SITE TEST REPORT Date : -11-2015
Customer:
Contractor’s name: NCC
SEC-EOA
SEC – EOA Contract No. :
380/230 kV JUAYMAH BSP 4400002933
AUXILIARY CONTACTORS Page 1 of 1
Panel No: Equip. : Dwg. Ref.: Record No.:
1. GENERAL DATA AND INFORMATION:
Panel No: Designation:
Manufacturer: Schneider Electric Rated Voltage: 24 Vdc
Main Unit Order No: CAD50 BD No. of Contacts (Main Unit): 5 NO
Auxiliary Unit Order No: No. of Contacts (Aux. Unit): NO___ + NC___
2. MECHANICAL CHECKS AND VISUAL INSPECTION:
ITEM DESCRIPTION CHECKED
1 Inspect for physical damage / defects. ok
2 Verify connections as per approved drawings. ok
3 Check tightness of all connections. ok
4 Check Ferrules. ok
5 Check apparatus lists. ok
3. ELECTRICAL TESTS:
a) FUNCTION TEST:
ITEM DESCRIPTION CHECKED
1 All contacts checked. ok
2 All output contacts resistance measured. ok
b) PICK-UP AND DROP OFF TEST:
Coil Pick Up Drop - Off
Voltage (V) Current (mA) Voltage (V) Current (mA)
A1-A2
Limits: Pick up Voltage: <0.7Uc Drop Off voltage: 0.1-0.25 Uc
c) PICK UP & DROP OFF TIME TEST (At rated voltage):
Contact No. Pick Up (ms) Drop Off (ms)
43-44
Limits: Operating Time: 63ms (15% Tolerance), Reset Time: 20ms (20 % Tolerance)
d) RELAY BURDEN TEST (At rated voltage):
Applied Voltage Measured Current (mA) Burden (W)
24 Vdc
Limits: 5.4W approximately
EQUIPMENT USED
>SVERKER 760
>FLUKE MULTIMETER
DATE: -11-2015
TESTING ENGINEER (XERVON) CSD- Engineer
Signature: ________________ Signature: ________________
Name : Name : ________________