Dimensioning of Current Transformers For Protection Applications
Dimensioning of Current Transformers For Protection Applications
GE Multilin
Technical Notes
Dimensioning of Current
Transformers for Protection
Applications
GE Publication No.: GER-3973A
INTRODUCTION When system protection installed on CT secondaries must correctly respond to short cir-
cuit transients, especially during the first few cycles, fault conditions (even more than
steady state under load conditions) must be taken into account when using current trans-
formers. As such, it is necessary to define how much a CT must be oversized to avoid
saturation due to the asymmetrical component of the fault current (the DC offset or expo-
nential component).
The initial value of this DC offset is dependent on the voltage incidence angle (the volt-
age value when the fault occurs). The line parameters may be between 0 and 2I sc ,
where I sc represents the RMS value of the short-circuit symmetrical current.
Considering this maximum value, the transient short-circuit current is defined by the fol-
lowing equation:
t T 1
i ( t ) = I sin ( t + ) + I sin ( ) e (EQ 1)
Ep
where: I = peak value of the current = ------------------------------
2 2 2
R + L
Ep = peak system E.M.F.
R = system resistance
L = system inductance
= 2f
= angle on the voltage wave at which fault occurs
= arctan ( X R )
T1 = X R of the power system
1
GER-3973A: Dimensioning of current transformers for protection applications
Assuming that the secondary load is essentially resistive, the necessary flux in the CT to
avoid saturation is defined as follows:
ts ts
T 1 T 2 ----- T
- ------
T
T = A ------------------ e 1 e 1 sin t (EQ 2)
T1 T2
For T2 >> T1 (the case of TPY and TPX class CTs with and without air gaps), Equation
2 is reduced to:
ts
------
T
T = A T 1 e 1 sin t (EQ 3)
As the load and wiring are mainly resistive, we can consider sin t = 1 ; as such, Equa-
tion 3 is reduced to:
ts
------
T1
T = A T 1 e + 1 (EQ 4)
Finally, since ts (relay response time + circuit breaker operating time) is normally much
greater than T1, the above expression can be reduced to:
T = A ( T 1 + 1 ) (EQ 5)
During faults, the CTs are forced to develop a flux sufficient to feed fault current to the
secondary with two components: the exponential component (DC offset asymmetrical
component) and the AC component (symmetrical component). The resultant voltage
must be greater than that necessary to feed the load connected in the secondary side of
CTs without distortions caused by saturation. Hence, the necessary oversize factor Ks is
defined by:
transient = DC + AC = K s A (EQ 6)
ts
-----
-
T1
K s = T 1 e sin t (EQ 7)
2 GE Multilin
GER-3973A: Dimensioning of current transformers for protection applications
DESCRIPTION Testing and experience have shown that the performance of many relays can be
adversely affected by moderate degrees of CT saturation. However, since it is not eco-
nomically feasible to test and determine the performance of all relays with different
degrees of saturation, it is common practice to specify CT requirements for various pro-
tective schemes. The requirement generally specified is that the CTs should not saturate
before the relays operate for some specified fault location.
To meet this criterion, the required transient performance for a current transformer can
be specified by calculating the minimum required saturation voltage. Generally, different
standards as IEC 185, BS3938, or ANSI/IEEE C5713 fix this voltage through the general
expression:
Vs = K0 Ks KR I2 R2 (EQ 8)
The offset present during the fault (K0) is a function of the time when the fault occurs,
being maximum at zero voltage (0 or 180). Incidence angles of the faulted voltage near
90 generally produce a lower offset effect. Therefore, this factor applies in those cases
where offset exceeds 0.5 p.u.
The remanent flux can remain in the core due to the following:
The excitation current leads the load current by 90 and thereby under normal control
open commands, the load current is cut near or at zero crosses, but the excitation
current in the CT has significant value.
DC tests performed on the CTs.
The effect of the DC component on offset fault currents (exponential component)
which is interrupted when tripping the circuit breaker.
The saturation or transient factor Ks is expanded as follows (as per Equation 2):
ts ts
T 1 T 2 ----- -
T1
------
T1
K s = ------------------ e e sin t (EQ 9)
T1 T2
Equation 2 is valid for CTs with air-gapped cores because of their low magnetizing
impedance and then with low secondary time constant T2. The air-gaps used in CTs
GE Multilin 3
GER-3973A: Dimensioning of current transformers for protection applications
tends to drastically reduce the effect of the remanent flux left in the core as a result of its
lower magnetizing impedance and much lower secondary time constant. The effect of
the remanent flux is also to reduce the time to saturation. This factor may vary from 1.4 to
2.6 times the rated flux in the core.
For a closed-core CTs (normal CTs), if the secondary time constant T2 is too high
( L magnetizing before saturation), Equation 7 does not include it. As such, a conserva-
tive value for time to saturation will result.
DESCRIPTION After the appearance of the short circuit, the flux 0 and the corresponding magnetizing
current I0 will reach a maximum at a time defined by:
T1 T2 T
t ( max ) = ------------------ ln -----1- (EQ 10)
T1 T2 T2
XR Ks 1
t s = ------------ ln --------------- (EQ 11)
2f XR
The rate of decay of the DC component is proportional to the ratio of reactance to resis-
tance of the complete circuit from the generator (source) to the short circuit.
If the ratio of reactance to resistance is infinite (i.e. zero resistance), the DC component
never decays. On the other hand, if the ratio is zero (all resistance, no reactance), it
decays immediately. For any ratio of reactance to resistance in between these limits, the
DC component takes a definite time to decrease to zero.
Generators, motors, and circuits all have a certain DC time constant that refers to the
rate of decay of the DC component. The DC time constant is the time, in seconds,
required by the DC component to drop to approximately 37% of its original value at the
instant of short circuit. It is expressed as the ratio of inductance in Henrys (V s / A) to
resistance in Ohms. This is merely a guide to illustrate how quickly the DC component
decays.
4 GE Multilin
GER-3973A: Dimensioning of current transformers for protection applications
TYPICAL X/R RATIOS Typical values of X / R ratios of distribution and transmission lines, depending on their
rated voltages and geometrical configuration, are shown in the following table.
The table below shows the X / R ratios for selected power system elements as a function
of their rated power.
TABLE 2. X/R Ratios for Other Power System Elements
Large Power
Generators Transformers Reactors Utilities
40 to 120 see curve 40 to 120 15 to 30
typically 80 typically 80 (near generating plant)
Power transformer X / R ratios for 0.03 to 3.0 MVA and 3 to 200 MVA rated transformers
are indicated in the curves below:
10
9
8
7
6
X/R Ratio
5
4
3
2
1
0
0 0.5 1 1.5 2 2.5 3 3.5
50
40
X/R Ratio
30
20
10
0
0 50 100 150 200 250
ONAN MVA Rating (3 to 200 MVA)
842738A1.CDR
GE Multilin 5
GER-3973A: Dimensioning of current transformers for protection applications
DESCRIPTION Instantaneous overcurrent (ANSI device 50) and distance (ANSI device 21) protection
normally operate in a 15 to 30 ms range. As such, dimensioning factors must recognize
that relay tripping times should be lower than time to saturation ts. To guarantee the cor-
rect operation of protection devices, Equation 2 must be applied with parameter t repre-
senting the instantaneous overcurrent operating time of the relay. The following table
shows typical tripping times for different GE relays and the necessary overdimensioning
factor Ks, using a class TPX CT with a secondary time constant T2 = 3 seconds.
DESCRIPTION With results shown in the table above and neglecting the K0 and KR parameters in Equa-
tion 8, the following example illustrates how to determine the resultant precision limit
and the necessary overdimensioning of the CT core (rated power dimensioning) to avoid
saturation previous to the tripping time of relays under consideration.
If the phase-to-phase short circuit current is assumed to be the same order of magnitude
as the phase-to-ground short circuit current, then a single equation should be used. If
not, then the Ks factor must be verified for both situations: the positive sequence compo-
nent during three-phase faults as well as the zero sequence component for phase-to-
ground faults. In the present case, Equation 8 will be used for all calculations.
6 GE Multilin
GER-3973A: Dimensioning of current transformers for protection applications
P short-circuit 3V rated
V s = ----------------------------------------------------- K s ( R CT + R wiring + R relay )
CT ratio
0.597 GVA ( 3 13.8 kV ) (EQ 12)
= ----------------------------------------------------------------------- 6.18 ( 1.5 + 0.059 + 0.04 )
600
= 411 V
V 20- 1.5 ( 1 ) 2 = 19 VA
P equivalent = 411
------------------------- (EQ 13)
1A
RATED PRIMARY SHORT The rated primary short circuit current is the RMS value of the primary symmetrical short-
CIRCUIT CURRENT circuit current on which the rated accuracy performance of the current transformer is
based.
INSTANTANEOUS ERROR The instantaneous error current (Ie) is the difference between instantaneous values of
CURRENT the primary current and the product of the turns ratio times the instantaneous values of
the secondary current. When both alternating current and direct current components are
present, Ie must be computed as the sum of both constituent components:
I e = I e ( AC ) + I e ( DC )
(EQ 14)
= ( nI secondaryAC I primaryAC ) + ( nI secondaryDC I primaryDC )
PEAK INSTANTANEOUS The peak instantaneous error (i ) is the maximum instantaneous error current for the
ERROR specified duty cycle, expressed as a percentage of the peak instantaneous value of the
rated primary short-circuit current
PEAK INSTANTANEOUS AC The peak instantaneous AC component error is the maximum instantaneous error of the
COMPONENT ERROR alternating current component expressed as a percentage of the peak instantaneous
value of the rated primary short-circuit current.
100I e ( AC )
AC = ------------------------------------------------- % (EQ 15)
2I primary short-circuit
GE Multilin 7
GER-3973A: Dimensioning of current transformers for protection applications
CT ACCURACY CLASS / The accuracy class is defined by the class index (see below) followed by the letter P.
CLASS INDEX
The class index represents the accuracy limit defined by composite error (c ) with the
steady state symmetrical primary current. This number indicates the upper limit of the
composite error at the maximum accuracy current feeding the accuracy load. The stan-
dard class indexes are 5 and 10.
LIMIT FACTOR The limit factor represents the ratio between the limit accuracy current and the rated pri-
mary current. For protection applications this factor normally is 10 or 20.
PRIMARY AND SECONDARY The primary time constant T1 represents the time constant of the DC component of the
TIME CONSTANTS primary current on which CT performance is based.
The secondary time constant T2 represents the time constant of the secondary loop of
the CT obtained from the sum of the magnetizing and leakage inductance (Ls) and the
secondary loop resistance (Rs). Normally, this value is higher than T1 in TPS class cur-
rent transformers (about 10 seconds). The value of T2 depends on the specific require-
ments but normally oscillates between 0.3 and 1 second for TPY class CTs. For TPZ
class CTs, T2 is generally much more lower (approximately 0.07 seconds).
TIME TO MAXIMUM FLUX The time to maximum flux ( t (max) see Equation 10) is the elapsed time during a pre-
scribed energization period at which the transient flux in a CT core achieves maximum
value, assuming that core saturation does not occur.
SECONDARY WINDING AND The secondary winding resistance RCT represents secondary winding DC resistance in
LOOP RESISTANCE ohms, corrected to 75C (unless otherwise specified) and inclusive of all external burden.
The secondary loop or burden resistance (RB) is the total resistance of the secondary cir-
cuit, unless otherwise specified, and inclusive of all external burden.
8 GE Multilin
GER-3973A: Dimensioning of current transformers for protection applications
FLUX PARAMETERS A low leakage flux current transformer is a CT for which a knowledge of the secondary
excitation characteristic and secondary winding resistance is sufficient for an assess-
ment of its transient performance. This is true for any combination of burden and duty
cycle at rated or lower value of primary symmetrical short-circuit current, up to the theo-
retical limit of the current transformer determined from the secondary excitation charac-
teristic.
The saturation flux (S) is the peak value of the flux that exists in a core during a transi-
tion from a non-saturated to a fully saturated condition. This corresponds to the point on
the B-H characteristic of the core at which a 10% increase in B causes H to be increased
by 50%.
The remanent flux (R) is the value of flux that remains in the core three minutes after
the interruption of an exciting current of sufficient magnitude as to induce the saturation
flux (S).
GE Multilin 9