Honeywell Solid State Economizer System - Documentation
Honeywell Solid State Economizer System - Documentation
(CONSISTING OF: C7046C DISCHARGE AIR SENSOR OR C7150B MIXED AIR SENSOR, C7232 OR C7632 CARBON DIOX-
IDE SENSOR, C7400 SOLID STATE ENTHALPY SENSOR OR C7660 SOLID STATE TEMPERATURE SENSOR, M7215
DAMPER ACTUATOR AND W7212, W7213 OR W7214 SOLID STATE ECONOMIZER LOGIC MODULE)
FEATURES
C7046C Discharge Air Sensors have probe lengths of 8 in.
(203 mm) and nominal sensor resistance of 3000 ohms at
77°F (25°C).
• No setting or calibration required.
C7232B M7215
C7150 • Solid state components not affected by dust or dirt.
• Fast reacting.
• Rugged aluminum insertion probe.
63-2576—02
SOLID STATE ECONOMIZER SYSTEM
C7400 Solid State Enthalpy Sensor and C7660 Solid State • Used with Honeywell actuators.
Temperature Sensors are used with the W7212 Solid State
• Combines minimum and DCV maximum damper
Economizer Logic Module to allow using outdoor air as the
position potentiometers with compressor staging.
first stage of cooling in HVAC systems.
• C7400 senses and combines temperature and • Relay functions with solid state enthalpy or dry bulb
humidity of outdoor air (heat index). changeover control.
• C7660 senses dry bulb temperature only. • Terminals included for switching between Occupied
and Unoccupied operation.
• Long-lasting, solid state sensing element is accurate
and stable over time. • Terminals included for connecting optional S963B1128
Remote Potentiometer for remote minimum damper
• When enthalpy/temperature of outdoor air increases,
position control.
the outdoor air damper closes to a preset minimum
position. • LED indicates when free cooling is available.
• When enthalpy/temperature of outdoor air is low, the • LED indicates when module is in DCV mode.
outdoor air damper opens to reduce the building
• LED indicates when exhaust fan contact is closed.
cooling load.
• W7213 is used with heat pump B terminal.
• Provides 4 to 20 mA output signal to the Economizer
Logic Modules; setpoint is located on economizer • W7214 is used with heat pump O terminal.
control.
IMPORTANT
• Maximum economizer savings is achieved with two
Specifications given in this publication do not include
C7400 Enthalpy Sensors connected to one
normal manufacturing tolerances. Therefore, this unit
Economizer Logic Modules for differential enthalpy
may not exactly match the listed specifications. Also,
changeover control.
this product is tested and calibrated under closely
controlled conditions and some minor differences in
M7215 Damper Motors are 25 lb-in. spring return damper
performance can be expected if those conditions are
actuators that provide modulating control of economizer sys-
changed.
tems, ventilation dampers and combustion air dampers used
in residential or commercial HVAC equipment.
• M7215 Damper Motors provide modulating control of When Installing this Product...
economizer dampers from a 2-10 Vdc controller.
1. Read these instructions carefully. Failure to follow
• Quiet, high efficiency drive motor. them could damage the product or cause a hazardous
condition.
• High impact, glass-fiber reinforced plastic case is
2. Check the ratings given in the instructions and on the
rugged, lightweight and corrosion resistant.
product to make sure the product is suitable for your
• Provides 2-10 Vdc output signal proportional to the application.
shaft position. 3. Installer must be a trained, experienced service
technician.
W7212 Economizer Logic Modules are used with C7232 4. After installation is complete, check out product
Demand Control Ventilation (DCV) Sensors, and solid state operation as provided in these instructions.
C7400 Enthalpy Sensors or C7660 Dry Bulb Temperature
Sensors to proportion outdoor and return air dampers for con-
trol of free cooling in commercial HVAC equipment.
• Operates from thermostat and DCV sensor to provide a
CAUTION
totally integrated control system. Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
• Solid state control package provides accurate, reliable circuitry.
and stable control. Disconnect power supply before installation.
• Mounts on M7215 Motor or duct work.
IMPORTANT
• Control can be tempered by DCV and fan cycling. All wiring must agree with applicable codes,
ordinances and regulations.
63-2576—02 2
SOLID STATE ECONOMIZER SYSTEM
1
(25)
LOCKING PUSH NEOPRENE
NUTS (2) GASKET
1/4 (6)
5/16 (9) DIAMETER DIAMETER (2 HOLES) TO
(BUSHING) APPROPRIATE
M22402
SYSTEM CONNECT SENSOR
COMPONENTS WIRES WITH TWO
WIRENUT CONNECTORS
Fig. 1. C7046C Air Temperature Sensor dimensions M22403 (NOT PROVIDED)
in in. (mm).
Fig. 2. Mounting C7046 Air Temperature
NOTE: Sensor probe diameter is 1/4 in. (6 mm). Sensor on a flat duct or plenum surface.
Installation
STANDARD UTILITY SENSOR FLANGE NO. 8 (4mm)
The sensor assembly (see Fig. 1) consists of an aluminum CONDUIT BOX PROBE MOUNTING
sensor probe (element housed internally) with attached flange SCREWS (NOT
PROVIDED)
that can be mounted on a flat duct or plenum surface, or in
a 2 in. by 4 in. (51 by 102 mm) junction box using two No. 8 BLANK
FACEPLATE
screws. Connections to the sensor are made through two 6 in. (OPTIONAL)
(152 mm) leadwires. CONNECTOR
LOCKNUT
AND
LOCATION CONDUIT
3 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
instructions. 10000
4. Erratic temperature readings from a sensor can be 9000
caused by improper wiring practices. These must 8000
be avoided to assure proper operation: 7000
•Avoid poor wiring connections. 6000
•Avoid intermittent or missing building earth ground.
5000
•Do not mount sensor in incorrect environment.
4000 3,000 OHMS
AT 77 F (25 C)
Connect low voltage wiring from the sensor to the appropriate 3000
10 20 30 40 50 60 70 80 90 100 F
Operation -10 -5 0 5 10 15 20 25 30 35 C
TEMPERATURE (DEGREES) M17969
The C7046C Air Temperature Sensors consist of a thermistor
sensing element mounted in a tubular probe. They are applied
at various locations throughout single zone and multizone Fig. 4. C7046C Sensor resistance vs. temperature.
duct systems. The negative temperature coefficient (NTC)
63-2576—02 4
SOLID STATE ECONOMIZER SYSTEM
3/4 3/4
(19) (19) Operation
1-1/2 The C7150B Air Temperature Sensor consists of a thermistor
(38) sensing element mounted on a phenolic board. It is applied in
ventilation duct systems. The thermistor element negative
temperature coefficient (NTC) characteristic causes its
3/16 (5) DIAMETER resistance to decrease as the sampled air temperature
increases. This resistance change is used as a control system
sensor to regulate discharge air temperature in a W973 Single
2-3/8 Zone System or damper position of the M7215A Motor (either
2 (60) directly, or through the Economizer Logic Module).
(51)
Checkout
2-1/2 (64)
Allow the C7150B Sensor to soak in the air moving through
2-1/4 (57) M17992
the duct for a minimum of 5 minutes before taking a resistance
measurement:
Fig. 5. C7150B approximate dimensions in in. (mm). 1. Disconnect sensor leadwires from associated system
components.
2. Connect an ohmmeter across the leadwires.
3. Nominal resistance measurements should be in
accordance with the resistance/temperature curves
shown in Fig. 7 and Fig. 8.
4. Reconnect sensor leadwires to associated system
components.
5. Check operation of the M7215A Motor, W973 System,
or the Economizer Logic Module.
5 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
17000 50000
16000
45000
15000
14000 40000
RESISTANCE (OHMS)
13000
35000
12000
11000 30000
RESISTANCE (OHMS)
10000
25000
9000
8000 20000
7000
15000
6000 10,000 OHMS
AT 77 F (25 C)
5000 10000
63-2576—02 6
SOLID STATE ECONOMIZER SYSTEM
Electrical Ratings:
3-5/16 (84) 1-13/16
Power Supply: 24 Vac ±20%, 50/60 Hz (Class 2). (46)
Maximum Power Consumption: 3W.
Peak Current (at 20 ms): 600 mA.
Relay: 5-5/8
(142)
Configuration: Shipped N.O. (reconfigure with software.)
Contact Rating: 1A at 50 Vac/24 Vdc.
Minimum Permissible Load: 1 mA at 5 Vdc. 1-5/8
Linear Analog Output: (41) 8 (203)
M17592
Voltage: 0/2-10 Vdc (resistive load greater than
5000 ohms). Fig. 10. C7232B dimensions in in. (mm).
Current: 0/4-20 mA (resistive load less than 500 ohms).
Ambient Ratings:
CAUTION
Temperature: Health Hazard.
Operating: +32°F to +122°F (0°C to +50°C). Improper use can create dangerous situations.
Storage: -4°F to +158°F (-20°C to +70°C). Use in application for sensing carbon dioxide only.
Relative Humidity (non-condensing): 0 to 95 percent. For life-safety applications, this device can function
only as a secondary or lesser device.
CO2 Pressure Dependence: 1.4% change in reading per
1 kPa deviation from 100 kPa.
CAUTION
Connections: Electrical Shock or Equipment Damage Hazard.
Wiring: Can shock individuals or short equipment
C7232A: 20-gauge cable with six 8 in. leadwires. circuitry.
C7232B: 20-gauge cable with six 6 in. leadwires. Disconnect power supply before installation.
Mounting:
C7232A: Vertical surface with standard single-gang junction
box. CAUTION
C7232B: Sheet metal duct with a sampling tube. Equipment Damage Hazard.
Electrostatic discharge can short equipment
Automatic Background Calibration (ABC) default: On. circuitry.
Ensure that you are properly grounded before
Approvals: handling the unit.
CE.
7 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
C7232A Cover Removal/Replacement NOTE: When mounting on a junction box, see Fig. 12.
NO. 6 SCREW
B
FRONT
COVER
SUBBASE
BUTTON HEAD
SOCKET CAP
SCREW NO. 6 SCREW
BUTTON HEAD
SOCKET CAP M17542
SCREW
Fig. 12. Junction box mounting (C7232A).
A C
M17541 ALLEN TOOL
OW
Fig. 11. C7232A cover removal. FL
WALL MOUNTING
The C7232 Wall Mount models can be mounted using two or
four screws:
1. Remove C7232 cover.
2. Mount the subbase to the wall using washers and two or
M17591
four screws (not supplied) appropriate for the wall
material.
Fig. 13. Duct mounting (C7232B).
63-2576—02 8
SOLID STATE ECONOMIZER SYSTEM
Wiring Operation
The factory ships the device with the output default settings
shown in Table 3 and Table 4. Set the jumpers and wire the Input Signal
device (see Table 2 and Fig. 14).
The C7232 Sensors have an adjustable range. These ranges
are determined by the SW1 and SW2 jumper settings
(see Table 3).
CAUTION
Electrical Shock or Equipment Damage Hazard. Table 3. CO2 Range Jumper Settings
Can shock individuals or short equipment
circuitry. SW1 SW2 AN (ppm) Relaya (ppm)
Disconnect power supply before installation. On On 0 to 1000 1000
On Off 0 to 2000 1200
CAUTION Offb Onb 500 to 1500 800
Equipment Damage Hazard. Off Off 500 to 2000 1200
Electrostatic Discharge Can Short Equipment
a
Circuitry. When the level reaches this value, the contacts close;
Ensure that you are properly grounded before when the level drops 100 ppm below this value, the con-
handling the unit. tacts open.
b Setting when shipped from the factory.
IMPORTANT
1. All low voltage connections to this device must be
24 Vac Class 2.
Output Signal
2. All wiring must comply with applicable local codes, The output signal can be adjusted for 0/2-10Vdc or 0/4-20mA
ordinances and regulations. (see Table 4).
Table 2. C7232 Wiring Connections (see Fig. 14). Table 4. Output Signal Jumper Settings
Voltage
Current
OFF
ON
OFF
ON
M19424
9 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
Example
For a CO2 setting of 0-2000 ppm and a voltage output of 0-10 Vdc, the output would be as shown in Table 5 (arbitrary points
along the analog curve).
For a CO2 setting of 0-2000 ppm and a voltage output of 2-10 Vdc, the output would be as shown in Table 6 (arbitrary points
along the analog curve).
Calibration Checkout
Typically, calibration is unnecessary. No calibration kits are Perform a quick test of the unit with the unit powered:
available. However, if CO2 gas can be purged from the sensor 1. Stand close to the unit and breathe air into the sensor.
chamber using a general gas purge device, the sensor can be 2. Check the CO2 level registered by the controller to
rezeroed: ensure a strong rise.
3. When connected to a damper in a ventilation system,
IMPORTANT the controller typically signals an increase in air flow.
Any CO2 present during calibration skews the sensor
zero level resulting in incorrect CO2 level reports.
63-2576—02 10
SOLID STATE ECONOMIZER SYSTEM
9/16
NOTE: The relationship between the C7400A Sensor output
(14) 7/32 3-7/8 (96) current and relative humidity is shown in Fig. 17.
(6)
1 (25) M9096
Installation 80
Location 70
PERCENT RF
IMPORTANT 60
20 m
16 m
12 m
4m
18 m
14 m
10 m
50
A
A
A
6m
A
A
40
NOTES:
— The C7400 Sensor can be mounted in any 30
position. However, the sensor must be installed
where it is exposed to freely circulating air, but 20
protected from rain, snow and direct sunlight.
— Differential enthalpy control requires two C7400 10
Sensors. Mount one sensor in the outdoor intake 40 50 60 70 80 90 100
duct, the other in the return air duct. (4) (10) (16) (21) (27) (32) (38)
— The C7400 Sensor is designed to operate in TEMPERATURE F ( C) M22117
500 ft/min. minimum airflow.
Fig. 17. C7400A Sensor output current vs. RH.
11 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
90
80
70
PERCENT RF
60
18 m
16 m
12 m
14 m
20 m
10 m
6m
8m
4m
A
A
A
A
A
A
A
50
40
30
20
10
40 50 60 70 80 90 100
(4) (10) (16) (21) (27) (32) (38)
TEMPERATURE ºF ( ºC) M27816
63-2576—02 12
SOLID STATE ECONOMIZER SYSTEM
(104)
Dimensions:
C7632A: See Fig. 9.
C7632B: See Fig. 10.
Electrical Ratings:
Power Supply: 24 Vac ±20%, 50/60 Hz (Class 2). 5-5/8
Maximum Power Consumption: (142)
Average: 1W.
Peak: 2W. 1-5/8
Peak Current (at 20 ms): 300 mA. (41) 8 (203)
Linear Analog Output: 0-10 Vdc. M19795
Approvals: CAUTION
CE. Equipment Damage Hazard.
Underwriters Laboratories Inc. Listed, File No. E4436. Electrostatic discharge can short equipment
cUL. circuitry.
C7632B: Flammability Rating, UL94-5V. Ensure that you are properly grounded before
C7632A: NEMA1. handling the unit.
C7632B: NEMA3.
13 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
C7632A Cover Removal/Replacement 4. Mount the subbase and wallplate to the junction box
The cover of the C7632A is fixed by a latch on the underside using the lower screw.
of the unit. 5. Replace the cover.
C7632A COVER REMOVAL (SEE FIG. 11) DUCT MOUNTING (SEE FIG. 13)
1. Unless the device is mounted, hold the base using the 1. Place gasket on aspiration tube.
wiring hole and/or the perforated vent.
2. Depress the tab on the underside of the device. IMPORTANT
3. Swing the cover away from the base. Ensure largest tab at tube control end is at the top.
4. Lift cover from base.
2. Insert tube into duct; attach using screws and washers.
C7632A COVER REPLACEMENT
1. Place top cover tab over the ridge along the base top. IMPORTANT
2. Swing the cover down. Leakage into the duct or the C7632 box cover from
3. Press the lower edge of the case to latch. the room will skew the sensor readings. Ensure the
box cover and duct seal completely.
Location and Mounting 3. Place o-ring on tube end; mount the control to the tube.
C7632 Sensors mount directly on the wall, sheet metal duct,
or a panel. When planning the installation, allow enough
clearance for maintenance and service. Mount the sensor in a
well-ventilated area.
M19797
OW
FL
M19796
63-2576—02 14
SOLID STATE ECONOMIZER SYSTEM
0-10 Vdc
NOTE: The device should now provide accurate out-
put.
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED. M19799 6. Check the output signal. (See “Checkout” on page 16.)
7. Reinstall the device.
Fig. 24. Wiring the C7632.
ZERO BACKGROUND
CALIBRATION CALIBRATION
Output (Table 5)
Table 8. 0-10 Vdc Output Signal.
CO2
Level 0 200 400 600 800 1000 1200 1400 1600 1800 2000
(ppm)
Voltage
Output 0 1 2 3 4 5 6 7 8 9 10 M19856
(Vdc)
Fig. 25. C7632 calibration pads.
15 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
63-2576—02 16
SOLID STATE ECONOMIZER SYSTEM
S
2-3/4
Output Signal: (70)
4 mA not OK to economize or 20 mA OK to economize.
17 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
4-1/2 (114)
1/4 (6)
5
(127)
2-1/4 (57)
7/16 3-1/2 (89) 1-1/4
(11) (32)
5-3/16 (132)
TOP VIEW SIDE VIEW POWER END VIEW M3851
63-2576—02 18
SOLID STATE ECONOMIZER SYSTEM
MAXIMUM MAXIMUM
Wiring
OPEN 1 CLOSED
POSITION POSITION
CAUTION
Electrical Shock or Equipment Damage Hazard.
MOTOR MOUNTING SURFACE Can shock individuals or short equipment
1 CRANK ARM FIELD ADJUSTABLE IN 7.5 DEGREE INCREMENTS. M3850 circuitry.
Disconnect power supply before installation.
Fig. 28. Limits of crank arm rotation.
The M7215 Damper Motor accepts input from a 2-10 Vdc
controller. The motor can be checked out either directly or by
Installation using a controller.
IMPORTANT
CAUTION 1. If necessary, release one of the previously tightened
linkage connections to prevent damage.
Electrical Shock or Equipment Damage Hazard. 2. Check for proper operation, making sure that the link-
Can shock individuals or short equipment age does not bind and that the motor travels smoothly
circuitry. throughout its cycle from fully open to fully closed.
Disconnect power supply before installation.
NOTES: This motor checkout assures that:
1. The motor operates the load.
CAUTION 2.
3.
The motor responds properly to the controller.
There is no linkage binding or motor stalling at
Personal Injury Hazard.
Spring-return assembly can release. any point of travel.
Leave end covers attached to the motor. 4. If questions arise regarding this product, contact
your distributor or local Honeywell representative.
Location and Mounting
Locate motor as close as possible to the equipment to be Direct Checkout
controlled. Refer to Fig. 27 for mounting dimensions. 1. Mount the motor for the required application.
2. Check the damper position and make sure 24 Vac is
1. Mount motor with the shaft horizontal to ensure present across TR and TR1.
maximum life. 3. Apply 10 Vdc to IN+ and IN- to move damper to the
opposite position. The motor should drive the damper.
NOTE: Operation in other positions is possible when 4. If the motor does not run, verify that the motor and crank
required by the application. arm are properly installed for either clockwise or
counterclockwise rotation.
2. Remove crank arm (secured with two screws) from the 5. If installation is correct, but the motor does not run,
motor hub. replace the motor.
IMPORTANT
Position crank arm on hub so it does not strike motor Controller Checkout
mounting surface during any portion of full stroke. 1. Adjust controller setpoint to call for cooling. Observe the
See Fig. 28. motor.
2. If the damper is closed, it should begin to open.
3. Reposition the crank arm to accommodate specific 3. If the damper remains closed, move controller setpoint
damper requirements. farther below room temperature.
4. If the damper still does not move, check for the
NOTE: Crank arm position is adjustable in eight presence of 24 Vac in the input.
degree increments. 5. If 24 Vac is present and motor does not operate, reverse
controller leadwires to determine if device was miswired.
6. If the wiring is correct and 24 Vac is present on the input
terminals but the motor does not run, replace the motor.
19 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
NOTES: 1-5/8
— All models include a minimum damper position (41)
potentiometer, and setpoints for: enthalpy or
dry-bulb, occupied/unoccupied control, DCV
operation, and DCV maximum.
— Occupied/Unoccupied overrides minimum
damper position setting when building is
unoccupied. 2-1/16
(53)
Dimensions: See Fig. 29. 1-15/16
(49)
Electrical Ratings:
4-1/8
Input Voltage: 24 Vac ±20%; 50/60 Hz (Class 2). (104)
Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA.
Relay Contact Rating at 30 Vac (maximum power from class 2
input only): 1.5A run, 3.5A inrush.
IMPORTANT
All inputs and outputs must be 24 Vac Class 2.
63-2576—02 20
SOLID STATE ECONOMIZER SYSTEM
Wiring
M7215 DAMPER MOTOR
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
W7212
ECONOMIZER
LOGIC MODULE IMPORTANT
1. All wiring must comply with applicable local codes,
ordinances and regulations.
2. All device inputs and outputs must be 24 Vac Class 2.
3. Ensure proper polarity of sensor connections.
Incorrect polarity negates the sensor signal.
21 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
DISCHARGE SPACE
AIR SENSOR THERMOSTAT
DIRECT DCV
C7046A 2 C7232
EXPANSION SENSOR
COIL
2
W7212, C7150B
W7213, C7400 ENTHALPY
1
W7214 MIXED AIR SENSOR
SENSOR
INDOOR
FAN
HONEYWELL
DISCHARGE ACTUATOR
AIR
OUTDOOR
AIR
C7400 1
ENTHALPY
SENSOR
63-2576—02 22
SOLID STATE ECONOMIZER SYSTEM
R MINIMUM
CW P1 POSITION
CLOSE ADJUSTMENT
P
W B
CW
ECONOMIZER
M20603A
NOTES:
— DCV and Free Cooling have setpoints and LED indications.
— For models with a B terminal (W7213):
No power to B: cooling mode, free cool enabled. Module follows logic detailed above.
24V power to B: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).
— For models with an O terminal (W7214):
24V power to O: cooling mode, free cool available. Module follows logic detailed above.
No power to O: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).
23 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
Demand Control Ventilation Setpoint NOTE: Make minimum position adjustments with at least a
The logic module modulates the outdoor damper to provide 10°F [6°C] temperature difference between outdoor
ventilation based on the 0/2-10 Vdc DCV. With no cooling and return air.
signal, the DCV overrides the outdoor air damper when
ventilation requires outdoor air. 1. Calculate the appropriate mixed air temperature, see
Equation 1. Formula to aid minimum position adjust-
ment.
EXHAUST 2. Disconnect mixed air sensor from terminals T and T1.
FAN SETPOINT 3. Ensure that either the factory-installed jumper is in place
LED LIGHTS
N1 EXH
Set
across terminals P and P1 or, of remote damper posi-
WHEN EXHAUST N 2V 10V tion is required, that it is wired according to Fig. 33 and
CONTACT IS MADE
P1 EXH turned fully clockwise.
MINIMUM DAMPER
POSITION SETTING P Min
4. Connect 24 Vac across terminals TR and TR1.
T1
Pos
5. Carefully adjust the potentiometer on the face of the
MAXIMUM DAMPER
DEMAND CONTROL
T
Open
device with a small screwdriver until the mixed air
VENTILATION SETPOINT DCV temperature reaches the calculated value.
Max
LED LIGHTS WHEN 2V 10V
DEMAND CONTROL
VENTILAION INPUT
AQ1
DCV NOTE: Ensure that the sensed air is well mixed.
AQ
IS ABOVE SETPOINT DCV
SO+
2V
Set
10V Equation 1. Formula to aid minimum position adjustment.
( T O × OA ) + ( T R × RA ) = T M
SO
DEMAND CONTROL Free
SR+ Cool
VENTILAION SETPOINT
SR B C Where:
LED LIGHTS WHEN A D TO = Outdoor air temperature
OUTDOOR AIR IS
SUITABLE FOR
OA = Percent of outdoor air
FREE COOLING TR = Return air temperature
ENTHALPY
CHANGEOVER SETPOINT M20604
RA = Percent of return air
TM = Resulting mixed air temperature
Fig. 34. Potentiometer and LED locations.
IMPORTANT
This procedure requires use of a quality thermometer
Adjusting Minimum and Maximum capable of reading to 0.5°F [0.25°C].
Positions
NOTE: The following sample calculation uses only
The minimum position potentiometer maintains the minimum
Fahrenheit temperature.
outdoor air flow into the building during occupied period. The
DCV maximum position potentiometer allows the installer to EXAMPLE: Assume local codes require 10% outdoor air
limit the amount of outdoor air flow into the building when the during occupied conditions, outdoor air is 60°F
DCV overrides the mixed air sensor. Setting the DCV and return air is 75°F. Under these conditions,
maximum position of the damper prevents the introduction of what is the temperature of the mixed air?
large amounts of hot or cold air into the space.
( 0.1 × 60°F ) + ( 0.9 × 75°F ) = 6.0°F + 67.5°F = 73.5°F
IMPORTANT
With the DCV maximum position set below the Mixed air will be 73.5°F when OA is 60°F and RA is 75°F with
minimum position, the minimum position overrides 10 percent outdoor air entering the building.
the maximum position (negating most DCV functions
of the logic module, as the damper cannot move). DCV MAXIMUM POSITION ADJUSTMENT
1. Disconnect mixed air sensor from terminals T and T1
NOTES: and short terminals T and T1.
— When the mixed air sensor takes control, it 2. Connect a jumper between terminals AQ and SO+.
overrides the DCV maximum position 3. Connect 24 Vac across terminals TR and TR1.
potentiometer.
— If the mixed air temperature drops to 45°F, the 4. Adjust the potentiometer on the face of the device with a
mixed air sensor overrides the DCV and fully screwdriver for desired maximum position.
closes the damper to protect from freezing the hot
or chilled water coils. Control returns to normal
once the mixed air temperature rises to 48°F.
63-2576—02 24
SOLID STATE ECONOMIZER SYSTEM
Enthalpy Changeover The logic module selects the lower enthalpy air (return or
outdoor) for cooling. For example, when outdoor air has lower
OUTDOOR ENTHALPY CHANGEOVER SETPOINT enthalpy than return air, the outdoor air damper opens to bring
(SINGLE ENTHALPY) in outdoor air for free cooling.
The outdoor enthalpy changeover setpoint returns the outdoor
air damper to minimum position when enthalpy rises above its Exhaust Setpoint
setpoint. Enthalpy setpoint scale markings, located in the The exhaust setpoint determines when the exhaust fan runs
device, are A, B, C, and D. See Fig. 35 for the corresponding based on damper position. When the exhaust fan call is
control point. The factory-installed 620-ohm jumper must be in made, the module provides a 60 ±30 second delay before
place across terminals SR and SR+. exhaust fan activation. This delay allows the damper to reach
the appropriate position to avoid unnecessary fan overload.
DIFFERENTIAL ENTHALPY CHANGEOVER SETTING
Differential enthalpy control uses two C7400 Enthalpy NOTE: EF and EF1 are dry contacts only. An external line
Sensors connected to one logic module. The logic module voltage contactor is required to operate the exhaust
compares outdoor air to return air instead of to a setpoint as it fan.
does for single enthalpy.
46
CONTROL CONTROL POINT 44
CURVE APPROX. °F (°C)
AT 50% RH 80
42
(27)
A 73 (23)
40
B 70 (21)
)
(%
R
C 67 (19)
AI
38
TY
D 63 (17)
RY
IDI
75
34 D D
36
UM
(24)
UN
EH
PO
TIV
R
32
PE
LA
70
U
30
BT
RE
(21)
—
PY
28
AL
0
10
90
26
TH
65
80
EN
(18)
70
24
60
22
60
50
(16)
20
A
40
55
18
(13) B
30
16
50
(10) C
20
14
45 D
12
(7)
40
(4) 10
35
(2)
1
B A
D C
Fig. 35. Partial psychrometric chart with single C7400A Solid State Enthalpy Sensor and
W7212 Solid State Economizer Logic Module performance curves.
25 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
46
CONTROL CONTROL POINT
44
CURVE APPROX. °F (°C)
AT 50% RH 80
42
(27)
A 73 (23)
40
B 70 (21)
)
(%
R
C 67 (19)
AI
38
TY
D 63 (17)
RY
IDI
E 55 (13) 75
34 D D
36
UM
(24)
UN
EH
PO
TIV
R
32
PE
LA
70
U
30
BT
RE
(21)
Y—
28
LP
0
HA
10
90
26
65
T
80
EN
(18)
70
24
60
22
60
50
(16)
20
40
55
18
(13) B
30
16
50
(10) C
20
14
45 D
12
(7)
40
(4) E 10
35
(2)
1
B A
D C
E
Fig. 36. Partial psychrometric chart with single C7400C Solid State Enthalpy Sensor and W7212 Solid State Economizer
Logic Module performance curves.
63-2576—02 26
SOLID STATE ECONOMIZER SYSTEM
N1 TR TR1
24 VAC HOT
MINIMUM POSITION 24 24 Vac
P1
ADJUSTMENT Vac COM
HOT 24 VAC COM
C7150B MIXED P
AIR OR C7046A T1 + ñ
DISCHARGE 2-10 VDC CONTROL
T
AIR SENSOR SIGNAL INPUT
1 2
AQ1
0/2-10 VDC ñ 5
INDOOR AIR AQ
SENSOR + SO+ 3 4
SO
SR+ EF EF1
SR
M7215
C7400 W7212 5
OUTDOOR + 3
AIR
ENTHALPY 620 OHM L1
SENSOR S RESISTOR (HOT)
L2
EXHAUST
FAN
Y1 C
Y2 Y1 COOL 1
W2 Y2 COOL 2
W1
W2 HEAT 2
A3
4 W1 HEAT 1
A2
A3
G
A2
RH
G FAN
2
RC
L2
1
X R L1
(HOT)
T7300/Q7300 HVAC EQUIPMENT
THERMOSTAT TERMINAL STRIP
2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
3 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
4 T7300 TERMINALS A1 AND A3 ARE CONNECTED WHEN THERMOSTAT IS IN THE UNOCCUPIED MODE.
27 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
P1 EXH
CAUTION
Min
Pos
T1
1 Open
T
SR B C
A D
2
620 OHM RESISTOR
1 INSERT DC VOLTMETER BETWEEN AQ AND AQ1 FOR
CHECKOUT AND TROUBLESHOOTING.
63-2576—02 28
SOLID STATE ECONOMIZER SYSTEM
Table 10. Checkout for W7212 Economizers Connected to Honeywell Actuator. (Continued)
Step Checkout Procedure Proper Response
4. DCV AND EXHAUST
Execute step one, Checkout Preparation. —
Ensure terminals AQ and AQ1 are open. LED for both DCV and Exhaust should be off.
Actuator drives fully closed.
Connect 9V battery positive to AQ and negative to AQ1. LED for both DCV and Exhaust turn on.
Actuator drives 90 to 95 percent open.
Turn Exhaust potentiometer CW until Exhaust LED turns off. Exhaust LED turns off with potentiometer at approximately 90 percent.
Actuator remains in position.
Turn DCV potentiometer CW. DCV LED turns off with potentiometer at approximately 9V.
Actuator drives fully closed.
Turn DCV and Exhaust potentiometers CCW until Exhaust LED turns on. Exhaust contacts close 30-120 seconds after Exhaust LED turns on.
5. MINIMUM AND MAXIMUM POSITION
Execute step one, Checkout Preparation. —
Connect 9V battery positive to AQ and negative to AQ1. DCV LED turns on. Actuator drives 90 to 95 percent open.
Turn DCV maximum position potentiometer to midpoint. Actuator drives to between 20 and 80 percent open.
Turn DCV maximum position potentiometer to fully CCW. Actuator drives fully closed.
Turn minimum position potentiometer to midpoint. Actuator drives to between 20 and 80 percent open.
Turn minimum position potentiometer fully CW. Actuator drives fully open.
W7212: Remove jumper from TR and N. Actuator drives fully closed.
W7213, W7214: Jumper TR to N.
6. MIXED AIR INPUT
Execute step one, Checkout Preparation. —
Set enthalpy potentiometer to A. Free cool LED turns on.
Actuator drives to between 20 and 80 percent open.
Remove 5.6K ohm resistor and jumper from T and T1. Actuator drives fully open.
Remove jumper from T and T1 and leave open. Actuator drives fully closed.
7. HEAT PUMP INPUT - W7213, W7214 ONLY
Execute step one, Checkout Preparation. —
Set enthalpy potentiometer to A. Free cool LED turns on.
Actuator drives to between 20 and 80 percent open.
W7213: Jumper TR to B. Free cool LED turns off.
W7214: Remove jumper from TR and O. Actuator drives fully closed.
29 63-2576—02
SOLID STATE ECONOMIZER SYSTEM
Appendix
IMPORTANT
This page is only for C7232 models with date code prior to 0309.
20 – 100%
OUT1
0 – 100%
Select
NOTE: When choosing analog output, be sure to set the
Voltage
Voltage
Current
Current
OFF
ON
OFF
SW1 jumper to the On position.
ON
AN1
AN2
Table 11. CO2 Range Jumper Settings for models
with date code prior to 0309.
Jumper SW1 Jumper SW2
Ona Ona
M20494
Jumper Setting Off Off
OUT1b AN1 X —c 0 to 1000 0 to 2000 Fig. 39. C7232 default jumper settings for models
with date code prior to 0309.
AN2a X —c 500 to 1500 500 to 2000
OUTPUT SIGNAL
The output signal can be adjusted for 0/2-10Vdc or 0/4-20mA
(see Table 12).
NOTES:
— On duct models with date code prior to 0309, remove
the screw holding the board in place to view jumper
settings on reverse. (See Fig. 39.)
— The CO2 settings and the output signal settings are
independent of each other. 0-100% and 20-100% are
simply markings for the OUT jumper settings on the
sensor (to differentiate between the two voltage and the
two current ranges) and do not refer to or alter the ppm
range chosen.
63-2576—02 30
SOLID STATE ECONOMIZER SYSTEM
31 63-2576—02
SOLID STATE ECONOMIZER SYSTEM