Sno Service Pipe Material: 4. Non Ibr Pipings

This document provides information about the materials and design specifications for pipe systems in a 30 MW captive power plant project for M/s. Bharathi cement corporation in Kadapa, Andhra Pradesh, India. It lists pipe materials for various plant systems, such as water treatment, RO water, circulating water, and others. It also provides recommended maximum velocity ranges for different pipe sizes and services, including steam, compressed air, pump suction and discharge, and pipe headers. The specified velocities are indicative and lower values may be selected if necessary.

Uploaded by

Arun Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views

Sno Service Pipe Material: 4. Non Ibr Pipings

This document provides information about the materials and design specifications for pipe systems in a 30 MW captive power plant project for M/s. Bharathi cement corporation in Kadapa, Andhra Pradesh, India. It lists pipe materials for various plant systems, such as water treatment, RO water, circulating water, and others. It also provides recommended maximum velocity ranges for different pipe sizes and services, including steam, compressed air, pump suction and discharge, and pipe headers. The specified velocities are indicative and lower values may be selected if necessary.

Uploaded by

Arun Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project: 1 x 30 MW (Gross)Captive Power Plant

Customer: M/s. Bharathi cement corporation. Kadapa, A.P.


Design Centre, Chennai

4. Non IBR pipings

S No Service Pipe Material

Water treatment plant


1. UPVC / MSRL as applicable
piping
For RO water after pH SS304
2.
boosting
Circulating water,
auxiliary cooling water,
IS 1239 Part-I Black Medium Class 150 NB
3. Plant water, service
IS 3589 ERW > 150 NB
water and potable water
piping
4. Service air applications IS 1239 Black Medium Class

5. Instrument air applications IS 1239 Part-I GI pipes

5. Velocity considered:
Nominal pipe size Average velocity in Meter / Second
in mm Below 50 to 200 mm &
50 mm 150 mm above
Saturated steam at sub-atmospheric Pressure - 10 - 15 15 - 20
Saturated steam at 0-1 kg/sq.cm.(g) 15 - 20 17 - 30 20 - 30
Saturated steam at 1.1 - 7 kg/sq.cm.(g) 15 - 22 20 - 33 25 - 43
Saturated steam over 7 kg/sq.cm.(g) 15 - 25 20 - 35 30 - 50
Superheated steam at 0 - 7 kg/sq.cm.(g) 20 - 30 25 - 40 30 - 50
Superheated steam at 7.1 - 35 kg/sq.cm.(g) 20 - 33 28 - 43 35 - 55
Superheated steam at 35.1 - 70 kg/sq.cm.(g) 22 - 33 30 - 50 40 - 61
Superheated steam over 70 kg/sq.cm.(g) 22 - 35 35 - 61 50 - 76
Compressed air 7 - 10 10 -15 18
Pump suction, condensate - 0.4 - 0.6 0.6 - 0.7
Pump suction, boiler feed - 0.6 - 0.9 0.6 - 0.9
Pump suction, general service 0.6 - 0.9 0.7 - 1.3 0.9 - 1.5
Pump suction, viscous liquid 0.3 0.3 - 0.4 0.4 - 0.5
Pump discharge, condensate 0.9 - 1.2 1.2 - 2.1 1.5 - 2.2
Pump discharge, boiler feed 1.0 - 1.2 1.5 - 2.1 1.8 - 2.4
Pump discharge, general service 0.9 - 1.0 1.5 - 2.4 1.5 - 2.4
Pump discharge, viscous liquid 1.0 1.0 1.2 - 1.4
Header, general service under 2.0 - 1.3 - 2.0 1.8 - 2.4
kg/sq.cm.(g)
Header, general service 2.0 kg/sq.cm.(g) & up - 1.5 - 2.4 2.1 - 2.4

Note: The above velocity values are indicative and showing the Maximum limits of the
flow velocity. Lower velocities may be selected if found necessary.

Doc Name : DESIGN BASIS REPORT (MECHANICAL) Date: 28.05.13


Doc No : JP0024-75990100-DBR-001 Page 43 of 48