The document contains 7 problems involving calculations for overhead transmission lines. Problem 1 involves determining the sending end voltage, power factor, and transmission efficiency for a single phase line delivering 1100 kW at 33 kV and 0.8 power factor lagging. Problem 2 involves calculating the power output and sending end power factor for a 3-phase line with given impedance and voltages. Problem 3 involves determining the sending end voltage for a 3-phase line delivering 50 MW at 220 kV using the short line approximation.

Uploaded by

Suhail Bilal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views2 pages

6 L 1 Ke 84 Mo 7

The document contains 7 problems involving calculations for overhead transmission lines. Problem 1 involves determining the sending end voltage, power factor, and transmission efficiency for a single phase line delivering 1100 kW at 33 kV and 0.8 power factor lagging. Problem 2 involves calculating the power output and sending end power factor for a 3-phase line with given impedance and voltages. Problem 3 involves determining the sending end voltage for a 3-phase line delivering 50 MW at 220 kV using the short line approximation.

Uploaded by

Suhail Bilal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Exercise 4

1. A single phase overhead transmission line delivers 1100 kW


at 33 kV at 0·8 p.f. lagging. The total resistance and
inductive reactance of the line are 10 Ω and 15 Ω
respectively. Determine: (i) sending end voltage (ii) sending
end power factor and (iii) transmission efficiency

2. A short 3-φ transmission line with an impedance of (6 + j 8)


Ω per phase has sending and receiving end voltages of 120
kV and 110 kV respectively for some receiving end load at a
p.f. of 0·9 lagging. Determine (i) power output and (ii)
sending end power factor.

3. A three phase 50 Hz transmission line has impedance of


(25.3 + j66.5) ohms and a shunt admittance of 4.42 * 10-4
mho per phase. If it delivers a load of 50 MW at 220 kV at
0.8 power factor lagging, determine the sending end voltage
by using short line approximation.

4. Determine the efficiency and regulation of a 3-phase, 150


km long, 50 Hz transmission line delivering 20 MW at a
power factor of 0.8 lagging and 66 kV to a balanced load.
Resistance of the line is 0.075 /km, inductance and
capacitance of the line are 0.1675 Henry and 1.49 F
respectively.
5. Determine the voltage, current and power factor at the
sending end of a 3 phase, 50 Hz, overhead transmission line
160 km long delivering a load of 100 MVA at 0.8 pf lagging
and 132 kV to a balanced load. Resistance per km is 0.16 
inductance per km is 1.2 mH and capacitance per km per
conductor is 0.0082 F.

6. Find the characteristics of the load at the sending end and the
efficiency of a three phase transmission line 160 km long
delivering 15 MVA load at 110 kV, 50 Hz and 0.9 power
factor (lagging) having inductance 1.356 mH/km per phase,
capacitance 0.0085 pF/km per phase and resistance 40 ohms.

7. The line constants of a transmission line are A = 0.9301


0.98° and B = 14124 8187° ohm. The load at the receiving
end is 60 MVA, 50 Hz, 0.8 pf lagging. The supply voltage is
220 kV. Calculate the load voltage.