RMU Report

This document summarizes the commissioning test results of an 11kV RMU. Key details include: 1) Continuity and insulation resistance tests were performed and found acceptable on the RMU components. 2) Relay characteristics were verified by injecting currents and checking the relay measured and tripped as expected. 3) Additional functional checks of the breaker, isolators, earth switch and gas gauge were performed satisfactorily. 4) Testing equipment used was verified to be calibrated and within validity dates.

Uploaded by

Feroz Hakkim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
2K views3 pages

RMU Report

This document summarizes the commissioning test results of an 11kV RMU. Key details include: 1) Continuity and insulation resistance tests were performed and found acceptable on the RMU components. 2) Relay characteristics were verified by injecting currents and checking the relay measured and tripped as expected. 3) Additional functional checks of the breaker, isolators, earth switch and gas gauge were performed satisfactorily. 4) Testing equipment used was verified to be calibrated and within validity dates.

Uploaded by

Feroz Hakkim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT BTS/MUS/R/016/2017 DATE OF TEST 13.02.

2018
CLIENT MZEC LOCATION MUSSANAH
CONTRACTOR MOWRED AL RAYYAN ENGINEERING DOCUMENT NO. 013/2018

11kV RMU COMMISSIONING TEST REPORT


1. RMU DETAILS
MAKE LUCY SWITCHGEAR SERIAL NO. SF00142439
TYPE VRE2a YEAR / MONTH 2017
S.S NO. 1030 TX. NO. 1

2. TRANSFORMER DETAILS

MAKE VOLTAMP SERIAL NO 9934450


RATING 200KVA RATIO 11000/433 V
RATED PRIMARY 10.5 A RATED SECONDARY 266.7 A
VECTOR GROUP Dyn 11 % IMPEDANCE 4.84

3. CONTINUITY TEST
4. INSULATION RESISTANCE TEST
TERMINALS CONTINUITY @ 5kV DC for 30 Sec
@ CB & 2 RING SWITCHES ON PHASE CB CONDITION IR VALUE
Ring Switch 1-R to T-off R OK R–E ON >1000G?Ω
Ring Switch 1-Y to T-off Y OK Y-E ON >1000G?Ω
Ring Switch 1-B to T-off B OK B-E ON 879 G?Ω
Ring Switch 2-R to T-off R OK R-Y ON >1000G?Ω
Ring Switch 2-Y to T-off Y OK Y-B ON >1000G?Ω
Ring Switch 2-B to T-off B OK B-R ON >1000G?Ω
@ EARTH SWITCH ON R – R’ OFF >1000G?Ω
Ring Switch 1-R to Earth OK Y – Y’ OFF >1000G?Ω
Ring Switch 1-Y to Earth OK B – B’ OFF >1000G?Ω
Ring Switch 1-B to Earth OK
Ring Switch 2-R to Earth OK
Ring Switch 2-Y to Earth OK 5. FUNCTION CHECK
Ring Switch 2-B to Earth OK
T-off R to Earth OK CHECK STATUS
T-off Y to Earth OK Breaker ON & OFF OK
T-off B to Earth OK Isolators ON & OFF OK
Ring Switch 2-Y to Earth OK Earth Switch ON & OFF OK
Ring Switch 2-B to Earth OK SF6 gas gauge indication OK
Breaker tripping through relay OK
RMU Earthing arrangement OK
Earth Fault Indicator Operation OK pickup @ 50A

6. O/C & E/F RELAY


a. RELAY DETAILS
MANUFACTURER Ashida TYPE ADR 241 S
AUX. VOLTAGE Self-Powered CURRENT RATING 1A
SERIAL 17G241S0166 CT RATIO SELECTED 50/1 A
PHASE O/C SETTING (IP) 26% (13 @ 1O) PHASE O/C TMS
E/F SETTING (IE>) 10% (5A @ 1O) E/F TMS 0.05 (C1-NI3)
PHASE INSTANTANEOUS DISABLED E/F INSTANTANEOUS DISABLED
TEST PUSH BUTTON DISABLED INRUSH BLOCK ENABLED
1 of 3
PROJECT BTS/MUS/R/016/2017 DATE OF TEST 13.02.2018
CLIENT MZEC LOCATION MUSSANAH
CONTRACTOR MOWRED AL RAYYAN ENGINEERING DOCUMENT NO. 013/2018

b. RELAY MEASEUREMENT CHECK


Injected Measured current in Relay (Amps)
Injected
Current in
Phase in R-Phase Y-Phase B-Phase N
Primary
Primary
(Amps) Pri Sec Pri Sec Pri Sec Pri Sec
R phase 25 23 0.48 0 0 0 0 23 0.47
Y phase 25 0 0 24 0.47 0 0 23 0.47
B Phase 25 0 0 0 0 24 0.47 23 0.47
CT ratio is verified to be 50/1 A

c. RELAY CHARACTERISTIC TEST


APPLIED PRIMARY OPERATING CHARA RELAY/CB TRIP
ELEMENT CB TRIP
CURRENT (A) AS PER GRAPH MEASURED INDICATION
Pick-up 13 A 15 A NA NA
R-Y 26(Is X 2) 500 mS 618 mS OK OK
130 (Is X 10) 148 mS 216 mS OK OK
Pick-up 13 A 15 A NA NA
Y-B 26(Is X 2) 500 mS 623 mS OK OK
130 (Is X 10) 148 mS 238 mS OK OK
Pick-up 13 A 15 A NA NA
R-B 26(Is X 2) 500 mS 634 mS OK OK
130 (Is X 10) 148 mS 227 mS OK OK
Pick-up 5A 7A NA NA
EF 10 (Is X 2) 500 mS 771 mS OK OK
25 (Is X 5) 214 mS 309 mS OK OK

7. TESTING EQUIPMENT DETAILS

EQUIPMENT NAME MAKE & MODEL SERIAL NO. CALIBRATION VALIDITY


Primary Injection Kit Omicron CPC100 LJ525T 21.06.2018
Insulation Tester Kyoritsu 3125 W0385620 29.09.2018
Digital Multimeter Fluke 87V 30510332 31.12.2018

TESTED BY WITNESSED BY
M/s. Labib Trading & Contracting L.L.C. M/s. Mazoon Electricity Company (SAOC)
Signature. Signature.

Name FEROZ HAKKIM (PE 001/2017) Name QASIM AL AJMI


Date 17.02.2018 Date
2 of 3
PROJECT BTS/MUS/R/016/2017 DATE OF TEST 13.02.2018
CLIENT MZEC LOCATION MUSSANAH
CONTRACTOR MOWRED AL RAYYAN ENGINEERING DOCUMENT NO. 013/2018