CB76 3261
CB76 3261
Synchronous Generators
Applications
Generators driven by steam or gas turbines are used by private users and power companies, both home and overseas. They are
also used as a regular, emergency-purpose, or peak-cut power supply in a variety of applications such as in manufacturing plants,
petrochemical plants, iron works, power plants, IT industries, and building power supplies.
Scope of manufacture
Rotation speed No. of Output (MVA)
(min-1) Poles 10 20 30 40 50 60
1500/1800 4
1 2
4 POLE
Meiden 4-Pole Synchronous Generators
5
19
7
Stator core
To reduce iron loss, the stator core is composed
of high-quality surface-insulated silicon steel
laminations, which are in turn punched into
stacks. The core is provided with air ducts so
that cooling air can effectively chill the core and
coils. Both ends of core stacks are clamped into
an assembly by welding the keys and clampers
arranged on the core rear surface.
16 10
15
11
20
14 8 13 1 12
3 4
4 POLE
Meiden 4-Pole Synchronous Generators
Rotor Bearing
Shaft and magnetic poles Bearing
The shaft is produced by shaving out a forged A sleeve bearing of the forced lubrication
carbon steel block. The section to be joined with system is used. A spherical bearing seat is used
a turbine is fabricated to make a perfect cou- to absorb any shaft distortion between the bear-
pling. ing and the bearing box. The bearing is made of
Massive salient poles are processed so that the a cast iron shell lined with a precisely machined
center of the forged shaft has the shape of a white metal.
cross. Each pole is fitted with a field winding.
The field windings are fixed by the use of the
pole shoes bolt-fastened to the respective poles
and the coil clampers that are arranged among
the poles.
Mechanical balance Main terminal construction Neutral point side Output side
A subject to keep in mind for 4-pole machines is In standard construction, six (6) main terminals
a solution for mechanical balancing both static (3 on the output side and 3 on the neutral point
and dynamic. The generator is manufactured side) are accommodated. Lead wires are
based on this subject in the respective pro- brought out toward the generator side.
cesses of the selection of materials, machining, The main terminals can be brought out on either
and assembly. Mechanical balancing is always side of the right or left. Generally, the terminals
checked and adjusted through the examination on the output side are located opposite those on
of static balancing and running balancing. the neutral point side. They can, however, be
This balancing is assured even after many installed in a lower position as requested.
years of operation. The shape of the terminal box can change
according to the cable type and cable connec-
tions.
5 6
4 POLE
Meiden 4-Pole Synchronous Generators
7 8
Meiden 4-Pole Synchronous Generators
AVR
Digital Automatic Voltage Regulator (AVR) TYPE YNEX06D External dimensions
General description
The Meiden AVR [YNEX06D] is adopted as a standard AVR unit. The digital automatic Unit: mm
voltage regulator (AVR) [YNEX06D] covers the functions of conventional analog automatic
voltage regulators. If two units of this type are used, the functions of a dual system become
225
193 185.2
available. Since a variety of options are used, space saving is possible for switchboards.
5.5
30
Analog output terminal
(for testing)
260
300
(for maintenance)
Main-circuit elements IGBT
Display operator section
Control system PID control
Communication port
Weight 7.8kg for dual connection
(optional)
Control source voltage DC source Input: DC24V 3A or below
(Duplex power supply) AC source Input: AC110V 40∼240Hz 0.7A or below External I/O terminal
209
Capacity of source fault output contact Load current 150mA or below
Rated input voltage AC110V or AC 220V 40∼240Hz
Rated output current DC20A
Bus VT AC110V 0.5VA or below
Connection U V W YNEX06D
Generator VT AC110V 0.5VA or below 1VT
Bus voltage Control source
diagram
UB P24
VB AC110V DC24V N24
Generator CT AC5A 0.5VA or below
Operating temperature –20∼60℃ (hot start) 2VT 0V
UG
Relative humidity 95% or below No dew condensation VG
Generator voltage DI0
AC110V
Storage temperature –20∼70℃ WG Digital input
DC 24V
Altitude 1000m or below P2 P2
3L
2CT 1L Generator current
Cooling system Natural air cooling P1 P1
3S AC5A
DI14
1S
List of functions U Control source *2 PCOM
V AC110V DO0
Item Specifications
UP PMG current Digital output
Voltage control range (90H) 90 ∼110% VP AC110V or DC24V
Automatic voltage regulation (AVR) Voltage control accuracy Within ±0.5%
WP 220V
AVR output DO15
Full stroke time 60 sec. PMG
J K
Field current control range (70E) 0∼130%
Automatic field current regulation (AFIR) Field current control accuracy Within ±0.5% G
AC
EX
Full stroke time 60 sec.
Smooth start system 0=100 sec. *2 When PMG voltage is 220V, an auxiliary transformer has to be installed.
Voltage buildup control function
Step start system –
Crosscurrent compensation function Setting range 0 ∼10%
Block diagram YNEX06D
V/Hz function Voltage droop system / Setting value (Droop point is set) 70∼100% (Default: 85%)
Ua Ub
Field overcurrent function (76E) Operating value 105∼130% Major loop Minor loop
Power factor control・ Setting range for Item A –1.0∼1.0PU
reactive power control functions Setting range for Item B –0.7∼0.7cosφ IGBT converter
(APFR・AQR) Reactive power control accuracy Within ±2% 90R + 1+STa + 1+STb
Formula: Q = A + BP
Ka
STa
Kth*Kb
STb
ACEX G
Power factor control accuracy Within ±2° − − −
Overcurrent limit (OCL), over-excitation limit (OEL), Under-excitation limit (UEL)
Reactive power limitation function OCL boundary setting 0 ∼100% Lb
(VARL) Lagging side setting 10 points max. La
www.meidensha.com
Specifications in this catalog are subject to change without notice. BB57-2608
CB76-3261A
A As
As of
of Jun.,
Oct., 2015
2015-10ME
(1.7L)1L
2015-6ME(1L)0.3L