HYDRAULIC CALCULATIONS
BLOCK – D, E & F
A. FLOW CALCULATION
Refer Annexure. A
B. HEAD CALCULATION
Total Head (H) = Static Head (h) + Head loss due to friction (hf) + Residual Head
(hr)
1. Static Head
Head loss due to friction, hf = head loss through pipe (hfp) + head loss through fittings
(hff)
For calculating head loss through Pipes from Pump room to first floor tapping point,
consider the frictional head loss through 50mm dia Pump header and 90mm dia water
supply riser.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart
For calculating head loss through Pipes from first floor tapping point to third floor
tapping point, consider the frictional head loss through 73mm dia water supply riser.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
From the Graph of Plumbing Design Hand Book at 762 loading unit for 73 mm dia Pipe,
head loss is 0.025 meters per meter run of Pipe.
For calculating head loss through Pipes from Third floor tapping point to Fourth floor
tapping point, consider the frictional head loss through 65mm dia water supply riser
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
From the Graph of Plumbing Design Hand Book at 381 loading unit for 65 mm dia Pipe,
head loss is 0.02 meters per meter run of Pipe.
For calculating head loss through Pipes from fourth floor tapping point to roof floor
tapping point, consider the frictional head loss through 50mm dia water supply riser.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
From the Graph of Plumbing Design Hand Book at 381 loading unit for 50 mm dia Pipe,
head loss is 0.04 meters per meter run of Pipe.
For calculating frictional loss through Apartment piping consider the frictional head loss
through 50mm dia water supply pipes from Water meter Cabinet to Master Bath
Bath Tub point,
40 mm dia Tee - 1 no
32 mm dia Tee - 1 no
25 mm Elbow - 2 nos
25 mm Gate valve - 1 no
25 x 16 mm Tee - 1 no
16 mm dia Pipe - 3 mtr
16 mm Elbow - 2 nos
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
From the Graph of Plumbing Design Hand Book at 0.8LPS flow rate for 50 mm dia Pipe,
head loss is 0.007 meters per meter run of Pipe.
Head loss due to friction, hf = Head loss through Riser piping + Head
loss through Apartment piping
Head loss due to friction, hf = 1.8 + 0.196 + 0.573 + 0.182 + 0.452 + 0.51
= 3.713 mtr.
3. Residual head
Total Head (H) = Static Head + Head loss due to friction + Residual Head
= 28.3 + 3.713 + 15.495
= 47.508 m
A.FLOW CALCULATION
Refer Annexure. A
B.HEAD CALCULATIONS
Total Head (H) = Static Head (h) + Head loss due to friction (hf) + Residual Head
(hr)
1. Static Head
Head loss due to friction, hf = head loss through pipe (hfp) + head loss through fittings
(hff)
For calculating head loss through Pipes from Pump room to ground floor tapping point,
consider the frictional head loss through 50mm dia Pump header and 90mm dia water
supply riser.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart
90 mm Elbow = 2.7 x 6 = 16.2 mtr
90 mm Tee = 5.4 x 2 = 10.8
mtr
90 x 73mm Reducer = 2.4 x 1 = 2.4 mtr
90 x 65 mm Reducer = 2.7 x 2 = 5.4 mtr
Total Length of Fittings = 34.8 mtr
For calculating head loss through Pipes from ground floor tapping point to second floor
tapping point, consider the frictional head loss through 73mm dia water supply riser.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
For calculating head loss through Pipes from second floor tapping point to third floor
tapping point, consider the frictional head loss through 65mm dia water supply riser
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
From the Graph of Plumbing Design Hand Book at 381 loading unit for 65 mm dia Pipe,
head loss is 0.02 meters per meter run of Pipe.
For calculating head loss through Pipes from third floor tapping point to roof floor
tapping point, consider the frictional head loss through 50mm dia water supply riser.
e. Head loss through 50mm dia Riser Pipe
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
From the Graph of Plumbing Design Hand Book at 381 loading unit for 50 mm dia Pipe,
head loss is 0.04 meters per meter run of Pipe.
For calculating frictional loss through Apartment piping consider the frictional head loss
through 50mm dia water supply pipes from Water meter Cabinet to Master Bath
Bath Tub point,
40 mm dia Tee - 1 no
32 mm dia Tee - 1 no
25 mm Elbow - 2 nos
25 mm Gate valve - 1 no
25 x 16 mm Tee - 1 no
16 mm dia Pipe - 3 mtr
16 mm Elbow - 2 nos
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
From the Graph of Plumbing Design Hand Book for 50 loading unit at 0.8LPS flow rate
for 50 mm dia Pipe, head loss is 0.007 meters per meter run of Pipe.
Head loss due to friction, hf = Head loss through Riser piping + Head
loss through Apartment piping
Head loss due to friction, hf = 1.8 + 0.0267 + 0.573 + 0.182 + 0.452 + 0.51
= 3.5437 mtr.
3. Residual head
Total Head (H) = Static Head + Head loss due to friction + Residual Head
= 24.5 + 3.544 + 15.495
= 43.539
= 43.539 m
A.FLOW CALCULATIONS
Refer Annexure. A
B. HEAD CALCULATIONS
Total Head (H) = Static Head (h) + Head loss due to friction (hf) + Residual Head
(hr)
1. Static Head
Head loss due to friction, hf = head loss through pipe (hfp) + head loss through fittings
(hff)
For calculating head loss through Pipes from Pump room to ground floor tapping point,
consider the frictional head loss through 50mm dia Pump header and 90mm dia water
supply riser.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart
For calculating head loss through Pipes from ground floor tapping point to second floor
tapping point, consider the frictional head loss through 73mm dia water supply riser.
From the Graph of Plumbing Design Hand Book at 1299 loading unit for 73 mm dia
Pipe, head loss is 0.04 meters per meter run of Pipe.
For calculating head loss through Pipes from second floor tapping point to roof floor
tapping point, consider the frictional head loss through 65mm dia water supply riser
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
For calculating frictional loss through Apartment piping consider the frictional head loss
through 50mm dia water supply pipes from Water meter Cabinet to Master Bath
Bath Tub point,
40 mm dia Tee - 1 no
32 mm dia Tee - 1 no
25 mm Elbow - 2 nos
25 mm Gate valve - 1 no
25 x 16 mm Tee - 1 no
16 mm dia Pipe - 3 mtr
16 mm Elbow - 2 nos
Equivalent Pipe Length of Fittings in Meter from the Plumbing Design Book Chart.
Head loss due to friction, hf = Head loss through Riser piping + Head
loss through Apartment piping
3. Residual head
Total Head (H) = Static Head + Head loss due to friction + Residual Head
= 20.7 + 3.8146 + 15.495
= 40.0096
= 40m