0% found this document useful (0 votes)
169 views4 pages

OE Spec MTU12V2000DS850 3D FC 50Hz 2 14

This document provides specifications for a 850kVA diesel generator set from MTU. Some key details include: - It is a standby power generator set with a frequency of 50Hz and output of 850kVA - The generator can output voltages of 380V, 400V, and 415V - It features a MTU 12V2000 DS850 diesel engine that is air cooled and has industry-leading fuel efficiency and reliability - The generator meets various certification standards and has standard equipment like a radiator, battery, and controls - It provides power factors of 0.8 and can support loads up to 85% of its rating for 24 hours

Uploaded by

Hoàng Thắng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
169 views4 pages

OE Spec MTU12V2000DS850 3D FC 50Hz 2 14

This document provides specifications for a 850kVA diesel generator set from MTU. Some key details include: - It is a standby power generator set with a frequency of 50Hz and output of 850kVA - The generator can output voltages of 380V, 400V, and 415V - It features a MTU 12V2000 DS850 diesel engine that is air cooled and has industry-leading fuel efficiency and reliability - The generator meets various certification standards and has standard equipment like a radiator, battery, and controls - It provides power factors of 0.8 and can support loads up to 85% of its rating for 24 hours

Uploaded by

Hoàng Thắng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DIESEL GENERATOR SET

AIR CHARGE-AIR COOLING


850kVA/50 Hz/Standby Power (Fuel Consumption Optimized)
380 - 415V

Optional equipment shown. Standard equipment may vary.

BENEFITS

// Industry-leading average load factor // Best-in-class reliability and availability


// Outstanding fuel economy // Lifting vertically or with diagonal pull
// Optimized maintenance intervals // Compact design
// Low installation costs

SYSTEM RATINGS➀
Standby Power MTU 12V2000 DS850 MTU 12V2000 DS850 MTU 12V2000 DS850

Voltage (L-L) 380V 400V 415V


Phase 3 3 3
PF 0.8 0.8 0.8
Hz 50 50 50
kW 680 680 664
kVA 850 850 830
Amps 1291 1227 1155
Generator model 574RSL7066 574RSL7066 574RSL7066
Temp rise 150 °C/40 °C 150 °C/40 °C 150 °C/40 °C
Connection 6 LEAD HI WYE 6 LEAD HI WYE 6 LEAD HI WYE

➀ Power available up to 40°C/400 m


2 / // / 50 Hz 850 kVA

CERTIFICATIONS AND STANDARDS


// Engine-generator set is designed and manufactured in // Power Rating
facilities certified to standards ISO 9001:2008 and - Permissible average power output during 24 hours of
ISO 14001:2004 operation up to 85%
// Performance Assurance Certification (PAC)
- Engine-generator set tested according to ISO 8528-5 for
transient response
- Verified product design, quality and performance integrity
- All engine systems are type and factory tested

STANDARD EQUIPMENT➀
// Engine // Generator

Air filters NEMA MG1, IEEE and ANSI standards compliance for temperature rise
Oil pump for draining and motor
Full flow oil filters VDE 0530, IEC 60034-1, BS 4999, BS 5000, CSA 22.2-100, AS 1359
Closed crankcase ventilation Sustained short circuit current of up to 250% of the rated current
Jacket water pump for up to 10 seconds
Thermostats Self-ventilated and drip-proof IP23
Exhaust manifold – dry Superior voltage waveform
Belt driven radiator fan Digital, volts-per-hertz regulator
Radiator – unit mounted No load to full load regulation
Electric starting motor – 24V Brushless alternator with brushless pilot exciter
Governor – electronic isochronous 4 Pole, rotating field
Base – formed steel 150 °C maximum standby temperature rise
SAE flywheel & bell housing Heavy duty shielded ball bearings with a minimum B-10 life of
Charging alternator 40,000 hrs
Flexible fuel connectors Flexible coupling
Flexible exhaust connection Full amortisseur windings
3-phase voltage sensing
±0.25% voltage regulation
100% of rated load – one step according to NFPA 110
3% maximum harmonic content

➀ Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.
3 / // / 50 Hz 850 kVA

STANDARD FEATURES➀
// The engine-generator set complies to G3 // 12V2000 diesel engine (23,88 liter (1457 cu inch)
// Engine generator set tested according to ISO 8528-5 for displacement; 4-stroke)
transient response // Engine-generator resiliently mounted
// Accepts rated load in one step as per NFPA 110 // Complete range of accessories
// All engine-generator sets are type and factory tested // Brushless, rotating field generator (PMG excitation;
// MTU Onsite Energy is a single source supplier 250% short circuit capability; 2/3 pitch stator windings)
// Global product support // Complete system metering
// Cooling System (integral set-mounted; engine driven fan) // LCD display

APPLICATION DATA
// Engine // Fuel Consumption➁
gal/hr l/hr g/kwh
Manufacturer MTU At 100% of power rating: 49 187 203
Model 12V2000G65TD At 75% of power rating: 37 140 202
Type 4-Stroke At 50% of power rating: 25 96 208
Arrangement 12-V
Displacement/cylinder: l (cu inch) 1.99 (121) // Cooling/Radiator System
Bore: mm (inch) 130 (5.1)
Stroke: mm (inch) 150 (5.9) Ambient capacity of radiator: °C 40 (optional 50)➂
Compression ratio 16:1 Max. restriction of cooling air, intake,
Rated speed rpm 1500 and discharge side of rad.: kPa (in. H20) 0,2 (0,803)
Engine governor Electronic isochronous Water pump capacity: l/min (gpm) 667 (176)
Max power: kWm (bhp) 765 (1026) Heat rejection to coolant: kW (BTUM) 330 (18,767)
Speed regulation ±0.25% Heat rejection to after cooler: kW (BTUM) 160 (9,099)
Air filter Dry Heat radiated to ambient: kW (BTUM) 40 (2,275)
Engine coolant capacity: l (gal) 90 (24)
// Lube Oil Capacity Coolant to cooler temperature: °C (°F) 95 (203)

Total oil system: l (gal) 77 (20) // Air Requirements➃

// Electrical Aspirating: m3/min (SCFM) 54 (1905)


Air flow required for rad.
Electric Volts DC 24 cooled unit: m3/min 1698 (59905)
Cold cranking amps under -17.8 °C (0 °F) 1000
// Exhaust System
// Fuel System
Gas temp. (stack): °C (°F) 565 (1049)
Fuel supply connection size M22x1,5 - 60°/Male Gas volume flow
Fuel return connection size M12x1,5 - 60°/Male temp: m3/min (SCFM) 150 (5292)
Maximum fuel lift: m (ft) 5 (16) Maximum allowable
Recommended fuel see MTU fluids & lubrication spec. back pressure: kPA 8,5 (34)
Total fuel flow: l/hr (gal/hr) 480 (127)

➀ Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.
➁ Values in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
➂ System ratings at 50°C may differ.
➃ Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
4 / // / 50 Hz 850 kVA

WEIGHTS AND DIMENSIONS

Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.

System Dimensions (L x W x H) Weight (dry)


Open Power Unit (OPU) 4242 x 1750 x 2072 mm (167 x 69 x 82 inch) 5477 kg (12,075 lbs)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.

SOUND DATA
// Consult your local MTU Onsite Energy distributor for sound data.

EMISSIONS DATA
// Consult your local MTU Onsite Energy distributor for emissions data.

RATING DEFINITIONS AND CONDITIONS


// Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for

Subject to change. | 3236091 | Edition 02/14 | ENC 2014-07.


the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1,
BS 5514 and AS 2789. Average Load Factor: ≤ 85%. Operating hours/year: max. 500.
// Deration factor:
Altitude: Consult your local MTU Onsite Energy distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy distributor for temperature derations.

Materials and specifications subject to change without notice.

MTU Onsite Energy


A Rolls-Royce Power Systems Brand

www.mtuonsiteenergy.com