Slide (9) Transformer Protection
Slide (9) Transformer Protection
1. Windings Failures
1. Windings Failures
The windings are usually of copper. Due to the copper line resistance
thermal losses occur. These thermal losses make hotspots in the
winding due to bad or lack of maintenance.
➢ The overtime thermal losses causes wear and tear and the
decrease of the physical strength up to the point of breaking of
the winding.
1. Windings Failures
The main reasons that cause mechanical windings fault are the
improper repair, bad maintenance, corrosion, manufacturing
deficiencies, vibration and mechanical movement within the
transformer.
Impacts of mechanical windings faults
2. Bushings Failures
2. Bushings Failures
➢ Not replacing of old oil over long time or its deficiency due
to leakage causes internal over-flashing.
Protection used
Fault Type ANSI
Protective relay
number
Primary winding Phase-phase fault Differential; 87T;
Primary winding Phase-earth fault Overcurrent 50/51
Differential; 87T;
Tank Fault Thermostat/Buchholz; 26/63;
Tank-Earth 50G/51G
Over fluxing Over fluxing 24T
RTD temperature
Overheating
monitoring
49T
3 V 30
Phase shift
between line &
phase voltages
MVA 10 3 C
TAP
3 kVLL CT ratio
With DABY compensation, the currents are first tap adjusted and
then combined mathematically to compensate for 30o phase shift
26 Prof Mahmoud El-Gammal October 9, 2017
Transformer Differential Protection
Advantages of using Numerical-based differential 87T relay
inrush
Idiff = i1 + i2 Idiff = i1 + i2
I 1 = I2 I1 >> I2
i 2 < i1 i1 >> i2
Idiff > 0 Idiff > 0
saturated
i. External Fault
Step-1:
Calculate the rated load of primary
and secondary sides from:
rated MVA 10 3 25 10 3
INp 131.2 A
3 kVNp 3 110
rated MVA 10 3 25 10 3
INs 687.3 A
3 kVNs 3 21
rated CT I s 1000
Tap Setting s 1.455 A
INs 687.3
31 Prof Mahmoud El-Gammal October 9, 2017
Transformer Differential Protection
Settings calculations
▪ 5% (HV CT error)
▪ 5% (LV CT error)
▪ 9×1.67% (Tap changer error)
▪ 4% (typical relay operation error)
▪ 5% (typical margin)
➢ Starting ratio setting (k1) = 34%
Step-4 cont. :
▪ 5% (HV CT error)
▪ 5% (LV CT error)
▪ 4% (relay operation error)
▪ 5% (typical margin)
➢ Starting ratio setting (k1) = 19%
34 Prof Mahmoud El-Gammal October 9, 2017
Transformer Differential Protection
Settings calculations
or
Ipu , min 27 100 1 A 0.27 A 270 mA
35 Prof Mahmoud El-Gammal October 9, 2017
Transformer Differential Protection
Settings calculations
Select K2 = 70%
An instantaneous overcurrent
protection (ANSI 50) device
located at the transformer primary
ensures Instantaneous release in
(15 ~ 50)ms against violent short
circuit currents.
➢ instantaneous pickup of
numerical 50-OCR is set at
1.3×Iinrush @ 15-50 ms
40 Prof Mahmoud El-Gammal October 9, 2017
Transformer Protection
Basics
Basics
Scheme Arrangements
From the table above it may be seen that when over fluxing
due to system hazards reaches such that the factor %V/f
ratio attains a values 1.4, the transformer shall be tripped
out of service instantaneously otherwise there may be a
permanent damage
Characteristics
➢ It is usual to provide a
definite time-delayed alarm
setting for overfluxing %V/f
ratio exceeds 1.1.
➢ Inverse time-delayed or an
instantaneous trip setting
when duration and severity
of the condition crosses safe
operation limit.
Rg
Ipu IFmax
Ri R g
The tripping time during an overload condition takes the prior level
of load current into consideration. An alarm can be set to operate
before the tripping condition is reached.