Teles Control
Teles Control
manual
Teles Controller
Teles Controller Manual
CONTENT
1. Introduction…………………………………………………………………2
2. Shape and connection of the controller……………………………………2
3. Operation panel…………………………………………………………… 5
4. Installation guide.………………………………………………………… 6
5. Instruction of control and operation………………………………………7
6. Measuring data…………………………………………………………… 10
7. Warning, Pre-alarm and Stop Fault…………………………………… 11
8. Parameters setting…………….……………………………………………12
9. LCD display and menu system…………………………………………… 14
10. Communication function………………………………………………… 17
11. Preparation before use…………………………………………………… 22
12. Troubleshooting…………………………………………………………… 24
1
Teles Controller Manual
1. Introduction:
Teles is a kind of intelligent controller of generator which adopt high grade CMOS chip. It can configure the
control procedure and protection parameters of the generator, including lots of function such as measuring,
controlling, protection, three remote and so on, which completely satisfied the automatic controlling requirement
of different generator sets for the generator user or factory.
The controller measure and display all parameters the generator output, and the rotating speed, oil pressure,
temperature, DC source voltage, running time of the engine and so on. All of the voltage measured in real virtual
value to ensure the accuracy of the data.
Including big LCD display and menu selection for Chinese and English.
The keys on the control panel are used to select the control mode, start the running procedure, display data, and
modify the running protection parameters. The LED indicates the operating mode of the controller and the
running state of the generator sets. LCD display each measured parameter and state.
The controller is integrated closely by aluminum alloy panel and steel shell which has been spurt powder. All
connection of the controller are connected by pin-like terminal with lock, such device can be connected、
moved 、maintained and replaced easily and conveniently.
This manual is available for the generator intelligent controller Teles only, which you should
carefully read before use
A 1 2 3 4 B 5 6 7 8
RS-CONNECTOR
C 9 10 11 12 13 14 15 16 D 17 18 19 20 21 22 23 24 25 26 27 28
2
Teles Controller Manual
NOTE:The shell of the controller should be grounded to earth, surge of the electricity system and transient
shock to the meter can be reduced by the perfect low ground impedance.
Running temperature of the controller -20~70℃
Storage temperature of the controller -30~80℃
2.2 Connection port:
Pin NO. Function Signal Line
A1 Phase A V input 0-300VAC 1mm² line
A2 Phase B V input 0-300VAC 1mm² line
A3 Phase C V input 0-300VAC 1mm² line
A4 N zero line 1mm² line
3
2.3
G Generator
F1 1
F2 2
Teles Controller Manual
F3 3
5
Typical wiring diagram:
6
RS CONNECTOR
FAULT
PRE.ALARM
IDLE
RUNNING
7
8
AUX SUPPLY
(8-35VDC)
4
28 27 9 12 10 11 13 14 15 16 20 21 22 23 24 17 18 19 25 26
- +
F4 F5
(2A) (10A) 充电机
Speed sensor
(PICK-UP)
油门 起动
(Fuel) (Crank)
DCV
Temperature
E.stop
Remote start
T-sensor
Oil sensor
Pressure
P-sensor
(standby)
Loading output
(3P&N)
Note:cathode of the battery and shell of the contoller must be grounded to earth properly
Teles Controller Manual
3 Operation panel
The whole Operation panel is divided into three parts: LED display for measuring parameters、operating keys
and running-status LED indicate。
5
Teles Controller Manual
START Key/LED
The key is used for generators manually startup. And when the
controller is in “manual-operation mode”, press this key to start the
generator. Till the controller performing the start procedure to the Gen
set run in normal, the LED above the key on. After the Gen set running
normally, the LED above the key on.
STOP/RESET key/LED
Used to stop the generator by hand, when the controller set in “MAN”
mode, this key could stop the generator. Press this key more than 2
seconds can release the fault stop lock if there is fault output. (When
the controller performing the stop procedure, the indicator light above
the key illuminate. If failed to stop, the light flash.)
LAMP TEST /MUTE key
Alarm mute and lamp test key. Press the key more than 2 seconds, all
LEDs on the panel will light. It used to test all LEDs on the panel.
When Pre-alarm or fault alarm occur, press this key can mute the
buzzer. At the same time the light above the key illuminate. Press it
again will cancel mute. If the controller still in fault, the buzzer will
keep alarm.
4 Installation guide
4.1 Hatch size for panel installation as the figure attached.
Four special screws fix the controller. If the shell of the controller is installed on the body of a generator
directly or other violent vibratory device, preventing device must be installed.
4.2 Connection for control line please refer to the diagram attached and the typical wiring
diagram 2.3 above.
4.3 Installation for oil pressure and temperature sensor of the engine:
6
Teles Controller Manual
7
Teles Controller Manual
Press “TEST” (for 2 seconds), the LED above illuminate, the controller
then operating in “TEST”
When the controller run in TEST, or the remote control start signal
able in Auto, or press “START” in MAN, the controller begin to
delay the start procedure, the light above the key will bicker.
The LCD display the count for start delay (not in “MAN”) START 00:09
Fuel relay action, the fuel electromagnetic valve of the engine open.
CRANK 1
After delay for 200 milliseconds, the start relay active and crank
begin.
When the running speed of the engine reach the crank cutout speed,
SAFETY-ON DELAY 00:08
the controller will stop the start output and begin the safety-on delay.
U=380V I=0A
After the controller has detected the normal running speed, output P=0kW F=50Hz
voltage, pressure, temperature has been setup, and no other fault the
SP=1500rpm OP=465kPa
same time, then display the parameters as right.
(Scroll page for detail) TEMP=70℃ Bat=24V
RUN
When the remote control start signal valid, the start delay will active and begin to time. During the delay, if
the remote start signal invalid, start delay will instantaneously stop, the controller will stop the start procedure,
and return to original state“READY” after the time for fail to start out.
During cranking or idle, if the remote control start input signal is invalid, the controller stop the followed
start procedure and close all output for relay control, then stop the start process and return to original state
“READY” after the time for fail to start out.
Note: when cranking, the engine ignited, while the alternator output frequency reach the preset frequency,
the start motor de-energized:
Or de-energized the motor through the following way
a、 The magnetism speed pickup device mounted on the flywheel of the engine has detected the frequency
reached preset.
b、 The output voltage of the alternator reach 80% of the rated voltage.
c、 The low oil pressure switch of the engine open.
8
Teles Controller Manual
If it occurs FAIL TO START fault, the operator must check the whole
“Genset” system. and confirm the fault and eliminate them, then press
“ STOP/RESET” key to unlock the fault-locking state, and reset the
controller again.
STOP
The Fail To Stop time begin, the LCD display:
00:24
9
Teles Controller Manual
When the stop failed time beyond, the engine still run, the controller will ALARM:
send an alarm, the LCD will display: STOP FAILURE
The engine stop slowly during the Fail To Start permission time, and the LCD
READY
display:
5.7 The oil electromagnetic valve is the start running and stop process of the generator of
normal open type.( Different from normal closed type).
Start control process:
When start running, oil relay of the controller take no action, no power in the oil electromagnetic valve,
namely the oil electromagnetic magnet take no action.
Stop control process:
The control at the begging of the stop control process output oil electromagnetic valve source, oil
electromagnetic valve action, the engine begin to stop. Then powered down after for the delay according to the
fail to start delay setting.
Other control process is the same to the engine of normal closed oil electromagnetic valve.
10
Teles Controller Manual
Battery voltage (V)
11
Teles Controller Manual
Low Oil Pressure After the safety-on time-delay timeout, the controller detects the oil pressure switch closed,
the engine stop instantaneously, and the LCD display “ALARM: LOW OILPRESS”, the fault indicator
light “LOW OIL PRESSURE”, the buzzer warn.
H Temperature The controller has detected the T-sensor switch of the engine closed, the engine stop
instantaneously, the LCD display “ALARM:COOLANT TEMP”,and the indicator light“HIGH
TEMPERATURE” illuminate, the buzzer warn.
Overspeed The controller has detected the running speed of the engine beyond the overspeed fault setting
value, the engine stop instantaneously, the LCD display “ALARM:OVER SPEED””,and the indicator
light “OVERSPEED” illuminate, the buzzer warn.
Under Speed The controller detects the running speed of the engine lower than the low speed fault value,
the engine stop instantaneously, and the LCD display “ALARM:UNDER SPEED”,the buzzer warn.
High Voltage The controller detect the output voltage of the generator higher than the high voltage fault
value, the engine will stop after confirming the delay, and LCD display “ALARM:V HIGH”,the buzzer
warn.
Low Voltage After the safety-on delay timeout, the controller detect the output voltage of the generator
lower than the low voltage fault value, the LCD will display “ALARM:V LOW””after confirming the
delay,and the buzzer warn.
Overcurrent The controller detect the output current of the controller higher than the over current fault
value, the engine will stop after confirming the delay, and the LCD display “ALARM:I HIGH”,the
buzzer warn.
Standby Output If set the aux input to fault stop, then when the signal at the input is valid, the engine will stop
instantaneously, and the LCD display “ALARM:EXT. ALARM”,the buzzer warn.
NOTE:
The data of low oil pressure pre-alarm is from the measuring of the oil pressure sensor, and the data of
low pressure stop fault is from the measuring of the oil pressure sensor (set for no use at factory) or the
oil pressure switch state.
The data of high temperature pre-alarm is the water position from the measuring of the temperature
sensor, and the data of high temperature stop fault is the water position from the measuring of the
temperature sensor (set for no use at factory) or the temperature switch state.
The rotating speed of the engine typically from the measuring frequency of the speed sensor mounted
on the flywheel of the engine, if no speed sensor equipped in the system, the controller will take the
voltage frequency of the generator output as the controlling and fault protection parameter. To be
convenient for the user, part of the data is rotating speed, RPM=HZ*30.
Generator fault during the running of the generator: stop instantaneously after the high temperature , or
low pressure, or overspeed, or under speed occur. But the low speed and low pressure required the idle
delay set to 0 (without idle function) to active protection, or it won't be active.
8 Parameter Setting
8.1 SYSTEM
NO. Item Preset Range
1.0 QUIT)
1.1 ( CT) 60 1~5000
1.2 VT) 1 1~100
1.3 Comm Address) 1 1~255
12
Teles Controller Manual
1.4 (Default settings)
1.5 Language> English/中文 English 中文/English
1.6 Firmware update
8.2 GENERATOR
NO. Item Preset Range
2.0 QUIT
2.1 V Low Alarm 0V AC45~20000V 0 (no setting)
2.2 V Low preALM 198V AC45~20000V 0 (no setting)
2.3 V High preALM 253V AC45~20000V 29999 (no
29999 i )(no
29999
2.4 V High Alarm AC45~20000V
i )
2.5 I High preALM 9999A 0~9999A 9999 (no setting)
2.6 I High Alarm 9999A 0~9999A 9999 (no setting)
2.7 Alarm delay 10s 0~600S
8.3 ENGINE
NO. Item Preset Range
3.0 QUIT
3.1 Nominal speed 1500 99-9999 RPM
3.2 Pickup frequency 3000 1-9999 Hz
3.3 Set pickup now
3.4 Fuel mode 0 0~1 0(NC) 1 (NO)
3.5 T-sensor mode 0 0~8 0 (no use)
3.6 P-sensor mode 0 0~9 0 (no use)
0 (no use) 1
3.7 H-sensor mode 0 0~1
(use)
3.8 Start delay 10s 0~300 S
3.9 Crank attempt 3 1~10 S
3.10 Crank time 8s 0~30 S
3.11 Crank reset 15s 0~300 S
3.12 Crank disconnect 300RPM 1-9999 RPM
3.13 Idle delay 0秒 0~9999 S
3.14 Safety-on delay 60s 0~600 S
3.15 Cooling delay 300s 0~600 S
3.16 Stop delay 20s 0~60 S
3.17 Under SP Alarm 0 RPM 0-9999 RPM 0 (no setting)
3.18 Under SP preALM 1440 RPM 0-9999 RPM 0 (no setting)
3.19 Over SP preALM 1600 RPM 0-9999 RPM 9999 (no setting)
3.20 Over SP Alarm 1710 RPM 0-9999 RPM 9999 (no setting)
3.21 Oil-P low Alarm 140KPa 50~300Kpa 0 (no setting)
3.22 Oil-P low preALM 220KPa 50~300Kpa 0 (no setting)
3.23 Coolant preALM 95℃ 70~160℃ 9999 (no setting)
3.24 Coolant Alarm 105℃ 70~160℃ 9999 (no setting)
3.25 Batt low preALM 8.0V 1~25V 0 (no setting)
3.26 External. Alarm 0 0 unit V, 1 unit %, measuring 0-5v
13
Teles Controller Manual
signal.
2 unit %, self determine the input
3.27 External analog 2
according to the resistance type and
sensor data.
Temperature sensor
NO. Type
0 NOT USE
1 VDO 120 degrees C
2 Datcon high
3 Datcon low
4 Murphy
5 Commis
6 TS120
7 KP-T01
8 User define
light. Press any key for a while to turn off the background light. Set a different parameter in every page and
controlled upon it, each electricity parameter of load displayed in main page, press “ ”and“ ”scroll to
display each electricity parameter and measuring data. If there is no fault occur, LCD hold the main page, and
when fault occur, LCD display the fault information in the state screen instantaneously. When more than one
fault occur, LCD display one fault state of them. Press “ ”and“ ”refer to the running parameters.
Increase and decrease by degrees to set and adjust the parameter. When press the increase or decrease key
for a while, the ones digit changes one by one, and then the tens digit change after ten changes, the rest may be
deduced by analogy. Press“ ”in the main page two seconds to enter setting state, then press “ ”and
“ ”to look over in the menu of the same level, and press “ ”to enter next submenu to select and adjust
the item, press “ ”to adjust. When indicate to enter password, enter “ ”“ ”“ ”“ ”,
then press“ ”two seconds to quit setting state.
14
Teles Controller Manual
15
Teles Controller Manual
Press “ ”for two seconds to enter the configure menu, and <<SETTING/参数设定>>
then the LCD display: 0.QUIT
Press “ ”nine times and then press “ ”, the LCD will 9. Crank attempt
display: =3
Press “ ”will indicate to enter password, enter the password: 9. Crank attempt
Password:****
“ ”“ ”“ ”“ ”
16
Teles Controller Manual
Press “ ”to default settings, then press “ ”before press 4. Default settings
“ ”for two seconds to exit the parameter setting menu. DONE
Press “ ”and“ ”key, then press “ ”one time, then 6. Firmware update
the LCD display:
Press “ ”key will indicate you to enter password(3132), enter 6. Firmware update
the password: “ ”“ ”“ ”“ ” Password:****
Then press “ ”to enter program mode. You should make sure Firmware Update.
the power supply is normal in this mode. The program will reset Download from PC.
for use after correctly burn to record according to the program Don’t turnoff power,
software, or it won’t exit, and you should remove the working
Before finished!
source. Then the LCD display:
Settings and operating for other parameters refer to above.
Tra n sfo rm te rm in a l
R S C O N N EC TO R
A
(D B9)
Te le s C o n tro lle r C I4 8 5 A B (R S 4 8 5 )
S
17
Teles Controller Manual
(Controller with RS232 com and CI232A accessory ),more details please refer to the following
wiring diagram:
R S C O N N EC TO R
(D B9)
C I232A
A b le to connected resp e ctively
M O D EM
C o m p uter
The communication interface provides users a method, to make the users fetch more
information that cannot obtain from the panel. The relative software can display the whole
parameters measured and state information; it also can set various parameters.
The controller with RS485 communication interface, which allows connect at least 255 same
serial controllers to the same communication line. And each equipment has sole ID No. To switch
PC or MODEM, you need to collocate another RS485/RS232 converter. Typical wiring diagram as
below:
Note:Communication cable use high quality twisted pair cable with shielded, and its total
length of cable less than 1000m. Each anode and cathode of RS485 interface must be connected
properly, and the cable shield only can be connected to the earth at one side.
18
A
A
B
B
Te le s C o n tro lle r C I485A S
(D B9)
S
RS C O N N EC TO R
R S485/232
Tra n sfo rm e r
Teles Controller Manual
A b le to c o n n e c t re sp e c tive ly
19
A
B
Te le s C o n tro lle r C I485A
(D B9)
S
RS C O N N EC TO R
M O D EM
A
B
Te le s C o n tro lle r C I485A
(D B9)
S
RS C O N N EC TO R
R c o n n e c t to risiste r C o m p u te r
Teles Controller Manual
21
Teles Controller Manual
$202B 1 Oil-P Alarm unit:Kpa
$202C 1 Oil-P preALM unit:Kpa
$202D 1 Coolant preALM unit:℃
$202E 1 Coolant Alarm unit:℃
$202F 1 Batt low preALM unit:V
$2030 1 RUNHr unit:HOUR
$2031 1 Ext.Alarm mode
$2032 1 Ext.Analog unit:0 - V / 1
$2040 1 V1 calibration
$2041 1 V2 calibration
$2042 1 V3 calibration
$2043 1 I1 calibration
$2044 1 I2 calibration
$2045 1 I3 calibration
$2046 1 Oil pressure calibration
$2047 1 Temerature calibration
$2048 1 Battery voltage calibration
$2049 1 Excitation charge voltage calibration
$204A 1 Aux input voltage calibration
$204B ――― $205E P-sensor data, ordered according to the resistance(0.1Ω) from big to small
and resistance-related value-resistance
$205F ――― $2072 T-sensor data, ordered according to the resistance(0.1Ω) from big to small and
resistance-related value-resistance
$2073F ――― $2086 oil position sensor, ordered according to the resistance(0.1Ω) from big to
small and resistance-related value-resistance.
4 O-SENSOR OPEN 14
5 LOW OILPRESS 15
7 COOLANT TEMP 17
8 START FAIL 18
9 STOP FAIL 19
22
Teles Controller Manual
11.2 To confirm the whole connecting of control lines accord to the electric norm, and confirm to the typical
connecting diagram of “1.3”. Especially the DC power supply must add fusing element safety wire for protection,
and the polarity must be right. Otherwise, it will destroy the controller
11.3 The controller must be ground to the earth properly.
11.4 We suggest that the operators install the “ E- stop” key outside. Connecting the “E-stop” output terminal to
the normal contact of “E-stop” key, and the other point of contact must connect to the anode of working source.
11.5 Putting through the DC working source, confirming the preset parameter accord with actual running
requirements. Such as: current ratio, mode of speed sensor, mode of pressure sensor, mode of temperature, etc.
11.6 If the speed sensor is magnetic speed sensor, we must adjust speed measuring parameter
according to the following steps.
Method 1:
After the power supply is available, set the controller to MAN mode, the LED above the MAN key on. Now,
calculate the measuring input frequency of the speed sensor first according to the rated rotating speed and number
of tooth of the engine flywheel. F=tooth × running speed÷60.] You can simply input the calculated value to the
controller to complete settings. Detail procedures are as below:
Operation Description
The controller is in ready state:
READY
Press “ ”for two seconds to enter the configure menu, then the <<SETTING/参数设定>>
LCD display: 0.QUIT
Press “ ”three times and then press “ ”, the LCD will 3.ENGINE
display: 0.QUIT
Press “ ”for two times and then press “ ”, the LCD will 2. Pickup frequency
display: =0
Press “ ”will indicate you to enter password, input the password 2. Pickup frequency
Password:****
is: “ ”“ ”“ ”“ ”
Press “ ”or“ ”at the same time to change the parameter. 3. Pickup frequency
Input the calculated measuring frequency of the speed sensor, the =
LCD will display the settings:
Press “ ”to confirm and then press “ ”for two seconds to READY
exit the configure menu, and the LCD will display:
Method 2
Operation Description
The controller is in ready state:
READY
Press “ ”for two seconds to enter the configure menu, then the <<SETTING/参数设定>>
LCD display: 0.QUIT
Press “ ”three times and then press “ ”, the LCD will 3.ENGINE
display: 0.QUIT
3.ENGINE
Press “ ”three times again, then the LCD display: 3.Set pickup now
23
Teles Controller Manual
NOTE: during the calibration of the speed measuring parameter, the protection of the controller is
imperfection, the operator should take more attention to the condition of the generator set. When it is out
of the way, stop the calibration process immediately. Check out the fault before do it again. If possible, it is
suggested that the operator equipped a protection circuit or device externally.
12 Troubleshooting:
Fault Phenomenon Fault Eliminate
24
Teles Controller Manual
destruction.
7. Please refer to the《Diesel Manual》for further details。
8. Once the fault eliminate, by press“RESET”key to reset again.
9. In the condition of unload, keep the generator running for 10
minutes. After the “ Genset” cooling down, on load again.
The LCD 1.Checking up the temperature sensor mode of controller“T-sensor
display:“LOW mode”, to know about whether it is in the wrong setting. If it is,
OIL then you need to reset again.
Low oil
PRESSURE” 2.Checking up the oil fuel. If it is not enough, please add some.
pressure
and“LOW OIL 3. Please refer to the《Diesel Manual》for further details.。
leads to stop
PRESS” 4.Checking up the oil pressure switch by testing instrument. If it is
fault indicator wrong, you need to change it.
light on. 5.Once the fault eliminate, by press “RESET”key to reset again.
1. Checking up the temperature sensor mode of controller“H-sensor
mode, to know about whether it is in the wrong setting. If it is,
The LCD then you need to reset again.
display: 2. Checking up the actuator, to know about whether it has throttle
Over speed
“OVERSPEED lever movement, if do, please readjust.
leads to
” and “OVER 3. If you installed electro-magnetic actuator, please check up the
diesel stop
SPEED”fault throttle level, to know about whether it is movement without
indicator light on. hindrance. If it is necessary, please adjust.
4. Please refer to the《Diesel Manual》for further details.
5. Once the fault eliminate, by press“RESET”key to reset again.
1. Checking up the diesel, to know about whether it is overload.
2. Checking up the fuel, to know about whether it is enough.
3. Checking up the actuator, to know about whether it is remove. If
Not enough The LCD will do, please adjust.
speed leads display“Speed L 4. If the electro-magnetic actuator has throttle lever, you need to
to stop alarm”signal. check it, to know about whether it is movement without
hindrance. If it is necessary, please adjust it.
5. When the diesel running, you need to adjust the speed of diesel.
6. Please refer to the《Diesel Manual》for further details.
1. Breaking the load adding to the AC generator. After the
generator stop, you need to eliminate the fault and reset the
“Genset” again..
The LCD will
2. Checking up the “low voltage fault setting value” of “Main”,
Low voltage display“Ph-V
confirming that the data is right.
leads to stop low alarm”
3. If the voltage low, you need to set the potentiometer via
signal.
adjusting the output voltage of generator, then return to the
normal voltage.
4. Please refer to the《Alternator Manual》for further details.
1. Breaking the load adding to the AC generator. After the generator
stop, you need to eliminate the fault and reset the “Genset” again.
2. Checking up the “high voltage fault setting value” of “Main”,
The LCD will confirming that the data is right.
display“Ph-V 3. Checking up the measuring voltage of controller, if it is in normal
High voltage
high alarm” mode, please check up the load, so as to confirm that whether it is
leads to stop
signal. non-capacitive.
4. If the voltage high, you need to set the potentiometer via
adjusting the output voltage of generator, then return to the
normal voltage.
5. Please refer to the《Alternator Manual》for further details.
After the
Controller close, 1. Checking up the fuel magnetic valve(or throttle lever), so as to
the generator still confirm that the fuel magnetic valve close the oil channel safely
Generator
keep running, then in the close condition.
fail to stop
the LCD will 2. Checking up the fuel magnetic valve, if it is necessary, please
display“Fail to change it.
start” signal.
25
Teles Controller Manual
26