S10: I/O error (on X bus or FIPIO bus),
%S16: I/O error (on X bus and FIPIO bus) in the task in progress,
%S40 à %S47: I/O error in racks at addresses 0 to 7 on the X bus.
Diagnostics table:
Status LED System Errors
RUN ERR I/O bits
Legend:
To: Lit LED,
I: State not determined.
Non blocking The indication of a non blocking error linked to program execution is signaled by
errors linked to setting to state 1 of one or several system bits %S15, %S18, %S20.
program The test and setting to state 0 of the system bits are controlled by the user.
execution
Diagnostics table:
Status LED System Errors
RUN ERR I/O bits
Legend:
To: Lit LED,
I: State not determined.
Note: the program diagnostics function, accessible through the PL7 Pro software,
enables certain non blocking errors linked to the program execution, to be turned
into blocking errors. The nature of the error is indicated in the system word %SW
125.
Blocking errors
General These errors, provoked by the application program, disable its execution but do not
cause system errors. On such an error, the application stops immediately and goes
to HALT state (the tasks are all stopped in their current instruction).
The application is thus in a preliminary state: the data has its preliminary values, the
tasks are stopped at the end of the cycle, the input image is updated and the outputs
are commissioned in fallback position, the RUN command enables application
restart.
The indication of a blocking error is signaled by the state LEDs (ERR and RUN)
flashing and according to the nature of the error by the setting to 1 of one or several
of the system bits %S11 and %S26. The nature of the error is indicated in the system
word %SW 125.
Diagnostics table:
State LEDs System Bits Errors
RUN ERR I/O
C C i %S11=1 Watchdog overrun
C C i %S26=1 Overrun of the grafcet activity table
Step, Grafcet not resolved
C C i Executing the HALT instruction
C C i Executing a non resolved JUMP
Legend:
C: blinking
i: not determined
Diagnostics table:
State LEDs System word Errors
RUN ERR I/O %SW124
Legend:
To: on
C: blinking
E: not determined
Diagnostics of When the PLC has stopped in error, it is no longer able to communicate with a
processor diagnostics device. The information relating to the errors is only accessible after a
errors: cold restart (see system word %SW124). In general, the information is not used by
the user, only the information H’80’ and H’81’ can be used to diagnose a cabling
error on the X bus.
14
General characteristics of TSX P 57 103 processors
TSX P 57 103 The following table gives the general characteristics of the TSX P 57 103 processor.
processors
Reference TSX P 57 103
fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
15
General characteristics of TSX P57 153 processors
TSX P 57 153 The following table gives the general characteristics of the TSX P 57 153 processor.
processors
Reference TSX P 57 153
fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog
channels can be accumulated
16
General characteristics of TSX P57 203 processors
TSX P 57 203 The following table gives the general characteristics of the TSX P 57 203 processor.
processors
Reference TSX P 57 203
fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog
channels can be accumulated
17
General characteristics of TSX P57 253 processors
TSX P57 253 The following table gives the general characteristics of the TSX P 57 253 processor.
processor
Reference TSX P57 253
fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog
channels can be accumulated
18
TSX P57 2623 Processors: General Characteristics
TSX P 57 2623 The following table gives the general characteristics of the TSX P 57 2623
Processors processor.
Reference TSX P 57 2623
(1) Fixed I/O profile: the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
(2) One of which is occupied by the TSX ETY PORT of the CPU.
19
TSX P57 2823 Processors: General Characteristics
TSX P57 2823 The following table gives the general characteristics of the TSX P 57 2823
Processor processor.
Reference TSX P57 2823
(1) Fixed I/O profile: the number of discrete I/Os, and application-specific and analog
channels can be accumulated
(2) One of which is occupied by the TSX ETY PORT of the CPU.
20
General characteristics of TSX P57 303 processors
TSX P57 303 The following table gives the general characteristics of the TSX P 57 303 processor.
processor
Reference TSX P57 303
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
fixed I/O profile (2): the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
21
General characteristics of TSX P57 303A processors
TSX P57 303A The following table gives the general characteristics of the TSX P 57 303A
processor processor.
Reference TSX P57 303A
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
fixed I/O profile (2): the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
22
General characteristics of TSX P57 353 processors
TSX P57 353 The following table gives the general characteristics of the TSX P 57 353 processor.
processor
Reference TSX P57 353
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
fixed I/O profile (2): the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
23
General characteristics of TSX P57 353A processors
TSX P57 353A The following table gives the general characteristics of the TSX P 57 353A
processor processor.
Reference TSX P57 353A
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
fixed I/O profile (2): the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
24
TSX P57 3623 Processors: General Characteristics
TSX P57 3623 The following table gives the general characteristics of the TSX P 57 3623
Processor processor.
Reference TSX P57 3623
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
(2) Fixed I/O profile: the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
(3) One of which is occupied by the TSX ETY PORT of the CPU.
25
TSX P57 3623A Processors: General Characteristics
TSX P57 3623A The following table gives the general characteristics of the TSX P 57 3623A
Processor processor.
Reference TSX P57 3623A
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
(2) Fixed I/O profile: the number of discrete I/Os, and application-specific and analog
channels can be accumulated.
(3) One of which is occupied by the TSX ETY PORT of the CPU.
26
General characteristics of TSX P57 453 processors
TSX P57 453 The following table gives the general characteristics of the TSX P 57 453 processor.
processor
Reference TSX P57 453
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
Flexible I/O profile (2): the maximum number of discrete I/Os, and application-
specific and analog channels cannot be accumulated. These area distributed
according to a formula.
27
General characteristics of TSX P57 453A processors
TSX P57 453A The following table gives the general characteristics of the TSX P 57 453A
processor processor.
Reference TSX P57 453A
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
Flexible I/O profile (2): the maximum number of discrete I/Os, and application-
specific and analog channels cannot be accumulated. These area distributed
according to a formula.
28
TSX P57 4823 Processors: General Characteristics
TSX P57 4823 The following table gives the general characteristics of the TSX P 57 4823
Processor processor.
Reference TSX P57 4823
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
(2) Flexible I/O profile: the maximum number of discrete I/Os, and application-
specific and analog channels cannot be accumulated. These area distributed
according to a formula.
(3) One of which is occupied by the TSX ETY PORT of the CPU.
29
TSX P57 4823A Processors: General Characteristics
TSX P57 4823A The following table gives the general characteristics of the TSX P 57 4823A
Processor processor.
Reference TSX P57 4823A
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
(2) Flexible I/O profile: the maximum number of discrete I/Os, and application-
specific and analog channels cannot be accumulated. These area distributed
according to a formula.
(3) One of which is occupied by the TSX ETY PORT of the CPU.
Aim of this The aim of this Chapter is to introduce the characteristics of devices that can be
Chapter used when installing a TSX 57 station.
General As the processors can be fitted with certain devices which do not have their own
power supply, the consumption of these devices must be taken into account when
establishing a global breakdown of power consumption.
z Devices without their own power supply which can be connected to the terminal
port:
z adjustment terminal: T FTX 117 ADJUST,
z TSX P ACC01 unit for connecting to the UNI-TELWAY bus.
z Devices without their own power supply which can be built into the processor:
z PCMCIA communication cards TSX FPP 10/20,
z PCMCIA communication card TSX SCP 111/112/114,
z PCMCIA communication card TSX MBP 100,
z PCMCIA modem card TSX MDM 10.
Power This table shows the consumption of the TSX PSY supply module at 5VDC:
consumption
Processor + PCMCIA Typical consumption Maximum consumption
memory card
TSX P57 103 440 mA 610 mA
TSX P57 153 530 mA 740 mA
TSX P57 203 750 mA 1050 mA
TSX P57 253 820 mA 1140 mA
TSX P57 2623 1110 mA 1450 mA
TSX P57 2823 1180 mA 1540 mA
TSX P57 303/303A 1000 mA 1400 mA
TSX P57 353/353A 1060 mA 1480 mA
TSX P57 3623/3623A 1360 mA 1800 mA
TSX P57 453/453A 1080 mA 1510 mA
TSX P57 4823/4823A 1440 mA 1910 mA
Dissipated This table states the dissipated power for TSX P57 processors:
power
Processor + PCMCIA typical maximum
memory card
TSX P57 103 2.2 W 3.1 W
TSX P57 153 2.7 W 3.7 W
TSX P57 203 3.8 W 5.3 W
TSX P57 253 4.1 W 5.7 W
TSX P57 2623 5.6 W 7.4 W
TSX P57 2823 5.9 W 7.8 W
TSX P57 303/303A 5.0 W 7.0 W
TSX P57 353/353A 5.3 W 7.4 W
TSX P57 3623/3623A 6.8 W 9.1 W
TSX P57 453/453A 5.4 W 7.6 W
TSX P57 4823/4823A 7.2 W 9.7 W
Tables of Consumption:
consumption
Consumption at 5VDC from the power supply module TSX PSY … Typical Maximum
and dissipated
power Devices without their own power supply which TFTX 117 310mA 340 mA
can be connected to the terminal port (TER) ADJUST
TSXPACC01 150mA 250 mA
PCMCIA communication card which can be TSXFPP10 330 mA 360 mA
built into the processor TSXFPP20 330 mA 360 mA
TSXSCP111 140 mA 300 mA
TSXSCP112 120 mA 300 mA
TSXSCP114 150 mA 300 mA
TSXMBP100 220 mA 310 mA
TSXMDM10 195 mA -
Dissipated power:
Dissipated power Typical Maximum
Devices without their own power TFTX 117 ADJUST 1.5 W 1.7 W
supply which can be connected to TSXPACC01 0.5 W 1.25 W
the terminal port (TER)
PCMCIA communication card which TSXFPP10 1.65 W 1.8 W
can be built into the processor TSXFPP20 1.65 W 1.8 W
TSXSCP111 0.7 W 1.5 W
TSXSCP112 0.6 W 1.5 W
TSXSCP114 0.75 W 1.5 W
TSXMBP100 1.1 W 1.55 W
TSXMDM10 0.975 W -
(*) Although these channels are application-specific, they should not be taken into
account when calculating the maximum number of application-specific channels
which can be supported by the processor.
Note: only channels configured from PL7 Junior or PL7 Pro software can be
counted.
31
At a Glance
Explanatory The following diagram describes the MAST task cycle time:
diagram
Program processing
I.P I.P
on input on output
cycle time
IP = internal
Definition of Ppt Ppt = Application code execution time (Apcet) + Grafcet overhead time (OtG7).
program
processing time
Application code Apcet = sum of the times of each instruction carried out by the application program
execution time in each cycle.
(Apcet)
The execution time of each instruction as well as the type of application which was
used to check them are given in the PL7 reference manual.
The table opposite gives the execution times in milliseconds (ms) for a 1K instruction
(1024 instructions):
Processors Application code execution time Apcet (1)
Internal RAM PCMCIA card
100% Boolean 65% Boolean + 100% Boolean 65% Boolean +
35% numerical 35% numerical
TSX P57 103 0.66 ms 0.95 ms 0.83 ms 1.18 ms
TSX P57 153
TSX P57 2•3/2•23 0.21 ms 0.28 ms 0.27 ms 0.40 ms
TPCX 57 203
TSX P57 3•3/3•3A/3623/3623A 0.15 ms 0.21 ms 0.22 ms 0.32 ms
TPCX 57 353
TSX P57 453/453A/4823/4823A 0.07 ms 0.11 ms 0.07 ms 0.11 ms
Grafcet overhead OtG7 = GFT + (AST x number of simultaneous active steps) + (OTT x number of
time (OtG7) transitions occurring simultaneously).
Summary table:
Processors GFT AST OTT
TSX P57 103 0.243 ms 0.088 ms 0.359 ms
TSX P57 153
TSX P57 2•3/2•23 0.075 ms 0.029 ms 0.109 ms
TPCX 57 203
TSX P57 3•3/3•3A/3623/3623A 0.047 ms/ 0.054 0.018 ms/ 0.021 0.069 ms/ 0.079
TPCX 57,353 ms (A) ms (A) ms (A)
TSX P57 453/453A//4823/4823A 0.039 ms/ 0.045 0.015 ms/ 0.017 0.058 ms/ 0.067
ms (A) ms (A) ms (A)
Definition of
input and output
MAST task overhead system time (Mtost)
internal
processing time +
(Ipt) max [receiving communication system Time (rcomT); management
time on input of implicit I/O %I (mTi%I)]
Ipt =
+
max [sending communication system Time (scomT); management time
on output of implicit I/O %Q (Mto%Q)]
Management time on input (IN) and on output (OUT) for each module:
Type of module Management time
On input (IN) On output (OUT) Total (IN+OUT)
8 channel discrete inputs 27 μs - 27 μs
16 channel discrete inputs 27 μs - 27 μs
(all modules except TSX DEY 16FK)
32 channel discrete inputs 48 μs - 48 μs
64 channel discrete inputs 96 μs - 96 μs
Fast discrete inputs (8 channels used) 29 μs 16 μs 45 μs
(module TSX DEY 16FK/TSXDMY 28FK)
Fast discrete inputs (16 channels used) 37 μs 22 μs 59 μs
(module TSX DEY 16FK/TSXDMY 28FK/28RFK)
8 channel discrete outputs 26 μs 15 μs 41 μs
16 channel discrete outputs 33 μs 20 μs 53 μs
32 channel discrete outputs 47 μs 30 μs 77 μs
64 channel discrete outputs 94 μs 60 μs 154 μs
Analog inputs (in groups of 4 channels) 84 μs - 84 μs
Analog outputs (4 channels) 59 μs 59 μs 118 μs
Counting (TSX CTY 2A/4A), by channel 55 μs 20 μs 75 μs
Counting (TSX CTY 2C), by channel 65 μs 21 μs 86 μs
Step by step control (TSX CFY ..), by channel 75 μs 20 μs 95 μs
Axis control (TSX CAY ..), by channel 85 μs 22 μs 107 μs
Note: discrete input/output module times are given in the theory that all channels
of the module are assigned to the same task.
Example: using module TSX DEY 32 D2 K
z if the 32 channels are assigned to the same task, use the "32 channel discrete
inputs" time,
z if only 16 channels are assigned to the same task, use the "16 channel discrete
inputs" time and not the "32 channel discrete input" time divided by 2.
Communication Communication (except telegram) is made during MAST task "Internal Processing"
system time phases:
z on input for receiving messages (rcomT),
z on outputs for sending messages (scomT).
This time only occurs in the cycles where there is a new message to be managed.
Examples of Terminal connected to PL7 Junior software and open animation table:
communication
Processors Average time per cycle Maximum time per cycle
system time
TSX P57 103 / 153 2.5 ms 3.5 ms
TSX P57 2•3/2•23 2 ms 2.5 ms
TPCX 57 203
TSX P57 3•3/3•3A/3623/3623A 1.3 ms/ 1,4 ms (A) 1.8 ms/ 2,1 ms (A)
TPCX 57 353
TSX P57 453/453A/4823/4823A 1 ms/ 1,1 ms (A) 1.5 ms/ 1,7 ms (A)
Note: these times cannot be combined in the same cycle. Transmission occurs in
the same cycle as instruction execution as long as communication traffic remains
light, but the reply is not received in the same cycle.
Example of the calculation of cycle times of a MAST task under the following
conditions
Definition FAST cycle time = Program processing time (Ppt) + input and output internal
processing time (Ipt).
Definition of Ppt Ppt = Application code execution time relative to the FAST (Apcet).
program Application code execution time:
processing time
see Application code execution time (Apcet), p. 256.
Definition of Ipt = FAST task overhead system time + input and output management time for
input and output implicit I/O %I and %Q.
internal
processing time
(Ipt) FAST task overhead system time (FosT)
Processors FAST task overhead system time
TSX P57 103 0.8 ms
PCX 57 203
TSX P57 2•3/2•23 0.6 ms / 0.69 ms (A)
TSX P57 3•3/3•3A/3623/3623A
PCX 57 353
TSX P57 453/453A/4823/4823A 0.2 ms / 0.23 ms (A)
Input and output management time for implicit I/O %I and %Q: see MAST task cycle
time: input/output internal processing, p. 258.
General Definition: time between an edge on an event input and the corresponding edge on
an output positioned by the program in the event task.
Example: program with 100 Boolean instructions and input module TSX DEY 16 FK
Processors Response time
Module TSX DSY 08T22 Module TSX DSY 32T2K
Minimum Typical Maximum Minimum Typical Maximum
TSX P57 103 1.2 ms 1.3 ms 2.8 ms 1.9 ms 2.4 ms 4.2 ms
PCX 57 203
TSX P57 2•3/2•23 1 ms/ 1.1 ms/ 2.2 ms/ 1.8 ms/ 2.2 ms/ 3.7 ms/
TSX P57 3•3/3•3A/3623/3623A 1.1 ms (A) 1.2 ms (A) 2.4 ms (A) 2 ms (A) 2.4 ms (A) 4.1 ms (A)
PCX 57 353
TSX P57 453/453A/4823/4823A 0.7 ms/ 0.8 ms/ 0.8 ms/ 1.5 ms/ 1.9 ms/ 2.1 ms/
0.8 ms (A) 0.9 ms (A) 0.9 ms (A) 1.7 ms (A) 2.1 ms (A) 2.3 ms (A)
IV
At a Glance
Aim of this Part The aim of this Part is to describe PCX 57 processors and their installation.
32
At a Glance
General introduction
At a Glance Integrated into a host PC (1) running Windows 95/98/2000 or Windows NT with a
16-bit ISA bus, PCX 57 processors manage, using PL7 Junior or PL7 Pro software,
a complete PLC station made up of racks, discrete input/output modules, analog
input/output modules and application modules, which can be distributed over one or
more racks connected to an X Bus.
Note: the PCX 57 processor communicates with the PC in which it is installed via
the 16-bit ISA bus. To do this, a communication driver (ISAWAY 95/98/2000 or
ISAWAY NY must be installed.
Illustration
PCX 57 processor
Host PC
Note: (1) the term "host PC" means a Schneider Group industrial PC or any other
office PC that has the characteristics defined above.
Illustration This diagram labels the different components of a PCX 57 processor module
Note: the TER terminal port offers master UNI-TELWAY communication mode by
default, and can be configured for slave UNI-TELWAY or ASCII character mode.
Real-time clock
Diagrams The various following diagrams show the dimensions, in millimeters, of PCX 57
processor cards.
249
Note: a PCX 57 processor uses two slots on the PC ISA bus. These slots must be
adjacent and 20.32mm apart.
Illustration This diagram shows the various components which make up a PCX 57 processor
card
3
4
2 5
Table of The following table gives the names and descriptions of the various components
components and which make up the PCX 57 processor card:
their
Address Element Description
descriptions
1 PCX 57 processor associated with a mechanical sub-assembly used to
card house a PCMCIA type 3 communication card.
2 battery the battery (See Changing the PCX 57 RAM memory
backup battery, p. 304) ensures the processor RAM
memory is saved, and it should be mounted in the
appropriate slot on the processor card.
3 line terminator TSX TLYEX /B (See Line terminator TSX TLYEX,
p. 105) line terminator.
4 removable cover a removable cover for a PCMCIA communication card
specific to the PCX 57 processor.
5 shield shield equipped with a 9-pin SUB D connector to link a
TSX CBY..0K (See TSX CBY..0K X Bus extension cable
(II ≥ 02), p. 100) X Bus extension cable, and a cable for
linking to the PCX 57 processor. This accessory is for
connecting the PCX 57 processor inside a section of the
X Bus.
6 daughterboard interfaces between the above shield and the PCX 57
processor card. This accessory should be used with the
above shield. It is fitted instead of the A/ line terminator
which is built into the processor as standard.
Note: in addition to the components given above, the following are provided with
the PCX 57 card:
z diskettes containing the ISAWAY drivers and OFS software package,
z instructions for installing the PCX 57 processor.
33
At a Glance
Aim of this This Chapter deals with the installation of PCX 57 processors and the PCMCIA
Chapter extension card.
General You are advised to limit charges of static electricity, which can cause significant
damage to electronic circuits. To do this the following rules should be observed:
z hold the card by the edges. Do not touch the connectors or any of the circuits that
are visible,
z do not take the card out of its protective anti-static packaging before you are
ready to install it in the PC,
z ground yourself during handling, if possible,
z do not put the card on a metal surface,
z avoid unnecessary movements, as static electricity is generated by clothing,
carpets and furniture.
General The PCX 57 processor physically occupies two consecutive slots, slots 1 and 2, on
the ISA bus but only uses one of them, slot 1, electrically. Slot 2 is used by the
PCMCIA communication card.
Logical The PCX 57 processor logically occupies the same slot as a TSX P57 processor
installation on (rack with address 0, position 00 or 01).
the X Bus
The TSX RKY••EX rack with address 0 must have a power supply module and the
position which is normally taken up by a TSX P57 processor will be unoccupied
(virtual slot for the PCX 57 processor).
Premium PLCs have two types of power supply (standard and double format). The
unoccupied position on the rack with address 0 will be depend upon the type of
power supply used.
Note:
z the slot corresponding to the PCX 57 processor address (physically free on the
rack) must not be used by another module.
z the X Bus address (See How to configure the PCX 57 processor address on the
X Bus, p. 286) must be configured using the micro-switches on the processor
card, so that the PCX 57 processor is aware of its address on the X Bus.
Using a standard In this case, the installation rule for the rack with address 0 is as follows:
format power z the power supply module automatically occupies position PS,
supply module z position 00, the virtual slot for the processor, must be unoccupied,
z the other modules are installed starting at position 01.
The following diagram shows the module installation rule when a single format
power supply module is used.
TSX RKY••EX rack at address x
Rack address: 00
Address position: 00
Using a double In this case, the installation rule for the rack with address 0 is as follows:
format power z the power supply module automatically occupies positions PS and 00,
supply module z position 01, the virtual slot for the processor, must be unoccupied,
z the other modules are installed starting from position 02.
The following diagram shows the module installation rule when a single format
power supply module is used.
TSX RKY••EX rack at address x
Rack address: 0
Address position: 01
General Certain operations must be performed before a processor card is installed in the PC:
z if necessary, insert the battery into the slot provided (See Changing the PCX 57
RAM memory backup battery, p. 304),
z if necessary, insert the PCMCIA memory card (See How to install/remove the
memory extension card on the PCX 57 processor, p. 297),
z configure the address of the processor on the X Bus (See How to configure the
PCX 57 processor address on the X Bus, p. 286),
z configure the processor’s standard I/O address on the ISA bus (See How to
configure the processor’s standard I/O address on the ISA bus, p. 288).
General points This address must be the same as the one which will be configured in the
configuration screen of the PL7 Junior or PL7 Pro software. This configuration is
carried out using micro-switches found on the processor card.
Rack address: the processor’s virtual slot is always situated on the rack with
address 0.
Processor position: the virtual position of the processor will depend upon the type
of power supply installed on the rack:
z single format power supply: virtual position of processor = 00,
z double format power supply: virtual position of processor = 01.
Default configuration:
z rack address = 0,
z module position = 00.
Rack 0 1 2 3 4 5 6 7
Position of the
micro-
switches
PCX ADD
Addresses not used
Position of the PCX ADD micro-switches in relation to the processor’s position on
the rack:
Position of the
processeur 00 01
Position of the
micro-
switches
PCX ADD
How to configure the processor’s standard I/O address on the ISA bus
CAUTION
Bad configuration
A bad configuration can lead to the PC malfunctioning.
Failure to follow this instruction can result in injury or equipment
damage.
Configuring the This configuration is carried out using the 6 micro-switches located near the PCX
standard 57’s ISA connector. They represent from left to right the bits with addresses SA9 to
address of the SA4.
PCX 57 The address H‘220’ is configured by default.
processor on the
ISA bus
Note: this address must be the same as the one which will be configured in the
configuration screen of the ISAWAY driver.
Illustration: the PCX 57 card and its micro-switches which are used to configure the
address
Configuring the This is configured using a jack-plug which should be placed over the interrupt to be
interrupt used by selected. IRQ 10 is selected by default.
the processor on
the ISA bus
(IRQ..)
Illustration: PCX 57 card with micro-switches which are used to configure the IRQ.
DANGER
Procedure to be The following table describes the procedure for installing the processor card in the
followed PC:
Step Action
1 Once the PC’s electrical power supply has been switched off, remove the
computer casing and find two free adjacent ISA slots.
Emplacement ISA 2
2 Remove the protective covers and fixing screws already in place which
correspond to the available slots.
3 Install the card in the planned free slots.
4 Fix the card to the PC by tightening the fixing screws you removed previously.
5 Place the casing back on the computer again and replace all the cables and
accessories which had to be switched off:
z X Bus cable and /B line terminator TSX TLYEX
Warning: The processor switches to a blocking fault, if the line terminator /B
is not installed:
z on the PCX 57 processor, if this is not linked to a rack by a TSX CBY ..
X Bus cable. . In this case, a /B line terminator (See Line terminator
TSX TLYEX, p. 105) must be installed on the processor’s X Bus output.
z on the available connector of the last rack of the station, if the PCX 57
processor is linked to a rack by a TSX CBY .. X Bus cable. . In this case,
a /B line terminator must be installed.
This device is used to show that the X Bus has not been adapted.
z FIPIO Bus cable and PCMCIA communication card, if necessary.
General As standard, the PCX 57 processor is equipped to be built into the start of the X Bus
line, and for this reason it has a built-in A/ line terminator.
If you want to integrate the processor into an X Bus section, the module is supplied
with two accessories which make this possible:
z a shield equipped with:
z a 9-pin SUB D connector for linking up a TSX CBY• X Bus cable,
z a cable for connecting the 9-pin SUB D connector to the processor card,
z a daughterboard equipped with two connectors which interface between the
PCX 57 card and the 9-pin SUB D connector of the aforementioned shield. This
daughterboard is fitted instead of the A/ line terminator, mounted on the PCX 57
card as standard.
Shield
Daughterboard
PCX 57
PCX 57
Note: in this example, as the PCX 57 processor is no longer integrated at the start
of the line, the TSX TLY EX A/ and /B line terminators must be installed on each
of the racks situated at the end of the lines.
Principle Perform the following steps to install the memory card on the PCX 57 processor:
Step Action
1 Place the PCMCIA card in its allocated slot.
2 Slide it in until it can go no further.
3 Position the card in the PC with the power turned off.
CAUTION
Installation precautions
The memory extension card must be installed on the processor card
with the power switched off and before the latter is installed in the PC.
Failure to follow this instruction can result in injury or equipment
damage.
Note: if the program in the PCMCIA memory cartridge contains the RUN AUTO
option, the processor will automatically restart in RUN mode after the cartridge is
inserted and the PC is turned on.
General
CAUTION
Insertion/Extraction
It is forbidden to insert or extract the PCMCIA memory card into or from
a PCX 57 when it is powered-up. These actions, although they will not
damage the processor or any other device, cause random processor
behavior and thus, correct operation cannot be guaranteed.
Failure to follow this instruction can result in injury or equipment
damage.
CAUTION
RUN AUTO option
If the program contained in the PCMCIA memory card includes the
RUN AUTO option, the processor will automatically restart in RUN
mode after the card is inserted and the PC is switched on.
Failure to follow this instruction can result in injury or equipment
damage.
General See Standard and Backup Memory Cards for PLCs, p. 162 andApplication + Files
Type Memory Cards, p. 165:
Important
CAUTION
Replacing a processor
If the PCX 57 processor is being replaced by another processor which
is not blank (i.e. the processor has already been programmed and
contains an application), you must cut the power to all of the PLC
station’s control units.
Before restoring power to the control units, check that the processor
contains the required application.
Failure to follow this instruction can result in injury or equipment
damage.
34
At a Glance
Labeling of the Six LEDs (RUN, TER, BAT, I/O, FIP and ERR) found on the processor card enable
LEDs fast diagnostics of the status of the PLC station.
Due to the small amount of space available on the shield, only the ERR LED is
visible when the PC housing the processor is closed.
To make it more user-friendly, the state of the RUN, I/O, ERR and FIP LEDs is
displayed via a utility in the task bar in Windows 95/98 or Windows NT on the PC
with the processor card. This functionality is only available when the host PC is
running (ISAWAY driver installed)
RUN PLC running normally, PLC in STOP mode or z PLC not configured:
(green) program executing. blocked by software application missing,
error. invalid or incompatible,
z PLC error: processor
or system error.
TER - terminal port link active. link not active.
(yellow) The rate of flashing is
relative to the amount of
traffic.
I/O input/output errors X Bus error (1). normal state, no internal
(red) coming from a module, a error.
channel or a
configuration error.
FIP - FIPIO bus link active. link not active.
(yellow) The rate of flashing is
relative to the amount of
traffic.
ERR processor or system z PLC not configured normal state, no internal
(red) error. (application missing, error.
invalid or
incompatible),
z PLC blocked by a
software error,
z memory card battery
error,
z X Bus error (1).
Note:
z (1) an X Bus error is indicated by simultaneous flashing of the ERR and I/O
LEDs.
z the FIP LED is only present on TPCX P57 353 processor.
Introduction This battery on the PCX 57 processor module ensures that the processor internal
RAM memory and the real-time clock are saved in the event of a power outage. It is
delivered in the same packaging as the processor and must be installed by the user.
Note: with a PCX 57 processor, there is no point in putting a battery into the rack
power supply which usually houses the processor (rack with address 0).
Changing the The battery can be changed every year as a preventative measure or when the BAT
battery LED is lit. However the LED is not visible when the PC is closed, but you have a
%S68 system bit (0 = backup battery OK) which can be used by the application
program to generate an alarm to warn that the battery needs changing.
CAUTION
Precaution to be taken when changing the battery
Changing the battery should not exceed the stated limit for the PC being
switched off. Exceeding this limit may cause data in RAM memory to be
lost.
Failure to follow this instruction can result in injury or equipment
damage.
1: cover
2: battery
Assuming that the processor was switched on previously, the guaranteed time
varies in the following way:
Ambient temperature when switching off 20°C 30°C 40°C 50°C
Backup time 2h 45mn 20mn 8mn
Introduction RAM memory PCMCIA cards (TSX MRP etc.) must have a battery (reference
TSX BAT M01) which needs to be changed.
Write protection
Lock
Battery slot
Number
Note: during operation, the processor’s ERR LED flashes if the PCMCIA card
battery is defective.
General All processors have a RESET button on their front panel, which when pressed,
causes a PLC cold start, in RUN or in STOP mode (1), in the application contained
on the memory card (or in internal RAM).
RESET following As soon as a processor fault appears, the alarm relay on rack 0 (2) is deactivated
a processor fault (open contact) and the module outputs switch to fallback position or are maintained
in the current state depending on the selection made at configuration. Pressing the
RESET button causes the PLC, forced into STOP mode, to cold start.
Note: when the RESET button is pressed, and during the PLC cold start, the
terminal link is deactivated.
General The following table describes the different actions on the PC and what implications
they have for the PCX 57:
Action on the PC PCX 57 behavior
Switching off/on warm restart if the application environment has not changed
Micro-outages on the As the PCX 57 does not have a filtering mechanism for micro-
network supplying the outages, every micro-outage not filtered by the PC’s internal
PC power supply causes a warm restart of the PCX 57, if the
application environment has not changed
Pressing the RESET generally, and subject to the PC’s RESET button activating the
button RSTDRV signal on the ISA bus, pressing the PC RESET button
causes a warm restart of the PCX 57, if the application
environment has not changed.
PC’s software RESET these actions have no effect on the current state of the PCX 57
(CTRL ALT DEL) processor (if the PCX 57 processor is in RUN, it stays in , etc.) and
does not cause a warm restart or cold restart
Note: a PC software blockage has no effect on the current state of the PCX 57
processor (identical behavior to a PC software RESET).
General See:
z Finding errors using processor state LEDs, p. 198,
z Non blocking errors, p. 199,
z Blocking errors, p. 201,
z Processor or system errors, p. 202.
35
General characteristics of the PCX 57 203 processor
PCX 57 203 The following table gives the general characteristics of the PCX 57 203 processor:
processor
Reference PCX 57 203
36
General characteristics of the PCX 57 353 processor
PCX 57 353 The following table introduces the general characteristics of the PCX 57 353
processor processor:
Reference PCX 57 353
(1) 1st figure when the application is in internal RAM, 2nd figure when the application
is in card memory.
Aim of this The aim of this Chapter is to introduce you to the characteristics of devices that can
Chapter be used when installing a PCX 57 station.
General As the processors can be fitted with certain devices which do not have their own
power supply, the consumption of these devices must be taken into account when
establishing a global breakdown of power consumption.
z Devices without their own power supply which can be connected to the terminal
port:
z adjustment terminal: T FTX 117 ADJUST,
z unit TSX P ACC01 for connecting to the UNI-TELWAY bus.
z Devices without their own power supply which can be built into the processor:
z PCMCIA communication cards TSX FPP 10/20,
z PCMCIA communication card TSX SCP 111/112/114,
z PCMCIA communication card TSX MBP 100,
z PCMCIA modem card TSX MDM 10.
Feature of PCX PCX 57 processors have their own 5VDC power supply, which is generated from the
57 processors host PC’s 12 VDC power supply. As a result of this, the 12 VDC power supply from
the host PC must have sufficient power to accommodate a PCX 57 processor.
Dissipated This table states the dissipated power for PCX 57 processors:
power
Processor + PCMCIA Typical consumption Maximum consumption
memory card
TPCX P57 203 4,8W 6,72W
TPCX P57 353 6,6W 9,24W
Tables of Consumption:
consumption
Consumption at 12VDC from host PC Typical Maximum
and dissipated
power Devices without their own power TFTX 117 ADJUST 144 mA 157 mA
supply which can be connected to the TSXPACC01 69 mA 116 mA
terminal port (TER)
PCMCIA communication card which TSXFPP10 153 mA 167 mA
can be built into the processor TSXFPP20 153 mA 167 mA
TSXSCP111 65 mA 139 mA
TSXSCP112 56 mA 139 mA
TSXSCP114 69 mA 139 mA
TSXMBP100 102 mA 144 mA
TSXMDM10 90 mA -
Dissipated power:
Dissipated power Typical Maximum
Devices without their own power TFTX 117 ADJUST 1.7 W 1.9 W
supply which can be connected to TSXPACC01 0.8 W 1.4 W
the terminal port (TER)
PCMCIA communication card which TSXFPP10 1.8 W 2.0 W
can be built into the processor TSXFPP20 1.8 W 2,0W
TSXSCP111 0.8 W 1.7 W
TSXSCP112 0.7 W 1.7 W
TSXSCP114 0.8 W 1.7 W
TSXMBP100 1.2 W 1.7 W
TSXMDM10 1.1 W -
(*) Although these channels are application-specific, they should not be taken into
account when calculating the maximum number of application-specific channels
which can be supported by the processor.
Note: only channels configured from PL7 Junior or PL7 Pro software can be
counted.
Processor performance
V
At a Glance
Subject of this This part describes TSX PSY ... supply modules and their implementation.
Part
Aim of this The aim of this Chapter is to introduce the TSX PSY… supply modules .
Chapter
General introduction
At a Glance TSX PSY… supply modules are designed to supply each TSX RKY… rack and its
modules. The supply module is chosen according to the distribution network (direct
or alternating current) and the power required (standard or double format model).
Supply modules The following table displays the types of supply module according to their format:
for an alternating
Standard format model Double format model
current network
Supply modules The following table displays the types of supply module according to their format:
for a direct
Standard format model Double format model
current network
Illustration These illustrations label the different components of a standard supply module and
a double format supply module:
Note: on the TSX PSY 2600/5500/5520/8500 supply modules, the primary voltage
protection fuse is inside the module and cannot be accessed.
8 110/220 voltage selector, only present on alternating current supply modules
TSX PSY 5500/8500. On delivery, the selector is set to 220.
Aim of this This Chapter deals with the installation of TSX PSY … power supply modules.
Chapter
Mounting The mounting of the TSX PSY… power supply module is identical to the mounting
of processor modules and, in general terms, the same as the mounting of other
modules (see How to mount processor modules, p. 156).
Installation This table describes the principles of installing power supply modules:
Type of supply module Description Illustration
Standard format: installed in the first slot
TSX PSY 2600/1610 in each TSX RKY rack
and occupy the PS
position.
Note: each supply module is provided with a locating device that only allows the
module to be installed in the slot designated above.
Note: the TSX PSY 8500 supply module does not provide 24VR voltage. Because
of this, a rack fitted with this supply module will not be able to accommodate some
modules, such as relay output and weighing modules
General points The TSX PSY ••• power supply modules on each rack are equipped with a non-
removable terminal block, protected by a flap, which is used to connect the power
supply, the alarm relay, the protection ground and, for alternating current supplies,
the supply of the 24 VDC sensors.
This screw terminal block is equipped with captive clamp screws which can connect
a maximum of 2 wires with a cross-sectional area of 1.5mm 2 with wire end ferrules,
or one wire with a cross-sectional area of 2.5mm 2 (maximum tightening torque on
screw terminal: 0.8N.m).
The wires come out vertically towards the bottom. These wires can be kept in place
with a cable-clip.
Illustration This diagram shows the screw terminal block:
Supply
24V
sensors
Alarm relay Alarm relay
Network ~ 24V
110-220V network (1)
Protection Protection
ground ground
PE PE
CAUTION
Positioning the voltage selector
For the power supply modules TSX PSY 5500/8500, position the
voltage selector according to the voltage power used (110 or 220 VAC).
Failure to follow this instruction can result in injury or equipment
damage.
Note: as direct current supply modules TSX PSY 1610/2610/5520 have a strong
signaling current, it is not advisable to use them on direct current networks which
protect flood-back current limits.
When a power supply module is connected to a direct current network, it is
mandatory to limit the length of the supply cable in order to prevent transmission
loss.
z TSX PSY 1610 supply module:
z length limited to 30 meters (60 meters there and back) with copper wires and
a 2.5mm2 cross-section,
z length limited to 20 meters (40 meters there and back) with copper wires and
a 1.5mm2 cross-section.
z TSX PSY 3610 and TSX PSY 5520 supply modules:
z length limited to 15 meters (30 meters there and back) with copper wires and
a 2.5mm2 cross-section,
z length limited to 10 meters (20 meters there and back) with copper wires and
a 1.5mm2 cross-section.
Warning Linking several PLCs supplied by a permissible direct current network not
connected to ground.
The 0V and physical ground are linked internally in the PLCs, in the network cabling
accessories and in some control consoles.
For specific applications which use a "floating" installation, special measures should
be taken with connections. These depend on the method used for installation.
In this case, it is mandatory to use insulated direct current power supplies. Please
contact us when you are defining the electrical installation.
Connecting a Illustration:
single-rack PLC
station Alternating network 100-240 V
Supply control
Pre-actuators
Sensor supply
for sensors on the rack (2)
Note: protective fuses: alternating current power supply modules TSX PSY 2600/
5500/8500 are fitted during manufacture with a protective fuse. This fuse, in series
with the L input, is located inside the module and cannot be accessed.
Connecting a Illustration:
PLC station Alternating network 100-240 V
made up of
several racks
Supply control
pre-actuators
Sensor supply
for sensors on the rack (2)
TSX PSY ..00
Supply control
pre-actuators
Sensor supply
for sensors on the rack (2)
TSX PSY ..00
Note: if there are several PLC stations supplied by the same network, the
principles of connection are identical.
Warning In the case of floating mounting (not linked to ground) used for specific applications
and in particular in Marine Applications, an insulated TSX PSY 5520 (24/48 VDC)
supply module must be selected.
Battery
charger
Pre-actuator
Battery supply control
Rack x
TSX PSY 5520
Insulation
tester
modules
Note: a device can continually measure the level of insulation of the 24 VDC (or
48 VDC) in relation to the ground, and can give an alert when the level of insulation
is abnormally low.
The input/output modules in the Premium range are insulated.
Supply control
pre-actuators
Supply control
pre-actuators
Supply
sensors/
pre-actuators
Supply control
pre-actuators
Note: if there are several PLC stations supplied by the same network, the
principles of connection are identical.
TSX PSY 5520 Connecting a single-rack PLC station with a ground-referenced network:
isolated power
supply module Alternating network 100-240 V
Supply control
pre-actuators
Note: protective fuse: the TSX PSY 5520 power supply modules are fitted during
manufacture with a protective fuse. This fuse, in series with the 24/48V input, is
located inside the module and cannot be accessed.
Supply control
pre-actuators
Note: protective fuse: the TSX PSY 5520 power supply modules are fitted during
manufacture with a protective fuse. This fuse, in series with the 24/48V input, is
located inside the module and cannot be accessed.
Note: if there are several PLC stations supplied by the same network, the
principles of connection are identical.
How to set up It is recommended that servo control of the different power supplies is set up in the
servo control following sequence:
Step Action
1 Switch on the power supply to the PLC and the inputs (sensors), using the
contactor KM (see diagram ("Connecting DC power supply modules from an
AC network", Premium and Atrium using PL7 Pro, Processors, racks and
power supply modules, Implementation Manual)).
2 If the PLC is in RUN mode and running on AUTO, switch on the output power
supply (pre-actuators), using the contactor KA. This is controlled by the alarm
relay contact in each power supply.
Safety standards Before restarting the installation following a stop (caused by a power outage or an
emergency stop), safety standards require authorization to be given by the operator.
The MANU/AUTO switch makes it possible to force outputs from a terminal, when
the PLC is in STOP mode.
Emergency
stop
Supply
pre-actuators
Run
Auto Man.
alarm relay alarm relay
contact
contact (1)
KA: contact controlled by alarm relay (1) When the PLC station is
from supply module in AUTO run mode. composed of several racks: set
all the "alarm relay" contacts in series
(RAL0, RAL1, RAL2, etc.).
Supply
Emergency sensors
stop
Supply
pre-actuators
Run
Auto
Man.
alarm relay alarm relay
contact contact (1)
KA: contact controlled by alarm relay (1) When the PLC station is
from supply module in AUTO run mode. composed of several racks: set
all the "alarm relay" contacts in series
(RAL0, RAL1, RAL2, etc.).
Introduction You are advised to mount a protection device, such as circuit-breaker and fuse, at
the start of the line on the supply network.
The following information can be used to define the minimum caliber of the circuit
breaker and the fuse for a given power supply module.
Selecting a line To select the caliber of the circuit breaker, the following three characteristics, which
circuit breaker are given for each supply module, should be taken into account.
z the nominal input current: I rms,
z signaling current: I,
z the It.
The minimum caliber for the circuit breaker should be selected as follows:
z caliber of circuit breaker IN > the supply I rms,
z max. circuit breaker I > the supply signal I,
z circuit breaker It at point A on the curve > the supplyIt.
Illustration: characteristics provided by the circuit breaker manufacturer.
Thermal zone
Magnetic zone
Selecting the line When selecting the caliber of the line fuse, the two following characteristics, which
fuse are given for each power supply, should be taken into account:
z the nominal input current: I rms,
z I2t.
Reminder of the characteristics of I rms, signal I, It and I2t for each power supply
module
TSX module PSY 2600 PSY 5500 PSY 8500 PSY PSY PSY
1610 3610 5520
I rms at 24VDC - - - 1.5A 2.7A 3A
at 48VDC - - - - - 1.5A
at 100VAC 0.5A 1.7A 1.4A - - -
at 24VAC 0.3A 0.5A 0.5A - - -
I signal(1) at 24VDC - - - 100A 150A 15A
at 48VDC - - - - - 15A
at 100VAC 37A 38A 30A - - -
at 24VAC 75A 38A 60A - - -
It at 24VDC - - - 0.2As 0.5As 7As
at 48VDC - - - - - 6As
at 100VAC 0.034As 0.11As 0.15As - - -
at 24VAC 0.067As 0.11As 0.15As - - -
Aim of this This Chapter deals with the diagnostics of TSX PSY … supply modules .
Chapter
Description The following table describes the various LEDs and their functions:
Display LED Description
OK LED (green) z on when operating normally,
z off when the output voltage is below the thresholds.
Sensor supply The alternating current supply modules TSX PSY 2600/5500/8500 have a built-in
power supply which delivers a voltage of 24VDC for supplying the sensors.
This sensor power supply can be accessed via the module’s screw connection
terminal block.
CAUTION
Parallelization
This supply module cannot be set in parallel with an external supply
module.
Failure to follow this instruction can result in injury or equipment
damage.
Note: the "24 VDC sensor supply module" output for the TSX PSY 8500 module is
a VLSV-(very low safety voltage) type This ensures the user’s safety.
At a Glance Each power supply module has a slot for the installation of a battery which supplies
the internal RAM memory of the processors in order to save the data when the PLC
is switched off.
This battery is delivered in the same packaging as the power supply module. When
inserting it, you must respect the polarities.
Note: if a Atrium processor which can be integrated into a PC is being used, the
back-up battery is built into the processor and its characteristics are the same as
those described below.
Data on the back- Battery characteristics: thyonile lithium chloride battery, 3.6V/0.8 Ah, 1/2AA size.
up battery
Period for which data is stored: the data storage time depends on two factors:
z the percentage of time for which the PLC is switched off and as a result the
battery is being used,
z the ambient temperature when the PLC is switched off.
Table of the ambient temperatures when switched off:
Ambient temperature when inoperative ≤ 30°C 40°C 50°C 60°C
Backup time PLC off for 12 hours 5 years 3 years 2 years 1 year
per day
PLC off for 1 hour 5 years 5 years 4.5 years 4 years
per day
Monitoring the battery status: when the power is on, it monitors the status of the
battery. If there are problems, the user is informed visually by the BAT (red) LED
which lights up. If this happens, the battery must be changed immediately. The
%S68 system bit gives the status of the backup battery (0 = battery OK).
Changing the battery: the battery can be changed when the power supply module
is on, or immediately after switching it off. In the latter case, the time for intervention
is limited.
The backup time depends on the ambient temperature. Assuming that the processor
was switched on previously, the guaranteed time varies in the following way.
Ambient temperature when switching off 20°C 30°C 40°C 50°C
Backup time 2h 45mn 20mn 8mn
General All the channels on this rack are seen as in error by the processor, but the other
racks are not affected. The values of the inputs in error are no longer updated in the
application memory and are reset to zero in a discrete input module, unless they
have been forced, when they are maintained at the forcing value.
Limit of failure If the failure period is less than 10 ms for alternating current power supplies or less
period than 1 ms direct current power supplies, the failure is not detected by the program,
which will run as normal.
What happens after pressing the RESET button on a power supply module
General The power supply module of each rack has a RESET button on its front panel, which
when pressed triggers an initialization sequence of the modules on the rack it is
supplying.
When this action takes place in a power supply module in the rack supporting the
TSX P57 processor (rack 0), it causes a warm restart.
Special case with In this case, the processor is not physically present on the rack at address 0, so
the PCX 57 pressing the RESET button on the rack power supply module does not cause the
processor application to warm restart, nevertheless the modules present on the rack are
reinitialized.
Aim of this This Chapter deals with the auxiliary functions of TSX PSY … supply modules .
Chapter
Introduction The alarm relay located in each supply module has a potential free contact, which
can be accessed on the module’s screw connection terminal block.
Illustration:
Connection
terminal block Ral
Alarm relay of When operating normally, with the PLC in RUN mode, the alarm relay is activated
the module and its contact is closed (state 1). Whenever the application is stopped, even
situated on the partially, when a "blocking" error appears, when there are incorrect output voltages
rack supporting or power disappears, the relay falls back and its associated contact opens (state 0).
the processor Illustration:
(rack 0)
PLC in RUN mode
Alarm relay
Operation appearance of a
alarm relay PLC blocking error or
rack 0 incorrect voltages
CAUTION
If this function is absolutely imperative for the proper operation of the installation, the
alarm relay of the power supply module can be replaced by the use of an alarm relay
output on the X Bus or the FIPIO bus. In order to achieve this, this output should be:
z a relay output,
z configured with fallback to 0 (default configuration),
z initialized at state 1 when the application program starts executing.
When configured in this way, the relay output will behave in the same way as the
alarm relay controlled by a TSX P57 processor.
Alarm relay for Once the module has been switched on and if the output voltages are correct, the
modules on the alarm relay is activated and the contact is closed (state 1).
other racks If the power disappears, or if the output voltages are incorrect, the relay falls back
(1 to 7) (state 0).
Aim of this The aim of this Chapter is to provide a breakdown of power consumption and power
Chapter for the selection of the power supply module.
General points The power needed to supply a rack depends on the type of modules installed on it.
It is therefore necessary to perform a consumption report in order to define the
supply module to be mounted on the rack (standard or double format module).
(1) The values in brackets correspond to the maximum values which can be
supported for 1 minute every 10 minutes. These values should not be taken into
account when calculating the breakdown of power consumption.
WARNING
Establishing the power breakdown
When the power breakdown is established, the total power consumed
on each output (5 VDC, 24 VR and 24 VS) must not exceed the total
output of the module.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
Note: the TSX PSY 8500 supply module does not have a 24 VR output for
supplying some modules at 24VDC. Therefore, the following provisions and
preparations must be made for all racks which have this type of power supply:
z the relay output modules TSX DSY 08R . / 16R. and the weighing module TSX
ISP Y 100 cannot be installed on these racks,
z the TSX ASY 800 analog output modules should be configured using an
external power supply (maximum of 3 modules per rack).
WARNING
Calculated power
The calculated power should be compared with the power of the supply
modules in the table below.
z power required on each output – available power on each output: 1-
1a, 2-2a, 3-3a.
z sum of the power required on each output – total power available: 4-
4a.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
Table 1 This table shows the typical consumption of each module and can be used to
calculate the consumption per rack and on each output depending on the modules
installed:
Rack number:
Module type Product references No. Consumption in mA (typical value) (1)
At 5VDC At 24VR At 24VS (2)
Module Total Module Total Module Total
Processor + TSX P57 103 440
PCMCIA memory TSX P57 153 530
card
TSX P57 203 750
TSX P57 2623 1110
TSX P57 253 820
TSX P57 2823 1180
TSX P57 303/303A 1000
TSX P57 3623/ 1360
3623A
TSX P57 353/353A 1060
TSX P57 453/453A 1080
TSX P57 4823/ 1440
4823A
Total
Table 2 This table shows the typical consumption of each module and can be used to
calculate the consumption per rack and on each output depending on the modules
installed:
Rack number:
Module type Product references No. Consumption in mA (typical value) (1)
At 5VDC At 24VR At 24VS (2)
Modul Total Module Total Module Total
e
Carried forward
Discrete input TSX DEY 08D2 55 80
TSX DEY 16A2 80
TSX DEY 16A3 80
TSX DEY 16A4 80
TSX DEY 16A5 80
TSX DEY 16D2 80 135
TSX DEY 16D3 80 135
TSX DEY 16FK 250 75
TSX DEY 32D2K 135 160
TSX DEY 32D3K 140 275
TSX DEY 64D2K 155 315
Rack number:
TOR outputs TSX DSY 08R4D 55 80
TSX DSY 08R5 55 70
TSX DSY 08R5A 55 80
TSX DSY 08S5 125
TSX DSY 08T2 55
TSX DSY 08T22 55
TSX DSY 08T31 55
TSX DSY 16R5 80 135
TSX DSY 16S4 220
TSX DSY 16S5 220
TSX DSY 16T2 80
TSX DSY 16T3 80
TSX DSY 32T2K 140
TSX DSY 64T2K 155
Discrete Inputs/ TSX DMY 28FK 300 75
Outputs TSX DMY 28RFK 300 75
Total
Table 3 This table shows the typical consumption of each module and can be used to
calculate the consumption per rack and on each output depending on the modules
installed:
Rack number:
Module type Product references No. Consumption in mA (typical value) (1)
At 5VDC At 24VR At 24VS (2)
Module Total Module Total Module Total
Carried
forward
Analog TSX AEY 414 660
TSX AEY 420 500
TSX AEY 800 270
TSX AEY 810 475
TSX AEY 1600 270
TSX AEY 1614 300
TSX AEY 410 990
TSX AEY 800 (3) 200 300
Counting TSX CTY 2A 280 30
TSX CTY 2C 850 15
TSX CTY 4A 330 36
Axis control TSX CAY 21 1100 15
TSX CAY 22 1100 15
TSX CAY 33 1500 30
TSX CAY 41 1500 30
TSX CAY 42 1500 30
TSX CSY 84 1800
Step by step TSX CFY 11 510 50
control TSX CFY 21 650 100
Grand total
Table 4 This table shows the typical consumption of each module and can be used to
calculate the consumption per rack and on each output depending on the modules
installed:
Rack number:
Module type Product references No. Consumption in mA (typical value) (1)
At 5VDC At 24VR At 24VS (2)
Module Total Module Total Module Total
Carried forward
Communication TSX ETY 110 (3) 800
(4) 1200
TSX ETY 120 (3) 800
(4) 1200
TSX ETY 210 (3) 800
(4) 1200
TSX ETY 4102/5102 360
TSX IBY 100 500
TSX PBY 100 400
TSX SAY 100 110
TSX SAY 1000 100
TSX SCY 21601 350
TSX SCP 111 140
TSX SCP 112 120
TSX SCP 114 150
TSX FPP 10 330
TSX FPP 200 330
TSX JNP 112 120
TSX JNP 114 150
TSX MBP 100 220
TSX MDM 10 195
Grand total
Table 5 This table shows the typical consumption of each module and can be used to
calculate the consumption per rack and on each output depending on the modules
installed:
Rack number:
Module type Product references No. Consumption in mA (typical value) (1)
At 5VDC At 24VR At 24VS (2)
Module Total Module Total Module Total
Carried forward
Weighing TSX ISPY 100/101 150 145
Emergency stop TSX PAY 262 150
backup TSX PAY 282 150
Remote X bus TSX REY 200 500
Other (devices TSX P ACC01 150
without their own T FTX 117 (adjust) 310
power supply which
can be connected to
the terminal port)
Grand total
Characteristics The TSX PSY 2600 module is a single format alternating current power supply
module.
Reference TSX PSY 2600
I2 t 0.63A2s to 100V
on locking 2.6A2s to 240V
It 0.034 As at 100V
on locking 0.067 As at 240V
Accepted length of micro-power outages ≤10ms
Integrated phase protection via internal, non-accessible fuse
(1) These values should be taken into account when starting up several devices at
the same time, or for dimensioning the protection systems.
(2) 24V direct current output for supplying relays of "relay output" modules.
Characteristics The TSX PSY 5500 module is a double format alternating current power supply
module.
Reference
I2 t 4A2s to 100V
on locking 2A2s to 240V
It 0.11 As at 100V
on locking 0.11 As at 240V
Accepted length of micro-power outages ≤10ms
Integrated phase protection via internal, non-accessible fuse
Reference
(1) These values should be taken into account when starting up several devices at
the same time, or for dimensioning the protection systems.
(2) 24V direct current output for supplying relays of "relay output" modules.
Characteristics The TSX PSY 8500 module is a double format alternating current power supply
module.
Reference
I 2t 15A2s to 100V
on locking 8A2s to 240V
It 0.15 As at 100V
on locking 0.15 As at 240V
Accepted length of micro-power outages ≤10ms
Integrated phase protection via internal, non-accessible fuse
Reference
(1) These values should be taken into account when starting up several devices at
the same time, or for dimensioning the protection systems.
(2) 77W at 60°C, 85W at 55°C, 100W at 55°C, if the rack is fitted with ventilation
modules.
(3) 24V direct current output for supplying relays of "relay output" modules.
Characteristics The TSX PSY 1610 module is a single format non-isolated direct current power
supply module.
Reference TSX PSY 1610
(1) With the supply of "relay output" modules, the limit range is reduced to
21.6V26.4V.
(2) These values should be taken into account when starting up several devices at
the same time, and for dimensioning the protection systems.
(3) 24V direct current output for supplying relays of "relay output" modules.
(4) The 24VR output voltage, which cannot be accessed by the user, is protected by
a fuse which is located under the module (5x20, 4A, Medium type).
Characteristics The TSX PSY 3610 module is a double format non-insulated direct current supply
module.
Reference
I2t 20 A2s
on locking
It 0.5 As
on locking
Accepted length of micro-power outages ≤1ms
Integrated input protection no
Reference
(1) With the supply of "relay output" modules, the limit range is reduced to
21.6V26.4V.
(2) These values should be taken into account when starting up several devices at
the same time, and for dimensioning the protection systems.
(3) 24V direct current output for supplying relays of "relay output" modules.
(4) The 24VR output voltage, which cannot be accessed by the user, is protected by
a fuse which is located under the module (5x20, 4A, Medium type).
Characteristics The TSX PSY 5520 module is a double format insulated direct current power supply
module.
Reference
I2 t 50 A2s at 24VDC
on locking 55 A2s at 48VDC
It 7 As at 24VDC
on locking 6 As at 48VDC
Accepted length of micro-power outages ≤1ms
Built-in protection of + input by internal, non-accessible fuse module
Reference
(1) These values should be taken into account when starting up several devices at
the same time, and for dimensioning the protection systems.
(2) 24VDC output for supplying the relays of the "relay output" modules.
VI
At a Glance
Aim of this Part This Part describes Process and AS-i supply and their installation.
General A wide range of power supply units and modules is offered to meet your needs in
the best possible way:
z TBX SUP 10 and TSX SUP 1..1 process power supply units and modules,
designed to supply 24 VDC to a PLC system periphery, and driven by PLCs
(TSX Micro and Premium). This periphery being composed of sensors, pre-
actuators, encoders, operator dialog terminals, regulators, LEDs, push-buttons,
pneumatic actuators, etc. . This 24 V power supply can be delivered using a 100/
240 V, 50/60 Hz AC network.
The power supply modules TBX SUP 10 and TSX SUP 1011 can also be
connected to a 125 VDC network.
z The AS-i power supply units and modules TSX SUP A02 and A05 designed to
supply 30 VDC to the components connected to an AS-i field bus. This power
supply is distributed over the same wires as those used for data exchange.
The attachment mode for these products has been specially designed to respond to
the specific mounting distances and specifications of TSX Micro and TSX Premium
PLCs, and TBX products.
1
2
3
4
Number table The following table shows the numbers and their corresponding descriptions from
the diagram above:
Numbers Description
1 LED showing power-up of module.
2 Screw terminal block for supply voltage wiring.
3 Identification label for the wire terminals.
4 Wings for fixing the module.
Number table The following table shows the numbers and their corresponding descriptions from
the diagram above:
Numbers Description
1 Support board for fixing the supply module directly onto the AM1-DE200 /
DP200 DIN mounting track or the AM1-PA Telequick perforated board.
2 Display block with:
z a 24 V LED (green): lit if the established internal and output voltages are
correct,
z a LSH LED (orange) "power optimization mode": lit if the power supply is
running in parallelization mode with power optimization.
3 Flap for protecting the terminal block.
4 Screw terminal block for connection:
z to the AC/DC supply network,
z to 24 VDC output.
2
3
4
5
6
7
Number table The following table shows the numbers and their corresponding descriptions from
the diagram above:
Numbers Description
1 Support board for fixing the supply module directly onto the AM1-DE200 /
DP200 DIN mounting track or the AM1-PA Telequick perforated board.
2 Display block with:
z a 24 V LED (green): lit if the internal and output voltages are correct,
z a LSH LED (orange) only on TSX SUP 1021 "power optimization mode":
lit if the power supply is running in parallelization mode with power
optimization.
3 Flap for protecting the terminal block.
4 Screw terminal block for connection:
z to the AC/DC supply network,
z to 24 VDC output.
Number table The following table shows the numbers and their corresponding descriptions from
the diagram above:
Numbers Description
1 Support board for fixing the supply module directly onto the AM1-DE200 /
DP200 DIN mounting rail or the AM1-PA Telequick board.
2 Display block with:
z an AS-i LED (green): lit if the internal and output voltages are correct,
Number table The following table shows the numbers and their corresponding descriptions from
the diagram above:
Numbers Description
1 Display block with an ON LED (orange): lit if power supply is running.
2 Display block with:
z a 24 V LED (green): lit if 24 VDC output voltage is present and correct,
z an AS-i LED (green): lit if the AS-i 30 VDC output voltage is present and
correct. This LED is only present on the TSX SUP A05.
3 Flap for protecting terminal blocks.
4 Screw terminal block for connection to alternating supply network.
5 Screw terminal block for connecting AS-i 24 VDC and 30 VDC output voltage
to TSX SUP A05.
6 Holes for the cable-tightening clip to go through.
7 Four fixing holes for M6 screws.
Introduction Each TSX SUP 10.1 and TSX SUP A02 supply module is delivered mounted on a
support board. This is used to fix the supply module: the DIN AM1-DE200 or
AM1-DP200 profile, or to a Telequick AM1-PA perforated mounting plate.
Each support board can take: either a TSX SUP 1021, TSX SUP 1051 or TSX SUP
A02 module, or one or two TSX SUP 1011 modules.
Information The following table shows the numbers and their corresponding descriptions from
Table the diagram above:
Number Description
1 Three 5.5 mm diameter holes for fixing the board onto a panel or an AM1-PA
perforated board with a mounting distance of 140 mm (mounting distance for
TSX 37 PLCs).
2 Four 6.5 mm diameter holes for fixing the board onto a panel or an AM1-PA
perforated board with a mounting distance of 88.9 mm (mounting distance for
TSX 57 PLCs).
3 Two M4 holes for fixing TSX SUP 1011/1021/1051/A02 supply module(s).
4 Windows designed to ink pins situated at the bottom and at the back of the
module.
Note:
• each of these supply modules can also be mounted on a TSX RKY••• rack in place
of another module, except in position PS. This must only be used by a TSX PSY•••
supply module for supplying rack modules.
• the following operations require the module to be removed from the support
board:
- positioning the "NOR/LSH" switch onto "LSH",
- mounting the board onto a panel or AM1-PA perforated board,
- mounting the module onto a TSX RKY••• rack.
Parallelization The aim of parallelization is to use two modules with the same product reference
mode with power in order to provide an output current which is greater than the maximum allowed by
optimization a single supply. The total current is the sum of the currents provided by all the
supplies put together.
Using this mode means output voltage can vary slightly: 24V + or - 5%
instead 24 V + or - 3% in normal mode.
When sharing loads, the power imbalance can reach a maximum of
25%.
A specific connection (See Connection of TSX SUP 1011/1021
power supplies, p. 418) is required for these types of modules.
TSX SUP 1051/1101 Power optimization mode does not require a switch on these supply
supply modules. A specific connection must be made for the TSX SUP 1051
(See Connection of TSX SUP 1051 power supplies, p. 420) module
and the TSX SUP 1101 (See Connection of TSX SUP 1101 power
supplies, p. 422) module.
The maximum current provided by two parallel supplies is limited to:
z 10A with 2 TSX SUP 1051 suppliers,
z 20A with 2 TSX SUP 1101 suppliers.
Redundancy/ Principle:
Safety on TSX
SUP 1011/1021
suppliers To ensure that the currents required for the application are available, even in the
event of failure of one of the suppliers.
To do this, the two suppliers are run in parallel by setting up the necessary
connections (see Connection of TSX SUP 1011/1021 power supplies, p. 418).
Fuse
Load
Note: TSX SUP 1051 and 1101 suppliers are not equipped with a serial diode,
which is required for the redundancy function.
General The simultaneous transmission of information and power down the same cable
means that data transmission needs to be filtered in relation to supply.
This is why AS-i supply module has a built-in decoupling filter which supports the
maximum direct current provided by the power supply. A standardized impedance
is introduced into the power supply in relation to the frequency of information
transmission.
Aim of this This Chapter deals with the installation of Process and AS-i supply modules.
Chapter
Dimensions/ Illustration:
mounting
The TBX SUP 10 supply block must be mounted in an upright position to allow for
the best possible natural air convection within the block.
It can be mounted on a panel, an AM1-PA Telequick perforated board or
AM1-DE200 / DP200 mounting rail.
Connections Illustration:
(1) External protection fuse on phase: 1A time delay 250V if single supply block.
Note: primary: if the module is supplied with a 100/240V alternating current, the
phase and the neutral wire must be taken into account when wiring. On the other
hand, if the module is supplied with a 125 V direct current, polarities do not need
to be taken into account.
secondary: the terminal, with 0V potential, must be connected to the ground as
soon as the supply module starts to provide output.
DANGER
Personnel safety
For personnel safety, the module ground terminal must be connected to
the protective ground with a green/yellow wire.
Failure to follow this instruction will result in death or serious
injury.
At a Glance Each power supply module is delivered with a support which allows it to be mounted
directly on a DIN (AM1-D••••) mounting rail or TELEQUICK (AM1-PA) mounting
plate.
Note: when using the TELEQUICK mounting plate, it is necessary to remove the
module.
Dimensions The illustration below shows the dimensions of the modules and support and the
overall dimensions for each type of mounting system.
SUP 1021/ Mounting support
SUP 1011 1051/A02
Dimensions in millimeters
Mounting on an
AM1-D mounting
rail
Mounting on an
AM1-PA board
Illustration:
Support
Support
Mounting on a TSX SUP 1011/1021/1051/A02 power supply modules can be mounted in any
TSX RKY••• rack position on the TSX RKY•• rack, except for the PS position reserved for the power
supply module of the rack. In this case, the support is not used and must be
removed.
The support delivered with the supply module is not used and must be removed; the
module is in this case mounted in the same way as the other modules (e.g.:
processor (see How to mount processor modules, p. 156).
Note: the power supply module of the TSX PSY••• rack must be in the PS position
in order to supply power to the modules in the rack.
Introduction TSX SUP 1101 and TSX SUP A05 supply blocks can be mounted on a panel, an
AM1-PA board, or DIN rail.
(1) The diameter of the fixing holes must be sufficient to take M6 screws.
Mounting on an Fix the supply block with 4 M6 x 25 screws + washers and AF1-EA6 clips nuts
AM1-PA (dimensions in millimeters):
Telequick
mounting grid
Mounting on 35 Fix the supply block using 4 M6 x 25 screws + washers and AF1-CF6 1/4 turn sliding
mm wide DIN nuts (dimensions in millimeters):
mounting rail
Summary table The following table lists a summary of the different methods available for mounting
of mounting Process and AS-i supply modules:
methods
Supply module TBX SUP TSX SUP TSX SUP TSX SUP TSX SUP TSX SUP TSX SUP
product reference 10 1011 1021 1051 1101 A02 A05
AM1-PA Telequick X X X X X X X
board
AM1-DE200/DP200 X X X X X
central DIN rail
AM1-ED DIN rail with X X X X X X
88.9 mm spacing
(TSX 57 PLC)
TSX 57 rack X X X X
TSX RKY••
Aim of this This Chapter deals with the connection of Process supply modules.
Chapter
Module 1
Module 2
Connection rules Primary:if the module is supplied with a 100/240V AC power supply, it is necessary
to observe wiring requirements for the phase and neutral when connecting the
module. However, if the module is powered by a 125 VDC supply, it is not necessary
to respect the polarities.
z an operating voltage ≥ 600 V AC with a cross-section of 1.5 mm2 for connection
to the mains,
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module
must be connected to the protective earth using a green/yellow wire.
Failure to follow this instruction will result in death or serious
injury.
The power supply terminal is protected by a flap which allows access to the wiring
terminals. The wires come vertically out of the power supply at its base. These wires
can be kept in place with a cable-clip.
Module 1
Connection rules Primary: observe the rules concerning phase and neutral when wiring.
z an operating voltage ≥ 600 VAC with a cross-section of 1.5 mm2 for connection
to the mains,
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module
must be connected to the protective earth using a green/yellow wire.
Failure to follow this instruction will result in death or serious
injury.
The power supply terminal is protected by a flap which allows access to the wiring
terminals. The wires come vertically out of the power supply at its base. These wires
can be kept in place with a cable-clip.
Module 1
Module 2
Connection rules Primary: Observe the rules concerning phase and neutral when wiring.
z an operating voltage ≥ 600 V AC with a cross-section of 1.5mm2 or 2.5mm2 for
connection to the mains,
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module
must be connected to the protective earth using a green/yellow wire.
Failure to follow this instruction will result in death or serious
injury.
The power supply terminal is protected by a flap which allows access to the wiring
terminals. The wires come vertically out of the power supply at its base. These wires
can be kept in place with a cable-clip.
52
At a Glance
Aim of this This Chapter deals with the connection of AS-i supply modules.
Chapter
Connection The TSX SUP A02 power supply module is designed to supply the AS-i bus, and the
synoptic connected slaves (30 VDC/2.4A).
AS-i Master
Connection rules Primary: observe the rules concerning phase and neutral when wiring.
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module
must be connected to the protective earth using a green/yellow wire.
Failure to follow this instruction will result in death or serious
injury.
The power supply terminal is protected by a flap which allows access to the wiring
terminals. The wires come vertically out of the power supply at its base. These wires
can be kept in place with a cable-clip.
(1)
(3)
Connection The TSX SUP A05 supply module is designed to supply the AS-i bus, including the
overview slaves which are connected to it (30V/5A output). It also has an auxiliary supply (24
VDC/7A) for sensors/actuators which consume large amounts of current. For this, a
black AS-i ribbon cable is used.
Principle diagram:
AS-i master
Rules of Primary: observe the rules concerning phase and neutral when wiring.
connection
z an operating voltage ≥ 600 V AC with a cross-section of 1.5mm2 or 2.5mm2 for
connection to the mains,
DANGER
Safety of personnel
For personnel safety, the module ground terminal must be connected to
the protective ground with a green/yellow wire.
Failure to follow this instruction will result in death or serious
injury.
The "AC power supply network" and "24V and 30 V DC output" AS-i terminals are
protected by a flap allowing access to the wiring terminals. The wires come vertically
out of the power supply at its base. These wires can be kept in place with a cable-
clip.
Using a shielded cable for the AS-i bus is only necessary if the installation is overly
disrupted in terms of EMC (Electro Magnetic Compatibility).
Given the large current that this supply module provides, its position on the bus is
very important.
If the supply module is placed at one of the ends of the bus, it will provide a nominal
current (e.g. 5A) for the whole bus. The fall in voltage at the end of the bus is
therefore proportional to the 5A.
If it is positioned in the middle of the bus, the voltage drop at the ends is proportional
to only 2.5A, assuming that the consumption for both sections of the bus is the
same.
Supply
AS-i
2.5 A 2.5 A
Note: where there are large power consumer actuators (contactor, solenoid coils
etc.) the TSX SUP A05 supply module can provide the auxiliary 24 VDC, insulated
from the AS-i line.
General precautions
Introduction While installing the yellow AS-i cable, it is essential to place it in a cable track which
is separate from the power cables. It is also advisable to place it flat and not twisted.
This will help make the two AS-i cable wires as symmetrical as possible.
Installing the AS-i cable on a surface connected to the electric potential of the
machine (for example, the housing) complies with the requirements of the EMC
(Electro Magnetic Compatibility) directive.
The end of the cable, or the ends in the case of a bus with a star-formation , must
be protected either:
z by connecting it (them) to a T-derivation,
z by not allowing them to come out of their last connection point.
Important It is important to distribute power effectively on the AS-i bus, so that each device on
the bus is supplied with sufficient voltage to enable it to operate properly. To do this,
certain rules must be followed.
Rule 1 Select the caliber of the supply module adapted to the total consumption of the AS-i
segment. Available calibers are 2.4A (TSX SUP A02) and 5A (TSX SUP A05).
A caliber of 2.4A is generally sufficient based on an average consumption of 65mA
per slave for a segment made up of a maximum of 31 slaves.
Rule 2 To minimize the effect of voltage falls and reduce the cost of the cable, you must
determine the best position of the supply module on the bus, as well as the minimum
size of cable appropriate for distributing power.
The voltage fall between the master and the last slave on the bus must not exceed
3V. For that purpose, the table below gives the essential points for selecting the
cross-sectional measurement of the AS-i cable.
Table of characteristics:
Cross-section 0.75 mm2 1.5 mm2 2.5 mm2
measurement of AS-i
cable
Linear resistance 52 milli Ohms/meter 27 milli Ohms/ 16 milli Ohms/
meter meter
Voltage fall for 1A over 100 5.2V 2.7V 1.6V
meters
The cable which can be used for most applications is the cable with a cross-section
of 1.5 mm2. This is the standard AS-i bus model (the cable is offered in the
SCHNEIDER catalog).
Smaller cables can be used when sensors consume very little power.
Note: the maximum length of all the segments making up the AS-i bus without a
relay is 100 meters. The lengths of cables which link a slave to a passive
distribution box must be taken into account.
Aim of this This Chapter presents the different electrical characteristics of Process and AS-i
Chapter supply modules in a table.
Table of The following table describes the electrical characteristics of supply modules:
Characteristics TBX SUP 10 and TSX SUP 1011:
Process supply TBX SUP 10 24V/1A TSX SUP 1011 24V/1A
Primary
Nominal input voltage V alternating 100240 alternating 100240
direct 125 direct 125
Input limit voltage V alternating 90264 alternating 85264
direct 88156 direct 105156
Network frequency Hz 47...63 47...63/360...440
Nominal input current On 0.4 0.4
(U=100V)
Maximum call to 100 V On 3 37
current (1) to 240 V On 30 75
Maximum It on to 100 V As 0.03 0.034
trigger (1) to 240 V As 0.07 0.067
2
Maximum I t on to 100 V A s 2 2 0.63
trigger (1) to 240 V 2 2.6
A2 s
Power factor 0.6 0.6
Harmonic (3) 10% (Phi=0°and 180°) 10% (Phi=0°and 180°)
Full load efficiency % >75 >75
Secondary
Output (2) W 24 26(30)
Nominal output On 1 1.1
current (2)
Output voltage/ V 24+/-5% 24+/-3%
accuracy at 25°C
(1) Values on initial power-up at 25°C. These elements are to be taken into account
on start-up for the dimensioning of protection devices.
(2) Output power and current for an ambient temperature of 60°C. Input value in ( )
= output in a ventilated cabinet or within a temperature range of 0+40°C.
(3) A nominal voltage for a repetition period of 1Hz.
Table of The following table describes the electrical characteristics of supply modules:
Characteristics TSX SUP 1021/1051/1101:
Process supply TSX SUP 1021 TSX SUP 1051 TSX SUP 1101
24V/2A 24V/5A 24V/10A
Primary
Nominal input voltage V alternating 100..0.120/200..0.240
Input limit voltage V alternating 85...132/170...264
Network frequency Hz 47...63/360...440
Nominal input current (U=100V) On 0.8 2.4 5
Maximum call current (1) to 100 V On <30 51 75
to 240 V On <30 51 51
Maximum It on trigger (1) to 100 V As 0.06 0.17 0.17
to 240 V As 0.03 0.17 0.17
Process supply TSX SUP 1021 TSX SUP 1051 TSX SUP 1101
24V/2A 24V/5A 24V/10A
(1) Values on initial power-up at 25°C. These elements are to be taken into account
on start-up for the dimensioning of protection devices.
(2) Output power and current for an ambient temperature of 60°C. Input value in ( )
= output in a ventilated cabinet or within a temperature range of 0+40°C.
(3) A nominal voltage for a repetition period of 1Hz.
Table of The following table describes the electrical characteristics of supply modules: TSX
Characteristics SUP A02/A05:
References TSX SUP A02 TSX SUP A05 24V/7 AS-i & 30V AS-i/5A
30V AS-i / 2.4A
Primary
Nominal input voltage V alternating 100..0.120/ alternating 100..0.120/200..0.240
200..0.240
Input limit voltage V alternating 85...132/ alternating 85...132/170...264
170...264
Network frequency Hz 47...63/360...440 47...63/360...440
Nominal input current (U=100V) On 1.3 5
Maximum call to 100 V On 30 50
current (1) to 240 V On 30 50
Maximum It on to 100 V As 0.06 0.17
trigger (1) to 240 V As 0.03 0.17
I2
Maximum t on to 100 V A s 2 4 8.5
trigger (1) to 240 V 4 8.5
A 2s
Power factor 0.6 0.51
Harmonic 3 10% (Phi=0°and 180°) 10% (Phi=0°and 180°)
Full load efficiency % >75 >80
Secondary
Output W 72(84) (2) 230 (3)
Peak nominal 30 V AS-i On 2.4(2.8) (2) 5 (3)(4)
current output
24 V output On - 7 (3)(4)
References TSX SUP A02 TSX SUP A05 24V/7 AS-i & 30V AS-i/5A
30V AS-i / 2.4A
(1) Values on initial power-up at 25°C. These elements are to be taken into account
on start-up for the dimensioning of protection devices.
(2) Output and output current for an ambient temperature of 60°C. Input value () =
surge output.
(3) Output and output current for a maximum ambient temperature of 55°C, if
product index II = 01 (60°C if product index II > 01).
(4) Distribution of current for each output (See Chart of available currents on 30 V
AS-i and 24 V output from the TSX SUP A05 supply block., p. 442).
(5) Acceptable period at nominal voltage for a repetition period of 1 Hz.
Chart of available The maximum power which can be delivered by the supply block is 230 W. If
currents on 30 V consumption is 5 A on the 30 V AS-i, possible flow on 24 V output is no greater than
AS-i and 24 V 3 A (see chart below).
output from the
TSX SUP A05
supply block. Chart:
Table of The following table describes the electrical characteristics of Process and AS-i
characteristics supply modules:
Process and AS-i supply TBX SUP 10 TSX SUP 1011/1021
blocks/modules TSX SUP 1051/1101
TSX SUP A02/A05
Connection to screw 1 terminal per output 1011/1021/1051/A02: 1 output terminal
terminals 1101 : 2 terminals/output
A05: 2 terminals/output (24 VDC)
1 terminal/output (30 VDC AS-i)
maximum capacity per mm2 1 x 2.5 2 x 1.5 with adapter or 1 x 2.5
terminal
Temperature: -25 to +70 -25 to +70
Storage °C +5 to +55 0 to +60 (TSX SUP 1011/1021/1051/1101
Operating °C -10 to +60 (TSX SUP A02/A05) (1)
Relative humidity % 5-95
Cooling % By natural convection
User safety - Very Low Voltage Safety (EN 60950 and
IEC 1131-2)
Dielectric strength: 50/60Hz-1 mm
Primary/secondary V eff 1500 3500
Primary/ground V eff 1500 2200
Secondary/ground V eff 500 500
Insulation resistance
Primary/secondary Mega Ohms ≥ 100
Primary/ground Mega Ohms ≥ 100
Leakage current I≤=3.5 mA (EN 60950)
Electrostatic uploading 6 kV per contact/8 KV in the air
immunity (complies with IEC 1000-4-2)
Fast electric surge 2 kV (serial mode and common mode on input and output)
Electromagnetic field 10 V/m (80MHz to 1GHz)
influence
Rejected electromagnetic (comply with FCC 15-A et EN 55022 class A
disturbances Test conditions: nominal U and I, resisting load,
cable: 1 meter horizontally, 0.8 meters vertically
Shock wave Input: 4kV MC, 2kV MS Outputs: 2kV MF, 0.5 kV MS
(complies with IEC 1000-4-5)
(1) -10°C +55°C for TSX SUP A05 supply module with product index II=01.
-10°C +60°C for TSX SUP A05 supply module with product index II > 01.
(2) Complies with IEC 68-2-6, FC test with module or block mounted on a board or
panel.
E 24
General introduction to TSX PSY power
Environment characteristics of AS-i supply
supply modules, 28
modules, 443
General introduction to TSX PSY supply
Event response time, 265
modules, 326
Extendable rack
General introduction to TSX RKY racks, 27
description, 75
General introduction to TSX SCY/ETY
communication, 39
F
FAST cycle time, 264 H
Finding errors using the processor state
How the PCX 57 behaves after an action on
LEDs, 198
the PC, 311
G I
General characteristics of the PCX 57 203
Installation/mounting TSX PSY supply
processor, 313
modules, 332
General characteristics of the PCX 57 353
Installing a PCX 57 in the PC, 292
processor, 315
Installing racks, 78
General introduction to PCX 57 processors,
Installing the PCX 57
26
preliminary operations, 285
General introduction to Process and AS-i
Installing the PCX 57 processor, 281
power supply modules, 392
Integrating a PCX 57 into an X Bus section,
General introduction to Process and AS-i
294
TSX SUP and TSX 1021/1051 power supply
Introduction to PCX 57 processors, 270
modules, 29
Introduction to TSX CAY axis control
General introduction to the AS-i bus interface
modules, 36
module
TSX SAY, 44
General introduction to the TSX FAN L
ventilation module, 46
Labeling, 109
General introduction to the TSX ISPY
Line terminator TSX TLYEX, 105
weighing module, 45
Logical installation of the PCX 57 processor
General introduction to the TSX P57, 146
on the X Bus, 282
General introduction to the TSX PAY
emergency stop monitoring module, 47
General introduction to the TSX REY X Bus
extension module, 31
M
General introduction to TSX CFY step by MAST cycle time, 255, 256, 258, 262
step control modules, 38 Memory Card TSX MRP DS 2048 P, 168
General introduction to TSX CTY/CCY Memory Card TSX MRP F 004M, 168
counting modules, 34 Memory Cards, 162, 165
General introduction to TSX DEY/DSY/DMY Module addresses, 94
input/output modules, 32 Module installation on a rack, 96
General introduction to TSX P57 processors, Mounting and fixing racks, 81
Mounting processor modules, 156 Rules for installing racks with ventilation
Mounting/Removing a PCMCIA Card on modules, 120
TSX P57, 158
S
N Standard rack
Non blocking errors, 199 description, 74
O T
Overview of a PLC station, 21 TSX CBY 1000 X Bus extension cable, 103
Overview of aPLC station, 20 TSX CBY..0K X Bus extension cable, 100
TSX P 57 103 characteristics, 203
TSX P57 153 characteristics, 205
P TSX P57 203 characteristics, 207
PCX 57 card components, 276 TSX P57 253 characteristics, 209
Physical description of TSX P57 processors, TSX P57 2623 characteristics, 211
148 TSX P57 2823 characteristics, 215
PLC station rack addressing, 91 TSX P57 303 characteristics, 217
PLC station topology, extension module, 139 TSX P57 303A characteristics, 219
Positioning of line termination, 107 TSX P57 353 characteristics, 221
Positioning of line terminators, 106 TSX P57 353A characteristics, 223
Positioning the processor module, 154 TSX P57 3623 characteristics, 225
Power supply management, 141 TSX P57 3623A characteristics, 229
Power supply servo control, 344 TSX P57 453 characteristics, 233
Precautions, 432 TSX P57 453A characteristics, 235
Precautions to be taken when installing a TSX P57 4823 characteristics, 239
PCI 57, 280 TSX P57 4823A characteristics, 243
Precautions to be taken when replacing a TSX P57 electrical characteristics, 248
TSX P57 processor, 175 TSX PSY supply modules
Processing on insertion/extraction of a description, 328
PCMCIA memory card on a PCX 57 PLC, TSX RKA 02 protective cover, 108
298 TSX RKY Racks
Processing on Insertion/Extraction of a introduction to, 70
PCMCIA Memory Card on a Premium PLC, TSX SUP 10 dimensions/mounting/
161 connection, 406
Processor/system errors, 202
Protection devices, 347
V
Ventilation module
R characteristics, 123
Rack power supply failure, 354 dimensions, 117
Real-time clock, 150 introduction, 114
Rules for connecting to TSX PSY supply mounting, 118
modules, 333 physical description, 116
W
What happens after pressing the RESET
button on a power supply module, 355
What happens after you press the processor
RESET button, 197, 310
X
X Bus extension module
diagnostics, 137
installation, 128
X-Bus extension module
configuration, 131
introduction, 126
maximum distances, 132
physical description, 127
X-Bus extension modules
connections, 135