TeSys GV7 - GV7RS50
TeSys GV7 - GV7RS50
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product TeSys GV7
Range TeSys
Product name TeSys GV7
Device short name GV7R
Product or component type Circuit breaker
Device application Motor
Poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Breaking capacity 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit 100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit rating 30...50 A
Trip unit technology Thermal-magnetic
Complementary
Mounting mode By clips
By screws
Mounting support Flush
Panel mounting
Rail
Kit for fixing the switchgear
Mounting position Vertical
Motor power kW 22 kW at 400...415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
30 kW at 660...690 V AC 50/60 Hz
Control type Rocker lever
Environment
Standards EN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-4-1
NF C 63-120
NF C 63-650
NF C 79-130
VDE 0113
VDE 0660
Product certifications DNV
UL
Protective treatment TC
IP degree of protection IP405 with terminal shrouds conforming to IEC 60529
Pollution degree 3
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -55...95 °C
Fire resistance 960 °C conforming to IEC 60695-2-1
Operating altitude 2000 m
Contractual warranty
Warranty period 18 months