001 Lab1 PDF
001 Lab1 PDF
1
Spring 2007 on-campus Three Phase Transformers
Experiment No. 1
The objectives of this experiment are to find the approximate per phase equivalent circuit
parameters of a 3-φ transformer bank using short circuit and open circuit tests and to
determine the regulation and efficiency of the transformer bank through load test. The
regulation and efficiency of the transformer bank determined through load test will be
compared with those calculated using the transformer parameters.
Apparatus:
1. 1 3-φ variac
2. 2 Test tables
3. 4 multimeters
4. 2 wattmeters
5. 1 15 kVA 3- φ transformer Bank
6. 1 3-φ Resistive load bank with fan
7. 1 3-φ Capacitive Load Bank
Procedure:
a) Refer to Fig.1 for Short circuit test. Connect the high voltage windings of each 1-φ
transformer in parallel and then connect them in STAR configuration. Connect the
low voltage windings of each 1-φ transformer in parallel and then connect them in
DELTA configuration. Make sure that the transformer is connected according to
nameplate specifications.
b) Connect the three phases of the low voltage windings to test table 2. Connect the
three phases of the high voltage windings through the test table to the output
terminals of the variac. Make sure that all test table line switches are open. Connect
the input terminals of the variac to the 120V AC power panel. Do not turn on power.
Have the lab instructor check your set up.
c) With the test table's line switches still open, turn on power and adjust the variac until
its output voltage is zero.
1/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
d) Calculate the rated current for the input windings. Check your value with the lab
instructor. Make sure that your current transformer is set up to handle this current.
e) Protecting the measuring instruments, close the test table line switches. Immediately
after closing the line switches check the current in lines 1,2 and 3. The current should
be close to zero. If the current is not close to zero de-energize your circuit and
recheck it.
f) Increase the output voltage of the variac until the ammeter in line 1 indicates rated
current. Measure and record VH12, VH23, VH31, IH1, IH2, IH3, IX1, IX2, IX3, PHWM1 and
PHWM2. Protect your measuring instruments and de-energize the circuit. Readings
should be taken with great precaution as you may see currents as high as 100A!
a) Refer to Fig.2 for Open circuit test. Connect the high voltage windings of each 1-φ
transformer in parallel and then connect them in STAR configuration. Connect the
low voltage windings of each 1-φ transformer in parallel and then connect them in
DELTA configuration. Make sure that the transformer is connected according to
nameplate specifications.
b) Connect the three phases of the high voltage windings to test table 1. Make sure that
the output connections are open circuited! Connect the three phases of the low
voltage windings through test table 2 to the output terminals of the 120V AC power
panel. Make sure that all test table line switches are open. Do not turn on power.
Have the lab instructor check your set up.
g) Measure and record VX12, VX23, VX31, IX1, IX2, IX3, PXWM1, PXWM2, VH12, VH23 and VH31.
Readings should be taken with great precaution as you may see voltages as high
as 420V!
b) Make sure that the resistance bank is connected to rated voltage. Open circuit the
secondary; i.e., resistance set to infinity. Turn ON the mains and then turn the
switches on the test table to ON position.
c) Now adjust the resistive load until IH1 = IH2 = IH3 = rated current. Measure and record
VX12, VX23, VX31, IX1N, IX2N, IX3N, PXWM1, PXWM2, VH12, VH23, VH31, IH1N, IH2N, IH3N,
PHWM1, PHWM2 and PHWM3 for rated current. .ote that a two-wattmeter method is
used on LV side and a three-wattmeter method on HV side for measurement of
three-phase power. So the selection switch on HV side should be used only
between positions 1-. and 3-..
2/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
d) Now vary the load resistance such that IH1 = IH2 = IH3 equals ½ of rated current.
Measure and record the same quantities as in step “c” for each value of IH.
b) Make sure that the resistance and capacitive bank are connected to rated voltage.
Open circuit the secondary by setting the resistance bank and capacitance bank to
infinity. Turn ON the mains and then turn the switches on the test table ON. Now
adjust the resistive and capacitive loads such that they draw equal currents and the
line currents IH1 = IH2 = IH3 = rated current. Measure and record VX12, VX23, VX31, IX1N,
IX2N, IX3N, PXWM1, PXWM2, VH12, VH23, VH31, IH1N, IH2N, IH3N, PHWM1, PHWM2 and PHWM3 for
rated current. .ote that a two-wattmeter method is used on LV side and a three-
wattmeter method on HV side for measurement of three-phase power. The
selection switch on HV side should be used only between positions 1-. and 3-..
c) Now vary the load resistance such that IH1 = IH2 = IH3 equals ½ of rated current.
Measure and record the same quantities as in step “c” for each value of IH.
Report:
1. Designate the parallel connected low voltage (X) windings the primary and the
parallel connected high voltage (H) windings the secondary.
2. Using the data found in the open circuit test calculate RC,X1 and XM,X1.
GCX1 is given by
Poc
3
Poc
GMX
2 2
Voc Voc
3
BM,X is given by
2 2
BMX Yoc − GMX
Where
Ioc
Yoc
Voc
3
3/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
Poc (
WMR⋅PT⋅CT ⋅ PXWM1 + PXWM2 )
Where WMR is the Wattmeter ratio, CT is the current transformer ratio and PT is the
Potential Transformer ratio (Treat PT = 1 for the whole experiment).
3. Using the data found in the short circuit test calculate Req,H and Xeq,H.
ReqH is given by
Vsc
ZeqH
3
Isc
Xeq,H is given by
2 2
XeqH ZeqH − ReqH
Where
Psc
ReqH
3
2
Isc
Draw the approximate per phase transformer equivalent circuit with all parameters
referred to the primary (LV side) as shown in Fig 5. Show the calculated values of
each parameter. Remember to include units. Remember the short circuit test was
performed with the voltage applied to the high voltage side! Also make a note of
the transformation ratio “a”.
a) Using the data gathered in Part 3, Transformer with R Load, calculate the efficiency
(η) of the transformer for full, ½ and no load.
b) Using the data gathered in Part 4, Transformer with RC Load, calculate the efficiency
(η) of the transformer for full, ½ and no load.
4/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
VHLLnoload − VHLLload
%Reg
VHLLload
a) Using the data gathered in Part 3, Transformer with R Load, calculate the voltage
regulation of the transformer for full, ½ and no load.
b) Using the data gathered in Part 4, Transformer with RC Load, calculate the voltage
regulation of the transformer for full, ½ and no load.
a) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side
average current), and PF (power factor), gathered in Part 3, Transformer with R Load,
and the equivalent circuit of your transformer, calculate the efficiency of the
transformer for full, ½ and no load.
b) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side
average current), and PF (power factor), gathered in Part 4, Transformer with RC
Load, and the equivalent circuit of your transformer, calculate the efficiency for the
transformer for full, ½ and no load.
7. Voltage Regulation from the transformer equivalent circuit and its parameters
a) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side
average current), and PF (power factor), gathered in Part 3, Transformer with R Load,
and the equivalent circuit of your transformer, calculate the voltage regulation of the
transformer for full, ½ and no load.
b) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side
average current), and PF (power factor), gathered in Part 4, Transformer with RC
Load, and the equivalent circuit of your transformer, calculate the voltage regulation
for the transformer for full, ½ and no load.
8. Compare the results found in step 4 with 6 and step 5 with 7 of the report section.
Calculate percent differences. What conclusions can you draw?
5/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
Table1: Short Circuit Test:
Quantity Measured reading
HV Side
Readings
PHWM1
PHWM2
VH12
VH23
VH13
IH1
IH2
IH3
LV Side
Readings
IX1
IX2
IX3
LV Side
Readings
PXWM1
PXWM2
VX12
VX23
VX13
IX1
IX2
IX3
HV Side
Readings
VH1
VH2
VH3
6/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
Table 3: R Load:
LV Side
Readings
PXWM1
PXWM2
VX12
VX23
VX13
IX1
IX2
IX3
HV Side
Readings
PH1
PH2
PH3
VH1
VH2
VH3
IH1
IH2
IH3
7/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
Table 4: RC Load:
LV Side
Readings
PXWM1
PXWM2
VX12
VX23
VX13
IX1
IX2
IX3
HV Side
Readings
PH1
PH2
PH3
VH1
VH2
VH3
IH1
IH2
IH3
IHR1
IHR2
IHR3
IHC1
IHC2
IHC3
8/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
H1 H3
X1 X3 2X
N
N
X2 X4
3H H2 H4
H1 H3
X1 X3 3X
N
N
X2 X4
H2 H4
AC N AC X2 X4
H2 H4
C 2X
2H
H1 H3
B X1 X3
120 V 240 V
X2 X4
H2 H4
3X
3H
H1 H3
X1 X3
120 V 240 V
N
X2 X4
H2 H4
9/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
AC N AC X2 X4
H2 H4
C 2 IHR2
2 R
H1 H3
B X1 X3 R
120 V 240 V
R
X2 X4
H2 H4
3 3 IHR3
H1 H3
X1 X3
120 V 240 V
N
X2 X4
H2 H4
10/11
ECE 420 Experiment o. 1
Spring 2007 on-campus Three Phase Transformers
IH NX
IX a=
a 3⋅ N H
Req,X Xeq,X
VXLNAC
VX GM,X BM,X aVH a2ZLOAD
Fig. 5. Per Phase Equivalent Circuit referred to LV side for the 3φ Transformer.
11/11