Transformer Questions
Transformer Questions
Ans : The principle of operation of a transformer is based upon the theory of mutual
induction Between two electrical linked by a common magnetic flux .
Ans: The rating of a transformer is the maximum power which can be drawn from it
without the temperature rise in the winding exceeding the safe limits for the particular
class of insulation employed .
Ans: The rated capacity of a transformer is expressed in KVA not in KW. Generally the
rating of a transformer is determined by its temperature rise . The temperature rise is
caused by the losses in the machine . Copper loss depends on the value of the load
current and iron loss on voltage . Therefore ,total loss of a transformer depends on volt-
ampere (VA) and is independent of load power Factor. A certain amount of current will
produce the same I2 R loss at any value of power factor . This loss limits the output of
the machine .The output in kilowatts is proportional to the power factor . For a given
KW load if the power factor decreases, the load current increases proportionately
causing more losses and temperature rise in the machine . For the above reason,
transformers are generally rated in KVA, not in KW .
Ans : The power factor of a transformer is very low and lagging on no load . But the
power factor on load is nearly equal to the power factor of the load which it is carrying .
6. What is the normal phase difference between the voltage and the on load current in
a transformer ?
Ans :The no load current in a transformer normally lags behind the voltage by about 70.
Ans: The essential parts are as follows :- a)Magnetic circuit consisting of laminated iron
core and clamping structures. b)Primary winding . c)Secondary winding . d)Tank filled
with insulating oil . e)H.T terminals with bushing . f)L.T terminals with bushing .
g)Conservator tank. h)Breather. i)Vent pipe . j)WTI ( Winding Temperature Indicator ) &
OTI ( Oil Temperature Indicator). k)Radiator.
9 . What is the name of the winding from which the supply is taken for load
connecting ?
10. What material is used for the cores of a transformer and why ?
Ans: Lamination of specially alloyed silicon steel (silicon content 4 to 5%) are used due
to its high electrical resistance ,high permeability non-ageing characteristics and
minimum iron loss .
Ans :The iron core is used in a transformer to provide a continuous easy magnetic path
of low reluctance .
Ans: The magnetic leakage is reduced to a minimum by sectionalizing & interleaving the
primary and secondary windings .
Ans: The joints in iron core should be staggered to avoid clear air gap in the magnetic
circuit as the air gap reduces the magnetic flux due to its high reluctance .
14.Why are iron cores made laminated in the transformer ?
Ans: Iron cores are made laminated to reduce the eddy current loss .
Ans: Frequency.
Ans: The laminations are insulated from each other by insulating varnish or thin paper to
break the path of eddy currents thus to reduce the eddy current loss .
Ans: Stacking factor is the ratio of iron content in the laminated varnished core by
volume. Its value is about 90% i.e. 10% volume is occupied by the varnish and air .
Ans: The grain oriented laminations are such cold rolled laminations specially annealed
to orient the iron crystals i.e the grains in a uniform direction in the direction of rolling
which produces loss . These laminations are punched and assembled in such a way that
the grains of different lamina line in the same direction as the magnetic field and not
across it .
Transformer’s interview
questions paper-2
21. What is the phase relationship between the primary and secondary voltages of a
transformer?
Ans: The ratio of number of turns in the primary to the number of turns in the
secondary winding is called the turn ratio or the ratio of transformation of the
transformer which is indicated by a constant ҅K ҆ .Than (N1/N2 ) = E1/E2 = K .
Ans : Voltage ratio is the ratio of the voltage between the line terminals of one winding
to that between the terminals of another winding at no load .
24. What is the relation between voltage ratio and turn ratio of (a) D/D ,(b) D/Y,(c)
Y/Y &(d) Y/D transformer ?
25. What do you mean by true ratio of transformation and commercial ratio
transformations ?
Ans: The true ratio of transformation is the ratio of phase voltages of the primary and
secondary winding whereas the commercial ratio of transformation is the ratio of the
primary and secondary line voltages .
26. What is the relation between primary ampere-turns to the secondary ampere-turns
?
Ans : The primary and secondary ampere-turns are equal and opposite i.e. I1 N1=
I2 N2 Then I1/I2= N2/N2 i.e the primary and secondary currents are inverse as the
respective turns .
27. How is the secondary voltage calculated by the turns of the winding ?
Ans: The voltage per turn is practically constant in particular transformer so the
secondary voltage is calculated by multiplying the input primary voltage per turn to the
number of secondary turns .
28.What current flows in the transformer primary when its secondary is open ?
Ans: When the secondary is open there is no current in the secondary of the
transformer. The primary takes a small current (I0)from the source called as no load
current which has two components, a magnetising component (I0 sin ∅0 )producing
the magnetic flux and a working component (I0 cos ∅0 ) supplying real power for iron
losses .
30. Why is the frequency not changed during transformation of electrical energy in a
transformer ?
Ans: As the same flux having a definite frequency is responsible for the production of
e.m.fs on both the primary and secondary windings so there is no question of changing
the frequency .
31. How is the induced e.m.f related with the flux linkage ?
32. What do you mean by the counter e.m.f in the primary winding of a transformer ?
Ans :when an alternating voltage to the primary winding it causes a flow of alternating
current which creates alternating flux. This alternating flux is linked with both the
primary and secondary winding and hence induces self-induces e.m.f on the primary
winding and a mutually-induced e.m.f on the secondary winding . Since the primary self-
induced e.m.f is in the opposite direction to the applied voltage , it is known as counter
e.m.f of the transformer .
Ans: E(r.m.s) =4.44 ∅m.f.T. volts Where ∅m=maximum value of the flux linking with both
the winding . F=frequency of the supply. T=number of turns.
Transformer’s interview
questions paper-3
34. What are the types of transformers according to transformation?
35. What are the types of the transformer according to the arrangement of iron cores ?
Ans : there are three types :- (a) Core type (b) Shell type (c) Distributed core or Berry
type.
36. What is the difference between a core type and a shell type transformer?
Ans :In core type transformer the primary and secondary winding are placed on each leg
having one magnetic circuit while in shell type transformer both the winding are placed
on a common central core having two magnetic circuits. In core type transformer the
iron loss will be less and copper loss will be more as compared with a shell-type
transformer .
37. What magnetic circuit is formed in Berry type construction and why ?
Ans : Distributed magnetic circuits are formed in Berry type construction because of its
distributed cores.
Ans: the vertical portion of the iron core where the windings are placed is called limb.
39. Why are the primary and secondary windings placed on each limb in core type
transformer ?
Ans: To reduce the total dielectric strength of the insulating materials provided on the
winding.
Ans : Practically the flux of primary winding does not link fully the secondary winding . A
portion of primary flux without linking the secondary winding passes through the air
path. This flux opposes the main circuit current and behaves in the same way as in
inductance . The effect is same as that of a reactance acting in series to the primary
circuit .
42. What are the types of transformers according to winding and supply?
Ans : (a) The single phase transformers ,(b) The three phase transformers and (c)The
polyphase transformers.
45. What is the difference between cylindrical type and sandwich type winding ?
Ans: In cylindrical type winding the length of the coil is equal to the length of the core
limb and the primary and secondary windings are placed one over the other placing low
voltage winding nearer the core ,while in sandwitch type winding the H.T and L.T
winding are placed on limb lengthwise one above the other link the sandwitch.
46. Name the different types of coils used in the transformer winding and state there
used.
47. What insulation is largely used in the windings of a high voltage transformer ?
Ans: Varnish coated paper insulation is largely used for the winding of a high voltage
transformer .
Ans: Where the insulation to earth at all points of a winding can withstand the separate
source test voltage appropriate to the line end then it is called as uniform insulation .
This is generally used up to maximum system voltage of 72.5 KV (r.m.s).
Transformer interview
questions paper-4
51. What are the types of transformers according to transformation?
Ans: When the transformer transforms low voltage to high voltage it is called a step up
transformer and when the transformer transforms high voltage to low voltage it is called
a step down transformer .
1. Voltage can be transformed from low voltage to high voltage for transmission and
high voltage to low voltage for distribution without changing the frequency.
2. As the transformer has on rotating parts there is no frictional losses and were and
tear of it .
3. A high voltage or an extra high voltage can be transformed easily by providing good
insulation.
4. Its maintenance cost is low.
5. Practically it requires very little attention for its operation.
Ans: The transformer which are used up on transmission, lines for the transmission and
distribution of relatively large quantities of energy are called power transformers.
Ans: The high capacity step up transformers , which are used in the generating station
for onward transmission of electrical energy, are called transmission transformers.
Ans: When the transformers are used for distributing the energy from transmission lines
and networks for local consumption and the secondaries are directly connected to the
consumers load, they are called distribution transformers.
60. How does a transformer taken part for wide-spread popularity of a.c. system
over d.c. ?
Ans: (1) High voltages of a.c. system can be obtained by using a transformer for
transmission of electrical power.
(2) A.C voltages can be increased or decreased without any power loss by using a
transformer.
61. Is there any difference of power if the secondary of the transformer is connected
in star and delta respectively?
Ans: To prevent the damage to the coils and core due to excessive heat accumulated
inside the transformers .
63. What are the sources of heart developed inside the transformer ?
Ans : Load current produces heat in the winding and eddy current produces heat in the
iron core .
Ans: In natural air cooling system is effected by atmospheric air which passes inside the
transformer through the holes provided on the casing of the transformer. Here
convection process helps in cooling. This type of cooling is applied only in low KVA rating
transformer.
67. What do you mean by oil natural air natural type cooling system?
Ans: During running of transformer the oil in contact with core and coils becomes
heated. The heated oil comes in contact with the casing and being lighter goes up
through the cooling tubes where the heat is dissipated to the surrounding air. Finally
cold having oil comes down and enters the tank again. This process continues in cyclic
order so long the transformer is on running operation.
Ans: In oil natural air forced type cooling method the oil cooling system is improved by
the arrangements of fans which create air blasting.
70. What do you mean by oil forced air forced type cooling ?
Ans : In oil forced air forced type cooling system the oil is circulated through coolers
which have cooling fans of exchange heat from oil to air.
Transformer interview
questions paper-5
71. What do you mean by oil immersed water forced type cooling ?
Ans: In oil immersed water forced cooling system the oil cooling method is further
improved by the arrangement of tubes on the top of the transformer tank but below the
oil level. Water is circulated through these tubes and cools the heated oil of the
transformer.
72. What do you mean by oil forced water forced type cooling?
Ans: In the oil forced water forced type cooling water are circulated through the heat
exchanger to exchange heat from oil to cooling water.
73. What are standard symbols used for describing different methods of cooling
transformer ?
Ans: The oil used in electrical apparatus for cooling purpose as well as quenching of arc
is called as power oil.
Ans: Transformer oil is a variety of mineral oil obtained by refining crude petroleum
which is an excellent insulator and its loss by evaporation is negligible small.
Ans: Power transformer are filled with oil to provide cooling by dissipating heat from
coils and core to the outer casing and also to increase the dielectric strength of the
insulation.
77.What do you mean by flash point and fire point of transformer oil?
Ans : The flash point of transformer oil is the ignition temperature of oil vapor i.e. the
lowest temperature at which the oil gives off sufficient inflammable vapour to produce
momentary flash on the application of a small flame . It is about 140⁰C.
Ans : The moisture , dust and temperature affect the dielectric strength.
Ans: “Askarel” means a group of synthetic liquids of high dielectric strength which
overcomes the disadvantage of mineral insulated oil e.g. susceptibility to catching and
propagate fire. This synthetic oil named as “Askarel” is used as an insulating and cooling
medium in the electrical equipment where there is a necessity to reduce the risked of
fire and explosion.
83. What are the fittings and accessories which should be provided on a transformer
?
Ans: The standard fittings and accessories - (1) Cable boxes, (2)Oil conservator,
(3) Breather ,(4) Oil gauge, (5) Relief and Explosion vent,(6) Tapping switch, (7) Buchholz
relay, (8)Radiator, (9)Bushings, (10) Oil level indicator, (11) Drain valve with plug, (12)
Lifting hook, (13) Earthing terminal, (14) Nameplate, (15) Oil filling hole and cap, (16)
Thermometer pocket & (17) Rollers.
Ans: The following accessories are fitted as the precautionary measure against
deterioration of transformer oil :- (1) Oil conservator, (2) Breather, (3)Buchholz relay &
(4) Oil level indicator
85.What is a conservator ?
Ans: Conservator is a cylindrical tank placed on the top of the transformer connected to
the main transformer oil tank by a short length pipe. It is partly filled with oil.
Ans: Oil conservators are fitted to the transformers to take up the expansion and
contraction of oil during running operation and also to observe the full oil filling of
transformer tank through its oil level indicator.
87. Why is the conservation tank not completely filled with oil ?
Ans : During running condition the oil volume is increased with the increase of
temperature . So the conservator tank is not completely filled with oil to absorb the
increased volume of oil in its upper air space.
89.What is a breather ?
Ans: Breather is a small cylindrical chamber containing silica gel and connected to the
top of the conservator by an air tight extended pipe. It allows moisture free air to the
conservator tank.
Ans: The function of a breather is to extract moisture from the ingoing air in order to
prevent any contamination of the transformer oil by the moisture which is very much
present in the open air.
Transformer interview
questions paper-6
91.What material is used to fill in the breather?
Ans: Moisture absorbing silicon gel or CaCl2 is used to fill the breather which turns pink
when it absorbs moisture . When fried again it gets its original form by removing its
moisture contents.
Ans : If there is a large volume of gas formed within the tank due to short circuit fault in
the winding the pressure is released from the transformer through the explosion vent
pipe by rupturing the diaphragms mounted on the mouth of it.
Ans : The temperature of the hot oil be determined with the help of a thermometer by
putting its bulb inside a low pocket meant for thermometer situated near the top of the
transformer tank where the oil is hottest.
95. What do you know about the temperature indicator of the transformer winding ?
Ans : The temperature indicator is nothing but a dial type thermometer fitted in such a
way that its bulb is immersed in the region where the transformer oil is hottest and the
bulb is associated with a small encircled heating coil connected to the is so designed
that the bulb temperature is increased by an amount equal to the greatest winding to
oil temperature gradient and an appropriate value of temperature is indicated directly
on the dial.
Ans: Bad cooling and overloading are the causes of temperature rise in a transformer .
Ans : The losses in a transformer are – (1) Core losses or iron or constant losses
consisting of hysteresis and eddy current losses in the core and (2)Copper losses in the
primary and secondary winding .
Ans: The hysteresis loss depends on (1)the quality and constituents of the iron core, (2)
the frequency and (3) the flux density.
101. What is the main purpose of using silicon steel in the laminations of transformer
core ?
102. Is there any variation of core flux between no load of full load ?
Ans : No load current produces core flux and supplies iron losses and copper loss on no
load.
Ans : When a load is connected to the secondary side of a transformer the transformer
is said to be on load and the current circulating through the secondary winding vai load
is called the load current.
Ans : When the load current (I2) flows through the secondary winding a
counterbalancing current (I1,) is induced on the primary winding varying inversely to
their respective turns . The total primary current on load (I1) is equal to the vector sum
of the primary counterbalancing current (I1) and the no load current (I0) which will be
approximately equal to (I1,) as I0 is practically very small.
106. What will be the effect on primary said if the load current increases ?
Ans : The equivalent circuit of the transformer means the simplified corresponding
transformer circuit modeling the behavior of a real transformer which represents the
primary circuit as well as the secondary circuit in one circuit with suitable parameters
for easy calculation with the addition of a shunt circuit to account for no load current.
Ans : The approximate equivalent circuit of the transformer means a slight modification
of the equivalent circuit by transferring the shunt circuit to the primary terminal with
close approximation affecting very little change in the result.
109. How do you calculate the equivalent resistance and reactance of the
transformer referred to the primary and secondary ?
110. A 50 KVA transformer has a turn ratio on (N1/N2 ) = 10. The impedance of the
primary winding is 4+j7 ohms while that of the secondary winding is o.6 + j 1.1 ohms.
What will be the impedance of the transformer when referred to the primary?
Ans : Resistance drop is the voltage drop in the resistance of the winding which is in
phase with the current (IR1’). Reactance drop is the voltage drop in the reactance of the
winding which is in quadrature with the current(IX1’). Impedance drop is the vector sum
of the resistance drop and the reactance drop.
Ans : The reactance voltage drop becomes larger because of the large value of the
inductive reactance of the transformer winding than its ohmic resistance.
Ans : Core losses are determined by open circuit test. In this test normal voltage is
applied on the low voltage side at rated frequency and since there is no load on the high
voltage side the reading of the wattmeter connected on the low voltage side gives the
no load loss or core losses of the transformer. High voltage side is kept open due to
suitability of using metering arrangement in the low voltage side rather than high
voltage side.
Ans : Since no load current is very small and no load copper loss is very small in
comparison with iron losses so the copper losses are neglected in open circuit test.
118. In a short circuit test if the wattmeter reads 160 watts at 20 amperes of current
what will be the reading of the wattmeter at 50 amperes of current ?
119. Why is a C.T used with the wattmeter when performing ashort circuit test on a
transformer ?
Ans : Since the current coil of a wattmeter is capable of carrying about 5 amps therefore
during short circuit test the current more than 5 amps will cause damage to the current
coil. So for safety of the current coil of the wattmeter a current transformer is used.
Ans: The impedance voltage of a transformer required to circulate rated current through
a winding of the transformer when another winding is short circuited with the
respective windings connected as for rated voltage operation. It is usually expressed in
percent of the rated voltage of the winding in which the voltage is measured.
Ans: The ordinary or commercial efficiency of a transformer is defined as the ratio of the
output in watts to the input in watts. Since the efficiency is based on the power output
in watts and not on volt-amperes, the power factor plays an important role in
determining the efficiency.
Efficiency =(Output power)/(Input power) =(E2 I2×P.F)/(E2 I2×P.F+Losses)
= (E2 I2 cos∅)/(E2 I2 cos∅+W1+I1’ R1+I2’ R2 )
Where E2 =Secondary voltage.
I2 = Secondary current.
I1 =Primary current.
R1 =Primary resistance.
R2 = Secondary resistance.
W1 =Iron losses.
Ans : The condition for the maximum efficiency of a transformer is (Iron losses =copper
losses).
Ans : The efficiency of a power transformer depends on the power factor of the load
and the percentage of the load.
124. How does the efficiency of a power transformer depend on the load current ?
Ans : The efficiency increases with the increase in load current and reaches to maximum
value and then decreases with further increase in load current .
125. A transformer has iron loss of 300 watts and full load copper loss of 500 watts.
What will be the total loss of the transformer for maximum efficiency ?
Ans : Since the transformer is a static apparatus without any rotating parts there
frictional loss. The only losses are iron losses end copper losses in the primary and
secondary. Therefore, the efficiency of a transformer becomes so high about 95% to
98%.
Ans : All day efficiency is defined as the ratio of energy output in 24 hours to energy
input in 24 hours.
Ans : The regulation of a transformer is the difference between the no load and full load
secondary voltages expressed in terms of the no load voltage with constant primary
voltage.
Interview questions of
Transformer paper-8
131. What will be the effect of power factor and load on the regulation of a
transformer ?
Ans : For lagging power factor of load current the regulation will be positive i.e. the
secondary voltage will be reduced with the increase in the load current. For leading
power factor of load current, the regulation will be negative i.e. the secondary voltage
will be negative i.e. the secondary voltage will be increased with the increase in the load
current.
132. Why is load test performed in addition to O.C. and S.C. test ?
Ans : Load test is performed not only to find the regulation and efficiency but also to
measure the temperature rise of the transformer at different loads.
Ans : The impedance voltage is the vector sum of resistance voltage and reactance
voltage. The percentage impedance is the value of impedance voltage expressed as a
percentage of rated voltage. Thus % Impedance = % Impedance voltage = (V1 Z1’)/V1 ×
100
Where, I1 =Rated primary current.
Z1 =Impedance with reference to the primary.
V1 =Rated primary voltage.
Ans : (1) OFF load tap changing & (2) ON load tap changing. Offload tap changing gears
can be operated only when all the loads on the transformer are cut off. The voltage ratio
of a transformer can be varied by about ± 10% by means of OFF load tap changing gears.
ON load tap changing gears can be operated even when the load is on. The voltage ratio
of a transformer can be varied by about ± 16% by means of ON load tap changing gears.
136. On which winding (H.V or L.V ) of a power transformer the tapings are normally
provided and why ?
Ans : The tapings are generally provided on the high voltage side since the current
loading is comparatively small on the high voltage side.
Ans: A diverter switch is a switching device having contacts with usually four separate
make and brake units and arranged along with separate tap selectors. It is used in an on-
load tap changer of a very large transformer to operate in rapid sequence and kept in a
separate compartment to minimize oil pollution by carbon.
Ans : Bussing is a type of porcelain or ebonite post insulator put on the top or side of the
transformer tank through which connections are made to the external circuits.
139. What type of bushings is generally used according to the voltage of the
transformer?
Ans : The types of bushing are as follows :- Procelain insulator bushing used up to 33KV.
Oil filled bushings consisting of a hollow porcelain cylinder of special shape with a
hollow tube-shaped conductor through its centre used for the voltages above 33 KV.
Capacitor type bussing made to thick layers of bakelite paper alternating with thin
garden layers of tin foil being covered by a porcelain rain shed and filled up with
bitumen in the annular space between the rain shed and the bushing used in outdoor
substation for the voltage above 33 KV.
141. What is the basic difference between distribution transformer and auto-
transformer ?
Ans : The basic difference is that the distribution transformer has two separate windings
and there is no electrical connection between the primary and the secondary while an
auto-transformer has a single winding in which the primary and secondary are
electrically connected.
Ans : (1) Being single winding transformer it requires less copper and becomes lighter in
weight. (2) The cost is less than a two-winding transformer. (3) As it is provided with a
large number of taps desired voltages can be obtained by adjusting suitable taps.
143. Why are the auto transformers not used for high voltages ?
Ans : If an auto-transformer is used in high voltage line a fault in the primary may affect
the secondary side in which case the secondary load equipment may be damaged. So it
is not used for high voltages.
Ans : Auto transformers are used in case of low voltage and low transformation ratio
e.g. starting equipment of three phase induction motor, control equipment of single
phase and three phase electric locomotives, voltage control of power and lighting
circuits, regulating transformers, boosters to raise the voltages in a.c. circuits etc.
Ans : A variable transformer (named as Variac, Dimmerstat etc) is nothing but an auto-
transformer having a continuously variable tap so that any output voltage desired could
be obtained.
146. What are the different forms of connections used in primary and secondary
windings in three phase transformer ?
Ans : The possible connections are as follows :- (1)Star/ Star, (2) Star/ Delta, (3) Delta/
Delta, (4) Delta/Star, (5) Open delta(Vee/Vee) & (6) Scott (Tee/Tee).
Ans : Delta/Delta connection may be used in large low voltage transformers where the
insulation problem is not so urgent.
Interview questions of
Transformer paper-9
151. What are the advantages of having the primary winding connected in delta and
the secondary winding in star ?
Ans : (1) An unbalanced four wire supply may be given. (2) The secondary neutral may
be earthed or it may be utilized for given a four wire supply to provide both three phase
and single phase loads.
(3) Third harmonic voltages are eliminated by the circulation of third harmonic current
in the primary delta.
Ans : Open delta connection is applied where the three phase load is too small and
when one of the transformer in a delta-delta bank is disabled so that service is
continued although at reduced capacity till the faulty transformer is repaired or a new
one is substituted.
Ans : Teaser or Scott connection is applied to supply three phase voltage from a two
phase source and vice versa.
Ans : High voltages terminals are marked with capital letters, N for neutral and A,B,C for
three phases. Corresponding small letters are used for the low voltage terminals. In
single phase transformers, the symbols are A2 A1 and a2 a1 in descending order from left
to right.
Ans : Phasing out of a 3-phase transformer means the detection of same phase
terminals from primary and secondary winding.
Ans : For phasing out of transformers all phases are short circuited except a primary and
a supposedly corresponding secondary. A small direct current is circulated in the
primary and a voltmeter is connected across the secondary. A momentary deflection of
the voltmeter, when the primary current is made and broken, confirms that the two
windings concerned belong to the same phase.
158. What are the symbolic vector groups for identification of 3-phase transformer ?
159. What do you mean by the expression given in name plate of a transformer
vector group Dy11 and impedance voltage 5% ?
Ans : A transformer with vector group symbol (Dy11) means a transformer having
primary winding delta connected and secondary winding star connected and belonging
to group-4 with +30⁰ or-330⁰ phase displacement between primary and secondary
winding as referred to the standard counterclockwise vector rotation. Impedance
voltage 5% means when 5% of normal voltage is applied across one winding it produces
normal voltage is applied across one winding it produces normal full load current to flow
through the secondary winding when its terminals are short-circuited.
Ans : (1) To share the increasing demand of the load. (2) To continue the supply in case
of any fault and periodical maintenance. (3) To get maximum operational efficiency.
163. What are the conditions to be fulfilled before paralleling two three phase
transformers ?
Ans : The secondary voltage will be different for which a circulating current will flow
through the two secondaries if the transformers are connected in parallel. This
circulating current will act as the extra load without any useful work being done and
cause heating of transformers even on no load.
165. Is it necessary for the ratings of two transformers to be the same for parallel
operation ?
Ans : Not necessary but they should share the load in proportion to their ratings.
166. what will be the results of incorrect polarity and unequal percentage impedance
of two transformers connected in parallel?
Ans : Incorrect polarity results in a dead short circuit and due to unequal percentage
impedance the load sharing of two transformers will not be in proportion to their KVA
ratings.
Ans : Since the percentage, impedance determines the voltage drop between no load to
full load, with equal percentage impedances the transformers running in parallel will
share the load in proportion to their capacities. The transformer with a lower
percentage impedance will have a lesser voltage drop and therefore it will take a greater
share of the load. On the contrary, the transformer with a higher percentage impedance
will have a higher voltage drop and it will not take its due share of the load.
168. In parallel operation of two transformers, how will they share a load if their
impedances are equal ?
Ans : Equally.
169. In parallel operation of two transformers if their ratings are equal but
percentage impedances are different how will they share a load ?
Ans : If the ratings of the two transformers are equal but percentage impedances are
different the loads will be shared inversely as the impedances of the transformers
expressed in percent of normal voltage.
170. In parallel operation of two transformers if their ratings and also percentage
impedances are different how do you calculate their load sharing ?
Ans: In the case of different percentage impedances for different ratings of transformers
the percentage impedances have to be converted to the same basic KVA. Then the loads
will be shared inversely as the converted impedances of the transformer.
Interview questions of
Transformer paper-10
171. In parallel operation of transformers of different capacities what should be the
capacity of the smallest transformer with respect to the largest transformer in the
group ?
Ans: The rated output of the smallest transformer in the group should not be less than
331/3 percent of the rated output of the largest transformer in the group.
172. How can you parallel a transformer in group-1 having vector group symbol Yy0,
Dd0, Dz0 with one in group-2 having vector group symbol Yy6, Dd6, Dz6 ?
Ans: This can be done by altering the internal connection only of all the three secondary
winding of any one transformer but not both.
173. How can you parallel a transformer in a group belonging to vector symbol Dy1
or Yd1 or Yz1 with one in another group belonging to voltage symbol Dy11 or Yd11
orYz11 ?
Ans: This can be done by transposing two of the external high voltage connections of
one of the transformers and also the two corresponding low voltage external
connections. The change of any of the internal connections is not necessary.
174. Is it possible to operate a transformer of groups 1&2 in parallel with a
transformer of groups 3&4 listed below ? If not ,why ?
Ans : Transformer in groups 1 & 2 can not be operated in parallel with those in groups 3
& 4 because there is an inherent phase angle difference which can not be corrected.
175. What will be the effect of the change in voltage on the performance of a
transformer ?
Ans : Iron loss varies approximately as square of the voltage. Copper loss and regulation
vary inversely as square of the voltage. Iron temperature increases and copper winding
temperature decreases with increase in voltage & vice versa. Efficiency at fractional load
decreases and that at full load increases with increase in voltage and vice versa.
Ans: Iron loss and temperature will vary inversely as the frequency. Copper loss is
independent of frequency. So total loss increases with the decrease in frequency.
Accordingly, efficiency decreases with the decrease in frequency. The regulator at low
power factor decreases with a decrease in frequency and vice versa.
178. What are the protective equipment required for a large transformer ?
Ans : The protective equipments are i) Buchholz relay,
ii) Over current relay,
iii) Differential relay,
iv) Earth leakage relay &
v) Lightning arrestor.
Ans : When the heat produced by any internal fault inside the tank is intensified then it
decomposes the oil and liberates gas.
Ans : The function of Buchholz relay is to actuate an alarm in case of small amount of
gas or trip the circuit breaker in case of excessive gas by making use of that gas liberated
inside the transformer due to any internal fault. It also detects the accumulation of air
on account of low oil level or faulty oil pumps.
181. What is the lowest capacity of the transformer on which the provisions of gas
pressure type protection is obligatory ?
Ans : On transformers of rating 1000 KVA and above the provision of gas pressure type
protection with Buchholz relay is obligatory as per I.E. rules.
Ans : The Buchholz relay is installed in the pipe connecting the transformer tank and the
oil conservator.
183. what should be the angle of inclination of the connecting pipe of the Buchholz
relay with the horizontal plane ?
Ans : The angle of inclination of the axis of the pipe with horizontal plane should be 10⁰
to 11⁰ .
184. What should be the size of the connecting pipe of Buchholz relay ?
Ans : The nominal pipe bore diameter should be 25 mm for transformers up to 1000
KVA, 50 mm for transformers exceeding 1000 KVA but up to 10000 KVA and 80 mm for
transformers exceeding 10000 KVA capacity. The length of the pipe of the lower section
between relay and transformer tank should be more than 5D and that of the upper
section between relay and conservator tank should be more than 3D (where D is the
internal diameter of the connecting pipe).
Ans : The function of overcurrent relay is to protect the transformers against overload
and short circuit.
186. What is the lowest capacity of the transformers on which the provision of
differential protection is obligatory ?
187. What do you mean by instrument transformers and why are they used ?
188. How do the instrument transformers differ from the power transformer ?
Ans : The instrument transformers differ from the power transformers mainly by their
volt-ampere rating. The instrument transformers have a very low rating of only a few
tens of VA e.g 10VA, 50VA, 100VA etc. whereas the power transformers have high KVA
rating e.g 25KVA, 200KVA, 500KVA, 1000KVA even up to 1000MVA.
Ans : The true ratio of a current or a potential transformer is the ratio of r.m.s primary
current or voltage, as the case may be, to the r.m.s secondary current or voltage under
specified conditions.
Transformer interview
Questions & Answers paper-11
191. what is called marked ratio of an instrument transformer ?
Ans : The making ratio of a current or a potential transformer is the ratio of the primary
current or voltage, as the case may be, to the secondary current or voltage as given on
the rating plate.
Ans : The ratio correction factor is that factor by which the marked ratio of a current or
a potential transformer must be multiplied to obtain the true ratio. So R.C.F = (True
ratio)/(Marked ratio.)
Ans : The two types are (1) Air-cooled current transformers and (2) Oil immersed
current transformers.
194. What are the types of current transformers according to the magnetic circuit ?
Ans : There are three types of current transformers in common use according to the
magnetic circuit, namely, “Ring type”, “Core type” and “Shell type”.
Ans : There are two of errors, e.g. ratio error and phase difference error. The ratio error
is the amount by which the secondary current differs from exact proportionality to the
primary current and is expressed as a percentage of the rated secondary current. The
phase difference error is the angle by which the secondary current differs in phase form
the primary current and is expressed in minutes of arc.
197. At what load the phase angle error of a c.t. will be negative ?
Ans : At the load of very low power factor the phase angle error will be negative.
198. why are the errors of a C.T. generally greater with relatively small loads than at
rated full load?
Ans: The errors are generally increased with relatively small loads than at rated full load
due to greater proportion of exciting current to the reversed secondary current .
199. If the core of a C.T. is permanently magnetized how will you demagnetize it ?
Ans: To demagnetize the core of a C.T. a variable resistance of high value is connected
across the secondary terminals and with full rated current flowing through the primary
the resistance is gradually reduced to zero.
Ans : Turn compensation means to keep the number of secondary turns one or two less
than that obtained by normal ratio and it is done to reduce the current ratio error.
201. How are the ratio error and the phase error of a C.T. improved ?
Ans : The errors of a C.T. can be improved by the following methods – By using high
permeability and low loss magnetic material of the core. By reducing the length of the
flux path in the core and increasing the area of the path with all joints reduced to a
minimum or avoided altogether. By increasing the primary ampere-turns. By using one
or two turns less in the secondary winding. By reducing the internal secondary burden
as far as possible. By keeping the connected burden on the secondary as small as
possible. By specifying the rated burden as near to the actual burden as possible.
202. What are the categories of current transformers and their applications ?
Ans : There are two categories of C.Ts, e.g, Measuring current transformers are used
with ammeters, wattmeters, KVA meters, KWH meters, power factor meters etc.
Protective current transformers are used with over current relays, earth fault relays,
differential protection, impedance protections etc.
204.why is only one turn of very thick conductor used in the primary of a current
transformer ?
Ans : In the primary of a current transformer only one turn of very thick conductor
having negligible resistance is used not only for reducing the induced voltage but also
for reducing the voltage drop to nearly zero. As large current flows through the primary
and small current as per current ratio flows through the secondary if one turn is
selected for primary the secondary turns will be smaller.
205. What materials are used for the core of a C.T. & why ?
Ans : In order to reduce the ampere turns required the core of a C.T. must have high
permeability, small iron loss, a low flux density and low phase difference error. Two
suitable materials are Silicon steel having the maximum permeability of 4500 at flux
densities in the neighborhood of 5000 lines/cm2 with phase difference error of 1.5 to 2⁰
. Mumetal, a nickel-iron alloy containing a small amount of copper having the maximum
permeability of about 80000 at flux densities of about 3500 lines/cm2 with phase
difference error of below 0.5⁰. As the nickel-iron alloy reduces the magnetizing current
and core loss to about 10% of that of the corresponding silicon steel values, Mumetal is
best suited for the core of a C.T. where a high degree of accuracy is desired.
207. What are the basic differences between current transformers and potential
transformers ?
Ans : (1) A C.T . is connected in series with the line whereas a P.T. is connected across
the supply lines. (2) In a C.T the number of turns is inversely proportional to the current
but in a P.T. the number of turns is directly proportional to the voltage. (3) In a C.T. the
primary has one or more turns of heavy conductor and the secondary has a large
number of turns of thin wires whereas in a P.T. the primary has a large number of turns
of thin wires and the secondary has a few number of turns of comparatively thick wires.
208. What are the types of potential transformers ? State the applications of
potential transformers ?
Ans : There are two types of potential transformers. E.g. Electromagnetic type potential
transformer, in which primary and secondary windings are used on the magnetic core
like usual transformers. Capacitor type potential transformer, in which a series capacitor
group is used with an auxiliary voltage transformer. The primary voltage is applied to
the series capacitor group and the voltage across one of the capacitor is taken to the
primary of the auxiliary voltage transformer. Then the secondary of the auxiliary voltage
transformer is finally taken to the metering and/ or control panel. Potential
transformers are used with voltmeter, KWh meter, power factor meter, frequency
meter, protective relays for the purpose of measurement and protection.
Electromagnetic type potential transformers are used upto 66KV lines while capacitor
type potential transformers are used for the voltages 66KV and above.
Ans : In single phase potential transformer the primary terminals are marked with
letters V1,V2and the secondary terminals bearing similar markings are encircled. In the
case of tapped windings the primary terminals are marked with the letters V1,
V2,V3,V4 and the secondary terminals bearing similar markings are encircled. In three
phase star/star potential transformer the primary terminals are marked with the letters
A B C N and the secondary terminals are marked with similar letters but encircled. The
terminal marked with the letter ‘N’ is the neutral.
210. What do you mean by the “ratio error” and “phase difference error” of
potential transformer ?
Ans : The amount by which the secondary voltage of a potential transformer differs in
magnitude from exact proportionality to the primary terminal voltage is called the ratio
error of a potential transformer. The angle by which the secondary voltage of a
potential transformer differs in phase from the primary terminal voltage is called the
phase difference error of a potential transformer.
Transformer interview
Questions & Answers paper-12
211. What will be the effect of open circuiting the secondary of a C.T. ?
Ans : If the secondary of a C.T. is open circuited the whole current in the primary
becomes magnetizing current & a dangerously high voltage will appear across the
secondary which may cause insulation breakdown, damage to the magnetic property of
its iron core, overheating and also death to life. For these reasons open circuiting of a
C.T. should never be permitted.
212. What is the usual limit of current and voltage above which C.T. and P.T. are
generally used ?
Ans : The standard secondary rating of P.T. is 110 volts and that of C.T. is 5 amps.
Ans : The maximum load in volt amperes (VA) which may be applied across the
secondary terminals of P.T. or C.T. is known as ‘burden’ of a P.T. or C.T. It depends upon
the number of instruments or relays connected and their individual ratings.
215. What should be done before disconnecting an ammeter from the secondary of
a C.T. ?
Ans : The secondary winding of a current transformer should always be short circuited
before disconnecting an ammeter.
216. What is the basic difference between a power transformer and a potential
transformer according to the operating condition ?
Ans : Though the primary winding in both power transformer and potential transformer
are energized continuously at a substantially constant voltage, the secondary of a power
transformer is connected to a load which may vary between zero and the maximum
which the transformer is capable of carrying whereas the load or burden connected to
the secondary of a potential transformer does not vary as a rule. The permissible
voltage drop in potential transformer between zero and maximum burden is much
smaller than the corresponding limit in a power transformer.
217. What precautions do you observe when working with instrument transformers
?
Ans : When working with C.T. the secondary should be short circuited and grounded. No
fuse should be inserted in the secondary circuit of C.T. because fuse may blow and
produce an open circuit. When working with P.T. the secondary should never be short
circuited. One end of the secondary should be grounded and fuse should be provided
both on the primary and the secondary circuit. one end of the secondary should be
grounded and fuse should be provided both on the primary and the secondary circuit.
218. How are the earthing arrangements made for the following :-
a) 132 KV or 220 KV generator transformers,
b) 11Kv or 33KV substation transformers,
c) 11KV/0.433KV distribution transformers,
d) Transformer with delta winding &
e) Instrument transformer ?
Ans : (a) The metallic frame is earthed by two separate and distinct connections with
earth. The neutral point is directly earthed by not less than two separate and distinct
connection with earth each having its own electrode thus permitting the grading of
insulation in the transformer form the terminal end to the neutral point.
(b) The frame is earthed by two separate earth electrodes as above but for neutral
earthing resistance earthing not less than two numbers may be used to limit the fault
current which is expected to be too high in this case.
(c) The frame is earthed by separate earth electrodes and the neutral of the secondary
star winding is erathed by not less than two nos separate and distinct connections
directly to earth having its own electrode.
(d) The frame is earthed by two separate earth electrodes . An earthing transformer
may be used to get the star neutral point which may be earthed by two separate
connections to the earth either directly or through a resistance if desired.
(e) Cases or frames of instrument transformers, the secondary winding of current
transformer and one point of the secondary winding of potential transformer shall be
earthed which may be done by connection to the earth bus.
Ans : Tertiary winding is a delta connected additional auxiliary winding used with three
phase star-star connected transformers which is wound on the same core and separated
from primary and secondary main winding . The function of the tertiary winding are as
follows :-
(i) It prevents the oscillation of the neutral point i.e stabilizes the neutrals of both
primary and secondary winding by reducing third harmonic voltage components.
(ii) It permits the transformation of unbalance three phase loads or single phase loads
only by limited the voltage unbalance.
(iii) It can supply an auxiliary load at low voltage mainly for station loads.
221.What are the important aspects related with the installation &operation of
power transformers ?
223. What are the tools and equipments required for the erection of a transformer ?
Ans : For proper ventilation the transformer should be kept well away from the to make
free movement of air round all the four sides. To ensure proper air circulation for the
efficient cooling of the transformer a minimum area of 1 sq. meter for inlet per 1000
KVA should be provided as near the floor as possible and a minimum area of 2 sq.
meters for outlet per 1000 KVA should be provided in the opposite side of air inlet as
high as the building allows to enable the heated air to escape readily and be replaced by
cool air.
225. In a transformer cubicle proper air circulation can not be achieved due to wall
blocking. What kind of arrangement is to be provided in the cubicle for efficient
dissipation of heat form the transformer ?
Ans : In addition to the provision of proper air inlet and outlet fans are provided extra
for cooling the transformer.
226. What is minimum recommended spacing between the walls and transformer
periphery in case (a) wall on one side, (b) wall on two sides, (c) wall on three sides
and (d) wall on all sides as in an enclosed room ?
Ans : (a) 0.5 meter (b) 0.75 meter (c) 1.00 meter & (d) 1.25 meters.
Transformer interview
Questions & Answers paper-13
227. What should be the minimum clearance between the highest point of the
conservation tank and the ceiling of the transformer room ?
228. What arrangement should be provided where two or more transformers are
installed side by side ?
Ans : If two or more transformers are installed side by side they shall be separated by
fire separation walls. Fire separation walls are deemed to be adequate from fire safety
point of view.
229. What type of oil draining arrangement should be provided for a transformer
having more than 2000 liters of oil ?
Ans : Oil soak pit filled with sand and gravels should be provided where the oil capacity
exceeds 2000 liters of oil. The capacity of the oil soak pit shall be such that to soak the
entire oil content of the transformer.
Ans : As a result of tests carried out if the presence of moisture is indicated or the oil
does not withstand the tests as recommended by the manufacturer or the insulation
resistance readings are not satisfactory it shall be necessary to dry out a transformer.
231. What are the methods of drying out transformer core and coils ?
Ans : i) Drying with core and coils in oil by short circuit method.
ii) Dering with oil removed by external heat.
iii) Drying under vacuum.
232. What are the precautions to be taken when drying out of transformers ?
Ans : (i) The transformer should never be left unattended during drying out. This must
be done under continuous and competent supervision.
(ii) The temperature should be carefully observed which should not exceed 90⁰C.
(iii) Only spirit type thermometer should be used.
(iv) No naked lights and flames should be allowed in the vicinity of a transformer being
dried and the fire fighting equipment should be kept ready during the dry-out period.
(v) Low voltage hand lamp should be used for inspection of the tank from inside.
235. What are the different methods of purifying and drying out transformer oils ?
Ans : The neutralization value also known as total acidity is the measure of free organic
and inorganic acids present together in the oil which is expressed in terms of the
number of milligrams of potassium hydroxide required to neutralize the total free acids
in one gram of the oil.
238. what is the effect of the presence of moisture and impurities in oil ?
Ans : The presence of moisture and impurities in the oil decreases the dielectric strength
of the oil and also reduces the insulation resistance of the transformer.
239. What is the effect of presence of air bubbles in the transformer oil ?
Ans : When air remains in the oil the oxygen reacts on the cellulose of the insulation and
the decomposition products of the cellulose lead to the formation of organic acids
soluble in oil and also sludge which blocks the free circulation of the oil.
Ans : varnishes of the oxidizing type readily reacts with the transformer oil and
precipitate sludge on the windings. But synthetic varnishes having acid inhibiting
properties generally delay the natural formation of acid and sludge in the oil.
Ans : Slackness of winding may cause a failure due to repeated movement of coils which
may be the conductor insulation at some places and lead to an inter-turn failure. The
coils may also get displaced under load conditions or momentary short circuit which
may cause electric and magnetic unbalance and produce even greater displacement.
Ans : It can be detected by crackle test. For this test some quantity of oil is heated in a
test tube over a silent flame or a red-hot metal rod is dipped in a cup containing oil. Any
cracking sound, in either case, indicates the presence of water.
Ans : Neoprene bonded cork gasket is generally used in between two metal surfaces in
transformer assembly which is squeezed by tightening nut bolts of the flanges to make a
leak-proof air-tight and oil tight joint.
244. What are the possible causes for abnormal noise in a transformer ?
Ans : External noise is caused by a loose nut-dolt on the transformer cover and its
accessories and internal noise is caused by slackness of winding or capacitance
discharge.
Ans : If a d.c. supply is connected across the primary winding it will produce a steady flux
in core and therefore it will not induce any voltage. Secondly, the transformer winding
has more reactance and very little resistance. Since the reactance has got no effect with
d.c. voltage the transformer will take high current due to low ohmic resistance and
absence of self induced counter e.m.f. As a result the winding will be burnt out without
transforming the electrical energy.