Intelecool2 User Manual (08-06)
Intelecool2 User Manual (08-06)
Liebert InteleCool2
User Manual - Outdoor Wall-Mount Air Conditioner,1.5 - 5 Tons, 50 & 60 Hz
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Optional Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.1 Refrigeration System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Ancillary Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.1 Room Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.3 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Unit Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5.1 Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5.2 Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Outside Air Damper - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Economizer - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.0 CHECKLIST FOR COMPLETE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.0 START-UP PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Compressorized Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Economizer Cooling - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.1 Enthalpy Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.2 Actuator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3 Heating - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.4 Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.1 Remote Control Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.2 High Pressure (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.3 Refrigeration Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.4 Anti-Short Cycle Timer - Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.5 Heater Protection - With Optional Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.6 Lockout Relay - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.7 Common Alarm - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1 Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.2 Blower Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.3 Economizer - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4 Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
i
6.5 Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.5.1 Refrigerant Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.5.2 Discharge Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.5.3 Thermostatic Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.5.4 Air-Cooled Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.6 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.6.1 Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.1 Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.2 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.0 MAINTENANCE INSPECTION CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10.0 PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
ii
FIGURES
Figure i Model number designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Figure 1 Unit mounting dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2 Low volt wiring terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 3 Mounting minimum position potentiometer on actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 4 Refrigeration system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5 Enthalpy control setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 6 Dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 7 Condenser/piping assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 8 Crankcase heater (reciprocating compressor only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 9 Evaporator blower. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 10 Evaporator coil and expansion valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 11 Electric panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 12 Heater assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 13 Economizer assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 14 Common alarm assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 15 Soft start device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
TABLES
Table 1 Mounting dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 Operating modes/contact closures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 3 Recommended applications for control options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 4 Pressure information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 5 InteleCool2 dimensional data in. (mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 6 Technical data, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 7 Technical data, 60 Hz, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 8 Technical data, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 9 Technical data, 50 Hz, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 10 Optional heater capacity, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 11 Optional heater capacity, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 12 Electrical data, 60 Hz - amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 13 Electrical data, 50 Hz - amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 14 Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 15 Refrigeration system parts, 1.5 and 2 ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 16 Refrigeration system parts, 3 ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 17 Refrigeration system parts, 4-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 18 Refrigeration system parts, 5-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 19 Electric panel, 1.5- and 2-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 20 Electric panel parts, 3-ton units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 21 Electric panel parts, 4-ton unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 22 Electric panel parts, 5-ton unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 23 Motor parts, heater, Economizer, 1.5- and 2-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 24 Motor parts, heater, Economizer, 3-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 25 Motor parts, heater, Economizer, 4-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 26 Motor parts, heater, Economizer, 5-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
iii
Figure i Model number designation
External Telecommunication
R = Right Compressor
L = Left Compressor
P = 208/230V 1 ph - 60 hz
S = 220/240 1 ph - 60 hz
A = 460V 3 ph - 60 hz
Y = 208/230V 3 ph - 60 hz
N = 200/230 3 ph - 50 hz
M = 380/415V 3ph - 50 hz
ET 0 36 H R P F B T
0 = Standard
F = Fixed Outside Air Damper
E = Economizer
0 = No Heat
A = 5 kW Heat
B = 10 kW Heat
C = 15 kW Heat
iv
Introduction
1.0 INTRODUCTION
1.1 General
The Liebert InteleCool2 Environmental Control System was designed for convenience and dependabil-
ity in unmanned and remote locations typical of the telecommunications industry. Ease of installation,
operation and service coupled with the use of high quality, high reliability components make InteleCool2
ideally suited for maintaining an environment for sensitive electronic equipment. Standard units are
NRTL-C listed/certified to meet U.S. and Canadian safety standards, and MEA listed for New York City
applications. These agency listings insure fast, hassle-free inspection and building code approvals.
Self-Contained
The InteleCool2 product is completely self-contained. All components are enclosed in the weather-
proof cabinet.
Space Savings
The InteleCool2 does not use any of the valuable floor space inside the secure space. Instead, it is
mounted on the outside wall. No additional space is required outside or on a roof.
Easy to Install
The InteleCool2 is assembled, wired, piped, charged with refrigerant, and fully factory tested as a sys-
tem to ensure trouble free installation and start-up.
1.2 Standard Features
Reciprocating Hermetic Compressor1.5, 2 and 3 Ton Units
The heart of the refrigeration system is a reciprocating hermetic compressor. The compressor features
a suction gas cooled motor, internal centrifugal oil pump, vibration isolating mountings, internal
thermal overloads, and crankcase heater.
Scroll Compressor4 and 5 Ton Units
The quiet and efficient scroll compressor features a suction gas cooled motor, internal centrifugal oil
pump, vibration isolating mountings and internal thermal overloads.
Refrigeration System
The refrigeration circuit includes a liquid line filter drier, an externally equalized expansion valve,
and a high-pressure switch.
Evaporator Coil
The evaporator coil is constructed of mechanically expanded copper tubes in enhanced surface alumi-
num fins. A coated, galvanized steel condensate drain pan is provided.
Condenser Coil
The air-cooled condenser coil is constructed of mechanically expanded copper tubes in enhanced sur-
face aluminum fins. Components rated for up to 115F (46C) ambient.
Evaporator Blower
Evaporator air is supplied by a direct drive blower package. Fans are centrifugal, double width, dou-
ble inlet.
Filter
The filter is 2 inches deep, pleated, with a minimum efficiency rating of 20% (based on ASHRAE stan-
dard 52.1). Located within the cabinet, the filter is serviceable from the front of the unit.
Cabinet
The exterior cabinet is constructed of painted steel. Internal structural parts (including base) are hot
dipped galvanized steel. The evaporator compartment is insulated with 1/2" thick, 2 lb. density, neo-
prene-faced, fiberglass insulation.
Control Interface
The unit is supplied with customary HVAC wiring designations (R, G, W, Y) inside the low voltage
partition of the unit electric box. The control interface can be provided by sources ranging from a wall
mounted thermostat, a Liebert control and monitoring system or a third party building management
control.
1
Introduction
2
Introduction
1.5 Accessories
Dual Unit Control
The hinged cover dual unit control (DUC) has a two-stage heat/cool thermostat with individual heat-
ing and cooling setpoints, adjustable interstage differentials, and bimetallic elements. The control
features a solid state timer with 1-2-4-8 day sequence. Unit lead selector, unit 1 & 2 power-on LEDs,
unit 1 or 2 lead unit LEDs, 48 hour program save on loss of power, industry standard connections and
24V power from each unit. The DUC provides auto sequencing and displays on-status and operating-
status parameters.
Tele2 Control
This microprocessor-based controller controls two InteleCool2 units. The unit has a 10-key keypad,
four-row by 20-column LCD, an RS-232 modem port, and an RS-232 terminal port. It allows up to
eight customer-selectable, isolated normally open, dry contact alarm inputs. The Tele2 control
requires either a THS28-30 or a THS28-60 sensor assembly. Models are available for
120/50-60/1 VAC, 230/50-60/1 VAC or 48 VDC power.
3
Installation
2.0 INSTALLATION
2.1 Preparation
2.1.1 Room Preparation
The room should be well-insulated and should be sealed to reduce airborne contaminants from pene-
trating the site. Outside air may be introduced through the damper option or be used for economized
cooling by using the Economizer option. However, uncontrolled outside air should be kept to a mini-
mum. Outside air adds to the cooling, heating, and filtration loads of the site. Doors should be prop-
erly sealed to minimize leaks and should not contain grilles.
2.1.2 Location Considerations
The InteleCool2 unit is field-mounted on an outside wall. Additional framing in the wall may be
required to ensure adequate structural support.
The outdoor area near the condenser supply and discharge must also be considered. To assure ade-
quate air supply, the unit should be mounted in a clean area, away from loose dirt and foreign matter
that may clog the condenser coil. The unit should not be located near steam, hot air, or fume exhausts.
Also, the unit should not be mounted closer than 12 feet (3.7 m) from an opposing wall, obstruction or
unit. For service clearance, provide 36 inches (914 mm) in front of the unit, and 30 inches (762 mm) on
each side. When mounting units side by side, provide a minimum of 36 inches (914 mm) between adja-
cent units unless the adjacent units will not be run at the same time. In this case, the units may be
placed as close as 18 inches (457 mm) apart. However, this will make the units more difficult to service.
In such situations, consider the compressor location option for improved serviceability. Before mount-
ing units, check local codes for applicable clearances.
2.1.3 Equipment Inspection
Upon delivery of the unit, inspect all items for visible damage. Concealed damage may be discovered
later during installation. Report any damage to the shipper immediately and file a damage claim.
Also, forward a copy of the damage claim to your Liebert supplier.
! WARNING
Use caution and adequate equipment to safely handle unit. Weight of each unit ranges
from 330 to 490 lbs. (150 to 222 kg), depending on model.
6. With the unit front panel removed, lift the unit onto the base angle, making certain that the rear
unit angle falls behind the turned up front edge of the mounting angle. Insert top and side unit
fasteners in holes and tighten, drawing the unit into place. Do not attach ducts to unit prior
to installing unit.
7. Caulk and flash the top and sides as required to form a watertight seal. Top flashing (not factory
supplied) is recommended to ensure that water does not run behind unit. All unit tops are sloped
to allow water to run off.
4
Installation
K
A C
F
K
K G
K B D
H
See Table 1 below for
K
keys to dimensions.
L
M ref.
N
Wf
1.5-2 Ton 38-3/4 20 20 9-3/8 9-13/32 8 20-3/4 12 25-1/16 5-15/32 12 3-25/32 4-1/2 37-7/8 2-15/32
(984) (508) (508) (238) (239) (203) (527) (305) (638) (139) (305) (96) (114) (962) (63)
38-3/4 28 28 5-3/8 5-3/8 8 18 14 26 5-15/32 12 32-5/32 4-1/2 37-7/8 2-15/32
3 Ton
(984) (711) (711) (137) (137) (203) (457) (356) (660) (139) (305) (96) (114) (962) (63)
42-3/4 30-1/4 29-7/8 6-1/4 6-7/16 9-7/8 30 15-7/8 25-25/64 1-45/64 16 6-1/64 6-1/2 41-3/4 4-3/8
4-5 Ton
(1086) (768) (759) (159) (164) (251) (762) (403) (645) (43) (406) (24) (165) (1060) (111)
4 or 5 Ton Unit 42-3/4 28 28 7-3/8 7-3/8 8 18 14 37-1/2 1-45/64 16 15/16 6-1/2 41-3/4 4-3/8
w/3 Ton
(1086) (711) (711) (187) (187) (203) (457) (356) (952) (43) (406) (24) (165) (1060) (111)
Openings
5
Installation
2.4 Ducting
Field-supplied ducting can be attached to the unit duct connection once the unit has been mounted to
the outside wall. The total external static pressure for the duct, including grille, must not exceed the
values shown in Table 5 and Table 6. Indoor discharge air rates are also given in the same tables.
! WARNING
Use voltmeter to make sure power is turned off before making any electrical connections.
! CAUTION
Refer to electrical schematic when making connections.
Each unit is shipped from the factory with all internal wiring completed. Refer to the electrical sche-
matic when making connections. Electrical connections to be made at the installation site are: line
voltage power supply to the power input and control wiring to remote control (customer supplied or
Liebert option). DO NOT RUN CONTROL WIRING WITH HIGH VOLTAGE!
2.5.1 Power Connections
All power and control wiring and ground connections must be in accordance with the National Electri-
cal Code and local codes
Use copper wiring only. Make sure that all connections are tight.
Make sure that the voltage supplied agrees with the voltage specified on the unit nameplate. The
InteleCool2 comes standard with a factory-installed circuit breaker, accessible through an external
access panel. An external, wall-mounted power disconnect switch (field-supplied) may be required for
local codes. If necessary, this switch should be wired according to those codes.
For access to the electrical enclosure:
Remove the screws securing the middle panel and pull the panel down and forward to remove.
Remove the screws securing the electric box cover and remove cover.
Verify that the unit wiring is correct for the actual input power. Some units are built with multi-
voltage serial tags. The transformer may need to be re-tapped if the actual input voltage is differ-
ent (see serial tag and electrical schematic).
Route the supply power to the customer-supplied disconnect switch (if required) and then to the unit
circuit breaker inside the unit. Route the conduit to the hole provided in the cabinet. Connect the
earth ground to the lug provided near the circuit breaker. Refer to the unit wiring diagram supplied
on the inside of the electrical enclosure cover.
! CAUTION
The optional three-phase scroll compressor must rotate in the correct direction to ensure
proper system operation. Wiring must be phased and connected as shown:
PHASE A to T1 or L1
PHASE B to T2 or L2
PHASE C to T3 or L3
6
Installation
Liebert Thermostat
See 2.5.2 - Control Connections for further information, refer to the detailed instructions that ship
with the thermostat.
NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of is
useful life. If this control is replacing a control that contains mercury in a sealed tube, do not
place your old control in the trash. Contact your local waste management authority for
instructions regarding recycling and the proper disposal of this control, or of an old control
containing mercury in a sealed tube.
If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.
! WARNING
The original Dual Unit Control (part # 153054G1, produced through March 2002), is phase
sensitive. The latest version Dual Unit Control (Part # 171170G1) is not. Please refer to
specific installation instructions supplied with each control. Failure to follow specific
instructions may damage the control and/or the unit and void the warranty.
NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of
its useful life. If this control is replacing a control that contains mercury in a sealed tube, do
not place your old control in the trash. Contact your local waste management authority for
instructions regarding recycling and the proper disposal of this control, or of an old control
containing mercury in a sealed tube.
If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.
Tele2
Consult the Tele2 user manual for installation instructions.
7
Installation
Adjustment
Units supplied with Economizer requiring outside air can be adjusted as follows:
1. Run motor to fully closed position and disconnect 24 VAC from terminals TR and TR1.
2. Connect minimum position potentiometer to terminals P and P1. (See Figure 3. T and T1 are
disconnected.)
3. Reconnect 24 VAC to terminals TR and TR1 and adjust potentiometer for desired minimum
position by turning Q709 adjustment screw clockwise to increase minimum position;
counterclockwise to decrease minimum position.
Push onto
actuator
8
Checklist for Complete Installation
! WARNING
Potentially lethal voltages exist within this equipment during operation. Observe all cautions
and warnings in this manual. Failure to do so could result in serious injury or death. Only
qualified service and maintenance personnel should work with this equipment.
9
Start-Up Procedure
NOTE
If the unit is supplied with crankcase heaters, Liebert recommends that the high voltage be
applied between four and six hours before start-up.
10
Operation
5.0 OPERATION
Liquid line
Liquid line
Filter drier
Compressors:
Hermetic Reciprocating (1.5, 2 and 3 ton units)
or Scroll
Optional compressor location available
Condenser
11
Operation
65
60
Temperature (DBF)
Enthalpy Control
55 Operating Range
50
45
40
10 20 30 40 50 60 70 80 90
5.2.2 Actuator
The Economizer actuator is mounted in the lower part of the Economizer section below the electric
box. It is accessible by opening the lower front panel. The actuator is a 24 VAC, spring return device
that will fully close the Economizer damper. The actuator has internal controls that allow it to oper-
ate based on signals from the enthalpy control and mixed air sensor.
12
Operation
Wall-mounted thermostats are to be low voltage, snap action or mercury type. Un-manned sites should
use a HEAT/COOL/AUTO type subbase to provide automatic switchover during climate changes.
5.4.2 High Pressure (Standard)
The high pressure switch is mounted in the liquid line. Electrically, it is connected in series with the
compressor start circuit, which will shut down the compressor and condenser fan if the liquid pres-
sure exceeds 400 PSIG (2758 kPa). This protects the InteleCool2 in the event of condenser motor fail-
ure or condenser coil blockage.
The pressure switch is an auto reset device. When the system pressure drops below 300 PSIG
(2069 kPa), the switch will reset. (An optional lockout relay is available which allows the switch to be
used as a manual reset safety.) If the call for cooling is present, the compressor start circuit will be
energized and the compressor will start after the 3 minute anti-short cycle time.
5.4.3 Refrigeration Control Options
Please review the following table for the recommended control options based on the site ambient and
your need for year-round operation.
Table 3 Recommended applications for control options
Application Unit Options Min ambient Max ambient
General Standard None 50F (10C) 115F (46.1C)
Low pressure with low pressure bypass
General Standard 50F (10C) 115F (46.1C)
timer
General Standard T-pack1 or T-pack2 -20F (-28.9C) 115F (46.1C)
Telecom/365-day operation Standard T-pack1 or T-pack2 -20F (-28.9C) 115F (46.1C)
General Standard High ambient 50F (10C) 125F (51.7C)
High ambient, low pressure with low
General Standard 50F (10C) 125F (51.7C)
pressure bypass timer
Telecom/365-day operation Standard High ambient with T-pack1 or T-pack2 -20F (-28.9C) 125F (51.7C)
Low Pressure Switch and Low Pressure Bypass Timer (Winter Start)
Low Pressure SwitchThe low pressure switch is mounted in the compressor suction line. Electri-
cally, it is connected in series with the compressor start circuit, which will shut down the compressor
and condenser fan if the suction pressure drops below 35 PSIG (241 kPa). The switch will automati-
cally reset once the system pressure rises above its cut-in setting (60 psig, 5 psig [414 kPa, 34 kPa]).
This protects the InteleCool2 in the event the evaporator fan fails, the filter becomes clogged or there
is a loss of refrigerant. If the call for cooling is present, the compressor will start after the 3 minute
anti-short cycle time.
Low Pressure Bypass TimerA low ambient temperature start relay is included with the low
pressure option. This relay locks out (ignores) the low pressure switch on start-up until the system
pressure stabilizes. This bypass relay is adjustable and should be set for 3 minutes greater than the
anti-short cycle timer setting. This option can be used for applications down to 50F (10C). For con-
trol down to -20F (-28.9C), use the T-pack1 and T-pack2 options, which include fan cycle control.
13
Operation
T-pack1 package
Includes a low pressure switch, low pressure bypass timer (described above) and fan cycle control.
Fan Cycle ControlCondenser Fan Cycling Control; allows the InteleCool2 unit to provide cooling
to the space when the outdoor ambient temperature is lower than 50F (10C) and down to -20F
(-28.9C). The control uses a reverse acting pressure switch mounted on the discharge line that cycles
the condenser fan in response to the discharge pressure. On a call for cooling, when the discharge
pressure increases to 250 PSIG (1723 kPa), the switch will close and start the condenser fan. When
the pressure drips below 170 PSIG (1172 kPa) the switch will open and stop the condenser fan. Dur-
ing low outdoor temperatures, the pressure switch cycles the condenser fan to maintain discharge
pressure that will allow the system to function.
NOTE
During normal operation in low ambient conditions, the condenser fan will cycle frequently.
T-pack2 package
Includes a low pressure switch, low pressure bypass timer and an adjustable fan cycle control. See
descriptions above.
14
Maintenance
6.0 MAINTENANCE
! WARNING
Potentially lethal voltages exist within this equipment during operation. Observe all cautions
and warnings in this manual. Failure to do so could result in serious injury or death. Only
qualified service and maintenance personnel should work with this equipment.
6.1 Filters
Replaceable evaporator air filter(s) are supplied with the unit. The filter(s) are easily serviceable from
the outside, through the top front access panel.
Filters are usually the most neglected item in an environmental control system. To maintain efficient
operation, they should be checked monthly and changed as required. Units supplied with Economiz-
ers may require replacement filters more frequently because of airborne dust and organic materials.
Filters can be replaced from the front by opening the lower front access panel.
! WARNING
Power must be OFF while replacing the filter.
! WARNING
POWER MUST BE OFF WHILE INSPECTING THE BLOWER EQUIPMENT.
6.4 Heat
Heaters can be serviced and/or removed from inside through the discharge opening or from outside by
removing the top.
! WARNING
Power must be OFF while working on heaters.
15
Maintenance
NOTE
Make no more than 1/4 turn of the stem at a time. As long as 30 minutes may be required
for the new balance to take place.
To determine superheat:
1. Measure the temperature of the suction line at the point where the TEV bulb is clamped.
2. Obtain the gauge pressure at the compressor suction valve.
3. Add the estimated pressure drop between bulb location and the suction valve.
4. Convert the sum of the two pressures to the saturated temperature.
5. Subtract this temperature from the actual suction line temperature. The difference is superheat.
6.6 Compressor
Infrequently, a fault in the motor insulation may result in a motor burn. However, in a properly
installed system, burnouts rarely occur. Of those that do, most are the result of mechanical or lubrica-
tion failures, resulting in the burnout as a secondary consequence.
If the problems that can cause compressor failures are detected and corrected early, a large percent-
age can be prevented. Periodic maintenance inspections by alert service personnel on the lookout for
abnormal operation can be a major factor in reducing maintenance costs. It is easier and far less
costly to take the steps necessary to ensure proper system operation than it is to allow a compressor
to fail and require replacement.
When troubleshooting a compressor, check all electrical components for proper operation, including
all fuses and circuit breakers and pressure switch operation.
If a compressor failure has occurred, determine whether it is an electrical or mechanical failure.
Mechanical Failure
A mechanical compressor failure will not be indicated by a burned odor. The motor will attempt to
run. If you have determined that a mechanical failure has occurred, the compressor must be replaced.
16
Maintenance
Electrical Failure
An electrical failure will be indicated by a distinct pungent odor. If a severe burnout has occurred, the
oil will be black and acidic. If a burnout does occur, correct the problem that caused the burnout and
clean the system thoroughly using the proper procedure. It is important to note that successive burn-
outs of the same system are usually caused by improper cleaning.
! CAUTION
Damage to a replacement compressor caused by improper system cleaning constitutes
abuse under the terms of the warranty, and the WARRANTY WILL BE VOIDED.
There are two kits that can be used with a complete compressor burnout: Sporlan System Cleaner and
Alco Dri-Kleener. Whichever kit is used, follow the manufacturers procedure.
! CAUTION
Avoid skin contact with the refrigerant and oils. Severe burns will result.
Use long rubber gloves when handling contaminated parts.
! CAUTION
Do not loosen any refrigeration or electrical connections before relieving system pressure from
both sides of the compressor.
NOTE
Release of refrigerant to the atmosphere is harmful to the environment and is unlawful.
Refrigerant must be recycled or discarded in accordance with federal, state, and local
regulations.
! CAUTION
The optional three-phase scroll compressor must rotate in the correct direction to ensure
proper system operation. Wiring must be phased and connected as shown:
PHASE A to T1 or Ll
PHASE B to T2 or L2
PHASE C to T3 or L3
17
Maintenance
9. Connect a vacuum pump to both the high and low sides of the system through properly sized
connections. Evacuate the system twice to 1500 microns, and the third time to 500 microns. Break
the vacuum each time with dry nitrogen to 2 PSIG (13.8 kPa).
10. Charge the system with refrigerant. Refer to unit serial tag for refrigerant charge amount.
11. Apply power and operate system. Check for proper operation. Suction and discharge pressures
will vary with load conditions and coil efficiency. The low pressure switch will shut the
compressor down if the suction pressure falls below the cutout setting. Conversely, the high
pressure switch will shut down the compressor if the discharge pressure exceeds the cutout
setting. High suction pressure reduces the ability of the refrigerant to cool compressor
components and can result in compressor damage. Refer to Table 4.
NOTE
High side gauge port is a liquid line connection. Proper procedures should be followed
when installing and removing gauges. A 6-foot (1.8 m) hose can hold up to 3 oz (0.1 l) of
refrigerant. Be sure to purge high side to low prior to removal.
18
Specifications
7.0 SPECIFICATIONS
7.1 Dimensional Data
Figure 6 Dimensional data
Ws
2-1/4"
(58mm)
J
Entrance for high
volt connections
4"
(102mm)
Wu
A
E supply
F
K C 1-11/16"
(43mm)
G Entrance
for low volt
connections
B
return
H
L
Shaded areas indicate a recommended clearance
of 34" (864mm) in front and 30" (762mm) each side,
or 36" (914mm) when mounted adjacent to another
unit, for component access. For recommended
minimum clearances, refer to 2.1.2 - Location Con- Wf
siderations.
D
2-1/4"
(58mm)
See Table 5 below for dimensions.
19
Specifications
20
Specifications
21
Specifications
22
Specifications
23
Specifications
24
Specifications
25
Specifications
26
Troubleshooting
8.0 TROUBLESHOOTING
Table 14 Troubleshooting guide
Problem Probable Cause Remedy
Unit will not start No power to unit Check voltage to input circuit breaker.
Control voltage circuit Locate short and reset breaker.
breaker open
Shut off by external Check operation of thermostat.
thermostat or stat is
defective
No cooling Low refrigerant Check with gauges.
charge
Compressor contactor Check voltage at contactor. If not present refer to print and determine
not pulling in voltage loss. Check enthalpy sensor for full CCW or D setting.
No output from Check operation of stat. Should have voltage output to Y terminal during
thermostat cooling.
Unit cycles on Loss or restriction of Check condenser blower assembly for proper operation. Check for dirty
high pressure switch air flow coil or inlet grille restriction.
Defective fan cycling Switch should make @ 240 PSIG 10 (1655 kPa 68.9). (Check settings
control on adjustable switch when supplied.)
Heat does not operate No voltage output Check stat for proper output to W terminal.
from thermostat
Fuseable link blown Check for open and replace.
Bad contactor Check for open and replace.
27
Maintenance Inspection Checklist
Monthly
Filters
___ 1. Unrestricted air flow
___ 2. Check filter
___ 3. Wipe section clean
Fan Section
___ 1. Impellers free of debris
___ 2. Bearings free
Economizer
___ 1. Check damper for tightness and wear
Semiannually
Compressor Section
___ 1. Check for leaks
___ 2. Vibration isolation
Refrigeration Cycle
___ 1. Check suction pressure
___ 2. Check head pressure
___ 3. Check superheat
___ 4. Evaporator coil clean
___ 5. Insulation intact
Electric Panel
___ 1. Check electrical connections
___ 2. Check operational sequences
Notes:
Signature _________________________________________________________
Make photocopies of this form for your records
28
Parts
10.0 PARTS
Table 15 Refrigeration system parts, 1.5 and 2 ton units
1.5 Ton 2 Ton
ET017S ET018P ET023S ET023M ET024P ET024Y ET024A
Figure Part Name/ 220-240V 208-230V 220-240V 380-415V 208-230V 208-230V 460V
No. Description Part # 1 Ph 50 Hz 1 Ph 60 Hz 1 Ph 50 Hz 3 Ph 50 Hz 1 Ph 60 Hz 3 Ph 60 Hz 3 Ph 60 Hz
Run capacitor, recip comp
7-7 Cap. 25F, 370V C03-005A 1 1 N/A N/A N/A
7-7 Cap. 30F, 370V 1A19537P1 1 N/A 1 N/A N/A
Run capacitor, scroll comp
7-7 Cap. 30F, 370V 1A19537P1 1 N/A N/A N/A
7-7 Cap. 40F, 370V 1A19538P1 1 1 N/A 1 N/A N/A
Compressors, reciprocating
7-5 Comp. 220/240-1 146301P1 1
7-5 Comp. 208/230-1-60 146300P1 1
7-5 Comp. 208/230-1-60 146303P2 1
7-5 Comp. 380/460-3 159147P2 1 1
7-5 Comp. 208/230-1 146303P1 1
7-5 Comp. 200/240-3 159147P1 1
Compressors, scroll
7-6 Comp. 220/240-1 156204P1 1
7-6 Comp. 200/230-1 159146P1 1
7-6 Comp. 220/240-1 138493P2 1
7-6 Comp. 380/460-3 148324P2 1
7-6 Comp. 200/230-1 159145P1 1
7-6 Comp. 208/230-3 159148P1 1
7-6 Comp. 380/460-3 159148P2 1
Pressure switches
High pressure - 400 psi 159482P1 1 1 1 1 1 1 1
Fan cycle switch - 170 psi 159483P1 Optional feature - quantity 1 (as required)
Low pressure - 35 psi 159484P1 Optional feature - quantity 1 (as required)
Adj Pr Sw for Adj FCC P67-0110 Optional feature - quantity 1 (as required)
Filter drier 127185P1 1 1 1 1 1 1 1
7-10 Condenser coil-1.5/3T 159118P1 1 1 1 1 1 1 1
10-1 Evaporator coil-1.5/2T 159200P1 1 1 1 1 1 1 1
10-1 Thermal expansion valve-1.5T 1C19507P3 1 1
10-1 Thermal expansion valve-2T 1C19507P1 1 1 1 1 1
Crankcase heaters
7-9 Strap style 240V recips 159202P1 1 1 1 1 1
7-9 Strap style 480V recips 159202P2 1 1
8-1 Well style (recips. only) 1A17648P1 1 1 1 1 1 1 1
8-2 Retainer plug 159136P1 1 1 1 1 1 1 1
15-1 Soft start kit 1C19540P1 Optional feature - quantity 1 (as required)
29
Parts
30
Parts
31
Parts
32
Parts
33
Parts
34
Parts
35
Parts
36
Parts
37
Parts
38
Parts
39
Parts
40
Parts
10
3
7
2
4
8 1
9
6
5
Compressor
2 1
Crankcase
heater
cartridge
Retainer
41
Parts
12
4 7 11
2 5 6 8 9 10 1
TEV systems
42
Parts
Evaporator MF
10 1
11
13
8
31 12
3 6 200/240V, 3 phase
4
10 1
11
13
8
31 12
3 6 1A 200/240V, 1 phase
15 9 4
1
10
43
Parts
159171G1 & G2, 159171G3 & G15 159171G4, G5 &G6 159171G7, G8, G10, G11& G12
G13 & G14 G16, G17 & G18 G19, G20, G21, G22, G23& G24
44
Parts
5
6
1 2
3
4
1
45
Parts
To compressor
capacitor
1
46
Parts
Notes
47
Parts
48
Ensuring The High Availability
0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical Technical Support / Service
continuity, ensures network resiliency and adaptability through Web Site
a family of technologiesincluding Liebert power and cooling www.liebert.com
technologiesthat protect and support business-critical systems. Monitoring
800-222-5877
Liebert solutions employ an adaptive architecture that responds
[email protected]
to changes in criticality, density and capacity. Enterprises benefit Outside the US: 614-841-6755
from greater IT system availability, operational flexibility and Single-Phase UPS
reduced capital equipment and operating costs. 800-222-5877
[email protected]
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
[email protected]
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
Fax: +39 049 5841 257
responsibility and disclaims all liability for damages resulting from use of Asia
this information or for any errors or omissions. 7/F, Dah Sing Financial Centre
2006 Liebert Corporation 108 Gloucester Road, Wanchai
All rights reserved throughout the world. Specifications subject to change
without notice. Hong Kong
Liebert and the Liebert logo are registered trademarks of Liebert 852 2572220
Corporation. All names referred to are trademarks Fax: 852 28029250
or registered trademarks of their respective owners.
SL-19530_REV1_08-06
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
2006 Emerson Electric Co.