PROJECT BTS/MUS/R/016/2017 DATE OF TEST 13.02.
2018
CLIENT MZEC LOCATION MUSSANAH
CONTRACTOR MOWRED AL RAYYAN ENGINEERING DOCUMENT NO. 013/2018
11kV RMU COMMISSIONING TEST REPORT
1. RMU DETAILS
MAKE LUCY SWITCHGEAR SERIAL NO. SF00142439
TYPE VRE2a YEAR / MONTH 2017
S.S NO. 1030 TX. NO. 1
2. TRANSFORMER DETAILS
MAKE VOLTAMP SERIAL NO 9934450
RATING 200KVA RATIO 11000/433 V
RATED PRIMARY 10.5 A RATED SECONDARY 266.7 A
VECTOR GROUP Dyn 11 % IMPEDANCE 4.84
3. CONTINUITY TEST
4. INSULATION RESISTANCE TEST
TERMINALS CONTINUITY @ 5kV DC for 30 Sec
@ CB & 2 RING SWITCHES ON PHASE CB CONDITION IR VALUE
Ring Switch 1-R to T-off R OK R–E ON >1000G?Ω
Ring Switch 1-Y to T-off Y OK Y-E ON >1000G?Ω
Ring Switch 1-B to T-off B OK B-E ON 879 G?Ω
Ring Switch 2-R to T-off R OK R-Y ON >1000G?Ω
Ring Switch 2-Y to T-off Y OK Y-B ON >1000G?Ω
Ring Switch 2-B to T-off B OK B-R ON >1000G?Ω
@ EARTH SWITCH ON R – R’ OFF >1000G?Ω
Ring Switch 1-R to Earth OK Y – Y’ OFF >1000G?Ω
Ring Switch 1-Y to Earth OK B – B’ OFF >1000G?Ω
Ring Switch 1-B to Earth OK
Ring Switch 2-R to Earth OK
Ring Switch 2-Y to Earth OK 5. FUNCTION CHECK
Ring Switch 2-B to Earth OK
T-off R to Earth OK CHECK STATUS
T-off Y to Earth OK Breaker ON & OFF OK
T-off B to Earth OK Isolators ON & OFF OK
Ring Switch 2-Y to Earth OK Earth Switch ON & OFF OK
Ring Switch 2-B to Earth OK SF6 gas gauge indication OK
Breaker tripping through relay OK
RMU Earthing arrangement OK
Earth Fault Indicator Operation OK pickup @ 50A
6. O/C & E/F RELAY
a. RELAY DETAILS
MANUFACTURER Ashida TYPE ADR 241 S
AUX. VOLTAGE Self-Powered CURRENT RATING 1A
SERIAL 17G241S0166 CT RATIO SELECTED 50/1 A
PHASE O/C SETTING (IP) 26% (13 @ 1O) PHASE O/C TMS
E/F SETTING (IE>) 10% (5A @ 1O) E/F TMS 0.05 (C1-NI3)
PHASE INSTANTANEOUS DISABLED E/F INSTANTANEOUS DISABLED
TEST PUSH BUTTON DISABLED INRUSH BLOCK ENABLED
1 of 3
PROJECT BTS/MUS/R/016/2017 DATE OF TEST 13.02.2018
CLIENT MZEC LOCATION MUSSANAH
CONTRACTOR MOWRED AL RAYYAN ENGINEERING DOCUMENT NO. 013/2018
b. RELAY MEASEUREMENT CHECK
Injected Measured current in Relay (Amps)
Injected
Current in
Phase in R-Phase Y-Phase B-Phase N
Primary
Primary
(Amps) Pri Sec Pri Sec Pri Sec Pri Sec
R phase 25 23 0.48 0 0 0 0 23 0.47
Y phase 25 0 0 24 0.47 0 0 23 0.47
B Phase 25 0 0 0 0 24 0.47 23 0.47
CT ratio is verified to be 50/1 A
c. RELAY CHARACTERISTIC TEST
APPLIED PRIMARY OPERATING CHARA RELAY/CB TRIP
ELEMENT CB TRIP
CURRENT (A) AS PER GRAPH MEASURED INDICATION
Pick-up 13 A 15 A NA NA
R-Y 26(Is X 2) 500 mS 618 mS OK OK
130 (Is X 10) 148 mS 216 mS OK OK
Pick-up 13 A 15 A NA NA
Y-B 26(Is X 2) 500 mS 623 mS OK OK
130 (Is X 10) 148 mS 238 mS OK OK
Pick-up 13 A 15 A NA NA
R-B 26(Is X 2) 500 mS 634 mS OK OK
130 (Is X 10) 148 mS 227 mS OK OK
Pick-up 5A 7A NA NA
EF 10 (Is X 2) 500 mS 771 mS OK OK
25 (Is X 5) 214 mS 309 mS OK OK
7. TESTING EQUIPMENT DETAILS
EQUIPMENT NAME MAKE & MODEL SERIAL NO. CALIBRATION VALIDITY
Primary Injection Kit Omicron CPC100 LJ525T 21.06.2018
Insulation Tester Kyoritsu 3125 W0385620 29.09.2018
Digital Multimeter Fluke 87V 30510332 31.12.2018
TESTED BY WITNESSED BY
M/s. Labib Trading & Contracting L.L.C. M/s. Mazoon Electricity Company (SAOC)
Signature. Signature.
Name FEROZ HAKKIM (PE 001/2017) Name QASIM AL AJMI
Date 17.02.2018 Date
2 of 3
PROJECT BTS/MUS/R/016/2017 DATE OF TEST 13.02.2018
CLIENT MZEC LOCATION MUSSANAH
CONTRACTOR MOWRED AL RAYYAN ENGINEERING DOCUMENT NO. 013/2018
3 of 3