This 3-page document provides a technical specification for an underground power cable. It includes: 1) Details on the cable construction including its conductor, insulation, screens, and outer sheath materials. 2) Electrical characteristics such as resistance, inductance, capacitance, voltage and current ratings. 3) Mechanical properties including minimum bending radii and maximum pulling forces. 4) Test results for voltage, impulse, and partial discharge testing.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
135 views

Datos Cable

This 3-page document provides a technical specification for an underground power cable. It includes: 1) Details on the cable construction including its conductor, insulation, screens, and outer sheath materials. 2) Electrical characteristics such as resistance, inductance, capacitance, voltage and current ratings. 3) Mechanical properties including minimum bending radii and maximum pulling forces. 4) Test results for voltage, impulse, and partial discharge testing.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Page 1 of 3

TECHNICAL SPECIFICATION
2XS(FL)2Y 1x630RM/95 127/220 (245)kV acc. to IEC 62067
CONSTRUCTION (x) The picture is informative only
– not in scale
Round, stranded and compressed
copper conductor. Class 2. APPLICATION
Extruded semi-conducting Laying in ground
conductor screen (wet or dry locations)
Insulation XLPE – dry cured Laying in air
Extruded semi-conducting Laying in ducts
insulation screen
Semi-conducting swelling tapes Highest permissible conductor
Metallic screen: temperature
copper wires screen and Continuous operation 90°C
copper equalizing tapes Overload 105°C
Semi-conducting swelling tapes Short circuit 250°C
Longitudinal aluminum foil (duration max 5s)
Sheath – black HDPE ST7 type
Laying is possible without any special
measures at natural cable temperatures and
ambient temperature not lower than -5ºC,
MARKING with Tele-Fonika supervising
TF KABLE, product name, date of
manufacture, standard, meter marking

DESCRIPTION UNIT DETAILS


CONSTRUCTION DATA Uo/U/Um 127/220 (245)kV
Conductor
material Copper
number of wires No 58
Nominal cross sectional area mm2 630
Conductor diameter and tolerance mm 30.0-0,2+0,5
Thickness of semi-conducting tape No x mm 2 x ~ 0.1
Min. / Nom. thickness semi-conducting XLPE on conductor mm 0.8 / 1.2
Nominal insulation thickness XLPE mm 22.0
Insulation thickness: minimum at a point mm 19.8
Diameter over insulation – nominal mm 76.4±0,5
Min. / Nom. thickness semi-conducting XLPE on insulation mm 0.8 / 1.2
Thickness of semi-conducting swelling tape No x mm 2 x ~ 0.35
Metallic screen mm2 50
Copper wires No x mm 60 x 1.44
Copper equalizing tapes No x mm x mm 2 x 10 x 0.18
Mean diameter over metallic screen mm 82.6
Thickness of semi-conducting swelling tape No x mm 2 x ~ 0.35
Thickness of aluminum foil mm 0.2
Diameter over aluminum foil mm 84.1
Nominal thickness of outer serving / min. at any point mm / mm 4.0 / 3.3
Approximate overall diameter
completed cable (De) mm 92.2
Weight of complete cable (approx.) kg/km 11980
DELIVERY DATA
Flange diameter of wooden drum m 3.0
Type 30OP
Maximum length per drum m 400
Weight of heaviest reel, including cable kg 6700

(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 2 of 3

ELECTRICAL DATA at 50Hz


Maximum D.C. conductor resistance at 20°C Ω/km 0.0283
Maximum A.C. conductor resistance at 90°C Ω/km 0.0384
Maximum D.C. metallic screen resistance at 20°C Ω/km 0.188
0.137
Maximum D.C. aluminum foil resistance at 20°C Ω/km 0.500
Operating inductance
flat trefoil mH/km 0.414
Induction reactance
flat trefoil Ω/km 0.130
Capacitance µF/km 0.160 (+ 8 %)
Capacitance reactance kΩ/km 20.27
Impedance
flat trefoil Ω/km 0.136
Zero sequence reactance Ω/km 0.080
Max. electric stress at conductor screen / (at insulation) kV/mm 9.1 / 3.9
Dielectric losses (tgδ = 0.001) – per phase W/m 0.786
Partial discharge test – at 1.5Uo pC ≤5
Charging current – per phase A/km 6.27
Charging power kVA/km 796
Earth fault current – per phase A/km 18.80
MECHANICAL DATA
Recommended min. bending radius for laying m 2.32
Recommended permissible bending radius at final installation m 1.86
Maximum permissible pulling force: kN 31.5
SHORT CIRCUIT CURRENTS
Maximum permissible thermal short-circuit (IEC 60949)
Current for 1.0 sec.
Phase conductor 90 → 250°C kA 90.8
Metallic screen 80 → 350°C kA 19.2
AMPACITY (**) – Bonding of the metallic screens Single point
Cables in tunnel
trefoil formation A 993
TESTS
AC voltage test (2.5Uo; 30min.) kV 318
Impulse voltage kV 1050
Partial discharge test (1.5Uo) kV 190

Marking:
TF-KABLE 5 2XS(FL)2Y 1x630RM/95 127/220kV IEC 62067 2017

(**)
Current rating guideline (Calculated with Cymcap 5.3 based on IEC Pub. 60287 and the following conditions)

Ground temperature 30°C


Ground thermal resistivity 2.5 K·m/W

(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 3 of 3
Ampacity 993A
Temperature in tunnel 40.0°C

Date: 2017-09-26; Mp15193


Prepared by: Michał Pstrągowski

(x)
Diameters are calculated values and subject to manufacturing tolerances