Safe Switchgear Specifications Paper PDF
Safe Switchgear Specifications Paper PDF
Abstract
The majority of specifications produced today for circuit breakers are often inadequate
for the application intended. Either too little information is provided (in comparison to
other building services disciplines) or the text has been recycled for a large number of
years.
Over the past few decades the low voltage installation has become increasingly more
challenging for Moulded Case Circuit Breakers (MCCBs)
Increased fault levels, higher harmonics levels, changing legislation and demand for
maximum uptime have substantially altered the requirements of this important protective
device.
The objective of this paper is to update the professional electrical engineer on the safe
application of low voltage MCCB technology.
In doing so we will examine thoroughly protection disciplines, isolation principles and
future trends for MCCBs
Index
1.0 Introduction
5.0 Protection
9.0 Conclusion
The area in between is normally where an MCCB would be located within the
distribution network. The protective device in this area could also be a fuse switch
but the comparison of pro and cons of fuses versus MCCB (albeit an interesting debate)
is not within the scope of this paper.
The key words here to note are switch, make, carry and break.
An MCCB is there to protect both plant and personnel from serious damage resulting
from an overcurrent .It must also provide isolation facilities to ensure maintenance can be
carried out safely and in line with current legislation.
Most manufacturers offer MCCBs with ratings anywhere from 12A to 2500A (but it is
possible for the frame size to be even higher and lower than this.) The minimum frame
rating is typically 125A and 90% of the UK volume of MCCBs is up to 800A or 1000A.
Although MCCBs are available at ratings higher than this, the majority of specifiers use
ACBs at these levels and above to ensure higher selectivity and maintainability.
The MCCB is so called as this housing of the contacts structure are contained within a
moulded base and finished with a moulded lid.
The main elements of a MCCB are the contacts, arc chamber, tripping unit ,trip
mechanism and toggle.
Arc chamber
Toggle Contacts
Tripping mechanism
Tripping unit
Contacts
Fixed and opening contacts ensure rapid opening under overcurrent condition. The
contacts are made from copper but with silver tungsten tips to increase conductivity and
electrical endurance
Arc chamber
The arc chamber consists of many splitter plates which help extinguish the low voltage
arc. The magnetic field of the overcurrent helps direct the arc away quickly from the
contact tips and into the arc chamber where overall surface length and impedance is
increased to help extinguish the arc and clear the overcurrent.
Tripping Unit
The tripping unit can either be thermal magnetic or microprocessor type. This instructs
the trip mechanism on how quickly it should take to operate and is usually has adjustable
in settings.
The above publications contain the minimum standards for safety, which all MCCB
manufacturers must meet. As an MCCB is an important safety device it is good practice
to design the MCCB beyond the standard where possible. Other standards that are
sometimes referred in MCCB specifications are:
BS EN 60204-1
Safety of machinery. Electrical equipment of machines. General requirements.
BS:7671
Requirements for Electrical Installation (IEE Wiring Regulations 17th Edition).
These standards will be referred to later in this paper.
The main MCCB ratings and specification items detailed in the IEC 947 series of
standards are shown below:
All of the above are important in determining the MCCB specification. However, as a
minimum ,the specifications should at least , refer to those associated with the main
definition of an MCCB.
That is to carry current (In),to break current (Icu) and to make current(Icm) at a specified
voltage level (Ue). We shall now look at each on in turn.
This temperature difference can influence the derating of an MCCB when installed in a
switchboard. This is important as all circuit breakers are rated in free air to establish a
common reference point. Once in an enclosure the derating characteristics can influence
the current carrying capacity.
In hotter climates such as the Middle and Far East it is common for specifications to ask
for all MCCBs to be rated at 500C, to ensure their performance is adequate for the
environment intended.
Fault levels are increasing all the time and the supply of large transformers up to
4MVA(100 kA at 415v), have dramatically increased due to the huge power and cooling
requirements, of power hungry installations such as data centres.
With high current limiting MCCBs it is possible to achieve fault levels up to 200kA at
415V (a fuse is usually limited to 80 kA).However this tends to be used only in marine
installations where several generators are operating in parallel at the same time.
This Icu is also referred to as the ultimate breaking capacity and is evaluated by
performing a breaking test at the maximum three phase fault level, then re-closing back
onto the same fault magnitude and breaking a second time.
This is also referred to as O-CO test( open, close open)
This test replicates two full 3 phase bolted short circuits at the MCCB terminals which
in practice only really occurs during a test condition. The vast majority of faults tend to
be towards the load end and the conductor impedance would substantially reduce the
fault level .Its also more likely to be a single phase rather than a three phase thereby
reducing the fault further.
After the Icu breaking test the MCCB musts still be able to carry load current, pass a
dielectric test and operate within tripping tolerance bands. This value is used within 90%
of UK electrical installations to determines the breaking capacity of an MCCB.
A more onerous rating is the Ics breaking capacity value also referred to as the service
breaking capacity. This is a three short circuit rating represented as O-CO-CO.
Ics is usually applied more to incoming circuit breakers such as ACBs where the
proximity of the circuit breaker is close to the supply source. However, it is also applied
to MCCBs in higher risk applications such as oil/gas installations and offshore.
Some specifications call unnecessarily for the Ics value to be 100% of the Icu. If an Ics
rating is required then this should be based on the system fault level.
Most manufacturers can offer both Icu and Ics ratings but the Ics rating can sometimes be
at higher cost, depending on the rating.
i. Category A
This is for MCCBs with no intentional time delay and are therefore not specifically
intended for high selectivity applications, which tend to be a thermal magnetic MCCB.
These MCCBs would not have a Icw rating.
ii. Category B
These MCCBs have a time delay which makes them more suited to applications that
demand higher selectivity .The majority (but not all) of microprocessor MCCBs have a
short time withstand Icw rating.
For example a 1250A MCCB may have an Icw of 15ka rms for 300msec
However the chances are much increased for an operator being present during a making
operation(unless remotely controlled ) as they must physically be holding the MCCB
toggle or operating handle to close the MCCB after say a routine maintenance schedule.
If an operator attempted to close an MCCB onto a short circuit and the making capacity
was inadequate, then serious and perhaps fatal consequences could be the result.
The standard BS EN 60947-2 sets out to provide minimum levels of safety. Within the
standard there is table which provides guidelines for ratios of breaking capacities to
making capacities which is shown as the multiplication factor n in the table below.
Short circuit ( I ), kA r.m.s Power Factor n
(cos )
As shown in the above table the factor n is proportional to the short circuit power
factor(not to be confused with load power factor).The lower the short circuit power
factor(sometimes also shown as reactance to resistance ratio X/R) the higher the DC
offset component and the higher the asymmetrical peak value.
Similar to the temperature rise issues the American and Japanese standard authorities
demand more onerous electrical parameters in relation to short circuit power factors for a
given fault level.
The value of an MCCB making capacity is more important today than in previous years
as backup generation facilities on mission critical facilities like data centres,
telecommunication and hospitals is increased to maximise uptime of the installation.
This is important as the supply characteristics (X/R) of a transformer fed installation are
quite different to a generator or rotary UPS supply source .This can result in very larger
peak asymmetrical short circuit (Iasym) currents, to which the MCCB must be able to
safely make onto,
A common example could be three parallel generators rated at 1.6MVA/415V, which has
a combined fault current output of 80 kA sym rms but a peak asymmetrical output of 204
kA.
This represents an n ratio of 2.55 which is well above what the BS standard for MCCBs
refers to.
If a standard 80 kA sym rms MCCB was to be installed it would probably only have a
making capacity of 176 kA asym peak. (The standard specifies an n of 2.2 as a factor
for 80 kA).
If this MCCB attempted to close onto the combined fault output of the generators it
would be disastrous for the installation.
In this example all MCCBs would have to be selected primarily on their making capacity
to ensure that the MCCB was capable of closing onto the potential value of a short circuit
Provided the building design software, accommodates short circuit studies fed from
sources such as generators/DRUPS ,then this would be highlighted and the MCCB
selection would need to be driven by making capacity first and breaking capacity second.
The actual voltage the MCCB is tested at is the recovery voltage which is the voltage
present immediately following a short circuit. This is expressed as a percentage of the
operational voltage. In the MCCB BS standard this is at 105%.
In the above example the voltage used in the actual test would be 435V (=415 x 1.05)
Again in the American and Japanese standards the recovery voltage is set at 110% so an
MCCB influenced by these standard would be tested at 456V (=415 x 1.10)
On the subject of overload protection there is also a Regulation in BS7671 that states
Every circuit shall be designed so that a small overload of a long duration is unlikely to
occur
This thermal part of the time current characteristic is shown with current magnitude
being inversely proportional to the operating time.
A typical interrupting time is 20seconds for an overload magnitude of 600% ( In) (as
shown by the inverse part of the curve in figure 7).
t
Thermal (Ir
(Ir))
0.63 125A
20sec 8 10
0.8
1 6 12
Magnetic(Im)
Magnetic(Im) Ir (x ln) Im (x ln)
I
600%In
The short circuit part is carried out by the magnetic operation. In this type of MCCB the
short circuit would create a strong magnetic force that would engage a moving magnetic
core to operate the trip bar very quickly. For low short circuits the total clearing
time(opening and arcing time) could be approximately 20msec.However most modern
MCCBs all exhibit current limiting properties. This utilises the magnetic force of the
short circuit to rapidly assist the opening of the contacts. In other words the higher the
short circuit the quicker the opening time. The typical clearing time of an MCCB
interrupting at its maximum fault current, could be anywhere from 2 to 5 msec.
This part of the curve is shown by the definite/instantaneous characteristics in the figure
above
Example
A 125A (frame size) MCCB fitted with a 63A(In) trip unit can have its rated current(Ir)
set anywhere from 63A(100%In ) to 40A(63%In).
This flexibility allows for last minute changes during commissioning where MCCB
ratings may have changed due to the alteration of the cable schedule.
Adjustable short circuit protection can sometimes be even more important to ensure
optimum performance. When switching inductive (motors) or capacitive (power factor
correction) loads, it is important to ensure the magnetic trip value(at minimum tolerance)
is above the inrush current that these loads could draw. Failure to do this could result in
the nuisance tripping of the MCCB during switch on. See figure 8 for more details.
t 125A
Adjustable 8 10
magnetic
range
6 12
Im (x ln)
Motor 6 12 Phase to
starting I
earth fault
Alternatively you may have an installation with a long cable run where the small short
circuit level at the end of the cable could result in non compliance with tripping times of
the wiring regulations BS7671.
The regulations (411.4.5) relating to earth loop impedance (Ze) require the protective
device to operate within 5 seconds for fixed equipment. If Ze is too high the MCCB may
take too long to operate for a low short circuit such as an earth fault.
The designer can get round this by increasing the cable size of the circuit protective
conductor (CPC) but this would incur extra cost to the client.
If the specification ensures MCCBs with adjustable magnetic/short circuit trips are used
then by simply decreasing the instantaneous trip setting then compliance with the
regulations can be achieved without over-sizing the cable,
There are many electrical engineers, who believe they have to use microprocessor based
MCCBs to have adjustable overload and short circuit settings. This is incorrect.
While microprocessor based MCCBs offer a wider range of adjustments and options
there is a cost penalty attached to this.
A practical compromise would be for the specification, to advocate the use of thermal
magnetic MCCBs up to 400A and use microprocessor based MCCBs above this.
The increase in harmonics (see section 6.0) highlighted problems with these types of
MCCBs as the vast majority were modelled on peak detection circuitry.
Analogue electronic MCCBs would look only at peak value of the waveform and
basically divide this by square root of two, to determine the rms value.
This could often lead to under or over protection of the conductor.
The transition to digital electronics with microprocessor based circuitry helped overcome
most of these issues.
Microprocessor MCCBs tend to have a much wider adjustment than its thermal magnetic
counterpart with a typical range being 40 to 100% of (In).
In addition several parts of the time current characteristics can be adjusted independently
of each other depending on the type of MCCB.
Most microprocessor MCCBs have at least three parts to the time current characteristic
curve. These are sometimes referred to as LSI curves.
5s
0.05s
Instantaneous trip 2 12
Short circuit protection
Electrical designs carried out today, take this into account when calculating transformer
and conductor sizes. There are many techniques that can be adopted to reduce the
harmonic level as much as possible. These range from active filters to isolating
transformers. The difficult problem is trying to predict the client harmonic load profile
five, ten and twenty years from now.
The important criteria for an MCCB is to always respond to the true root mean square
(rms) value of the load current as this is what contributes towards the heating effect of the
conductor.
Thermal Magnetic MCCBs are excellent for this as the basic bimetallic strip(responsible
for overload protection) will always respond to the true rms value of the load current. The
heat produced is directly positional to I2R so a thermal magnetic MCCB will read the true
rms value up to the infinite harmonic.
As mentioned earlier, basic electronic MCCBs responded to the peak value of the
waveform which resulted in the term nuisance tripping being associated with some
MCCBs. The more modern microprocessor based MCCB utilizes different techniques to
read to the true rms value of the load current.
One technique is to use a sampling and integrating technique. A sampling interval of
0.5msec would enable an MCCB to read up to an including the 19th harmonic based on
Shannons sampling theorem.
(i)
Time (sec)
t = 500sec
Whilst this will capture a large majority of harmonics it could still under or over protect
the conductor if higher harmonic levels were present. Important triple N harmonics(those
that are odd and divisible by 3) such as the 9th and 15th harmonic could be missed.
Percentage of
fundamental
1 3 5 7 9 11 13 Harmonic
component
The problem with triple N harmonics is that due to the phase angle they arithmetically
combine in the neutral conductor. For example L1, L2 and L3 may have say 15% 3rd
harmonic current in each phase but these would combine in the neutral conductor.
This means that traditionally balanced 3phase system with minimal neutral current
flowing has now changed where the neutral conductor can now carry as much current as
the phases. This requires the designer to consider overload protection for the neutral
conductor.
This phenomena has now been recognised in the new 17th Edition of IEE wiring
regulations (BS7671) which contains a new appendix 11(Effects of Harmonics) to help
provide guidelines for the system designer.
It draws attention to the Triple N harmonics and suggests neutral pole protection should
be considered where high harmonic distortion can exist.
For an MCCB to be suitable as an isolating device and be labelled as such it must meet
the requirements for a disconnecter as described by BS EN 60 947-3.
This consists of three basic tests:
Once these tests have been complete it can be labelled with isolator symbol (Figure 12)
The latter provides a best practice guide called Guidance on safe isolation procedures
for low voltage installations which is also applicable to MCCBs
This guide emphasises that isolation should be made on the main incoming MCCB or
switch disconnecter on the switchboard or distribution board. The point of isolation
should use a recognised lock system, with the main key or combination held by the
person carrying out the work. In the case of multiple operators working on one device or
circuit a multi lock hasp should be used. The device should only be used in combination
with an adaptor approved by the manufacturer of the isolating device.
With regards to isolation of individual circuits on distribution boards this best practice
guide states the following:
Some distribution boards are manufactured with Slider switches to disconnect the
circuit from the live side of the circuit breaker. These devices should not be used as a
means of isolation for circuits, as they do not meet the requirements for isolation and the
wrong switch could easily be operated on completion of the work
The practice of placing insulating tape over a circuit breaker to
prevent inadvertent switch on is not a safe means of isolation
Do use MCCB or
isolator
The new 17th edition of the IEE wiring regulation for the first time makes reference to
BS EN 60204-1 (Safety of machinery. Electrical equipment of machines. General
requirements)
Regulation 537.4.1 states that where equipment is within the scope of BS EN 60204 the
requirements for emergency switching of that standard applies
This standard gives guideline on Measures to minimise risk in the event of failure and
Recommendation for the use of switches having direct opening action.
It suggests it is good practice to have a direct mechanical link from the toggle to the main
contacts. Some operating springs can become weak or even fail .In this case they should
not be relied upon for manual opening in an emergency switching condition. Figure 14
below shows a cross section of the MCCB with direct opening action.
Several MCCB manufactures have now incorporated these guidelines for direct opening
action into the main mechanism of the MCCB, to provide an enhanced safety function
which is beyond the traditional requirements of isolation.
8.0 Present and Future trends
The MCCB continues to evolve in pace with other emerging technologies. Todays
modern MCCBs are smaller and lighter than previous generations. However the demands
for increased fault levels, temperature performances, enhanced safety and reliability
continues to drive the developments of this important protective device.
It is a fact that the majority of electrical fires are due to an undetected earth leakage
condition around the magnitude of 300 mA or greater.( Regulation 532 refers to
Limit consequence of fault current from point of view of fire risk)
The traditional method to achieve earth leakage protection on an MCCB would be use a
separate earth leakage relay (ELR) and current transformer (CT).Another method was to
add an earth leakage block (ELB) to the load side of the MCCB.
Both these systems require additional panel space and the ELB can sometimes affect the
MCCB temperature performance and cannot be a retrofitted solution.
Several manufacturers can now offer MCCBs with integral earth leakage protection in the
same footprint as the MCCB. These are also referred to as Circuit Breakers with Residual
protection (CBR).
It is also possible to have an earth leakage alarm facility which can be set to give an
early warning of a potentially dangerous situation rather than a trip function.
Many end users are showing a preference for the alarm facility rather than have a critical
load trip for an earth leakage condition.
The integral LCD monitor can display all the electrical parameters that you would expect
to be available on a traditional panel with multi-meters. These include phase currents
(including neutral and ground) and voltage, power, energy, maximum demand, harmonic
analysis etc. An example of such an MCCB is shown in figure 16.
i Fault Diagnosis
This can show type of fault that has occurred (overload, short circuit or earth fault) and
the magnitude and tripping time of the MCCB. This can help achieve faster fault
diagnosis and contribute towards reducing downtime. Fault data can be stored and can be
compared to previous trips. Similar to a multi-meter all available information can be
transmitted to the Energy Management System (EMS) where further analysis of trends
and log history can be viewed.
The modern microprocessor MCCBs can provide more information after a fault event.
However many end users would of course prefer to know about an issue in advance that
may cause downtime within their facility.
In section 8.1 one technique that can be used on the lower rated thermal magnetic
MCCBs is earth leakage monitoring.
From an overload protection point of view one of the drawbacks with a microprocessor
MCCBs is that they respond to current and not heat.
Some of the most common problems associated with MCCBs tend to be associated with
temperature. If an over temperature issues is not detected and corrected this could
potentially be a future fire hazard over a long period of time.
Common over temperature problems include
i. Loose connections
The terminal bolts that connect the conductor to the MCCB need to be at a
certain torque to achieve good conductivity. If these are not tightened
correctly or become loose due to vibration from a machine (ie. generator) this
could result in their terminal temperature exceeding its design parameters
Figure 17.A 1250A circuit breaker fire damaged from an over- temperature situation
As a microprocessor MCCB responds to current and not heat, all of the above conditions
would not seen by the MCCB as a possible problem. In some severe cases the MCCB
may be less than 50% loaded but any one of the above conditions (particularly item 1 or
3) could result in a dangerous terminal temperature.
Figure 17 is a real life example of such an incident. The loose terminal connection in the
top middle phase resulted in an increased temperature which over a period of time
exceeded the limitations of the moulded material. The result was a fire within the
switchboard which resulted in 6 weeks lost production time due to this major incident.
An advantage of a thermal magnetic MCCB is that it would self protect in all of the
above conditions due to the nature of detecting overloads.
Thermal imaging is a very useful technique which can greatly assist in detection of hot
spots. However this is a one time event and does not provide 24/7 coverage.
9.0 Conclusion
The MCCB is much more than a basic switch within the low voltage distribution network.
It is an important safety device whose main purpose is to protect the conductors within
the installation.
As such it demands more than a paragraph in the electrical specification document to
ensure it can adequately support the application for which it is intended.
A detailed knowledge of the circuit breaker standards it not too important so long as the
specifying engineers has an understanding of the basic requirements of the MCCB.
That is to carry (In), break (Icu) and make current (Icm) safely.
The standards are there to determine minimum levels of safety for the MCCB. The
specifying engineer needs to decide if the nature of the installation requires higher
margins of safety. This could be relevant to breaking/making capacities or
temperature/harmonic requirements within the system.
The recently published 17th edition of IEE wiring regulations also provides additional
guidance on the topics of overcurrent protection, isolation and harmonics.
Ensuring that the MCCB has a basic adjustment of overload and short circuit protection
will enable the protective device to be more flexible.
This does not mean that we always need to use microprocessor MCCBs as the basic
thermal magnetic MCCB still has a number of advantages such as cost, temperature
response, harmonic measurement and DC application.
Developments of MCCBs will continue to add value to the protection of the low voltage
network. Recent trends in earth leakage protection, measurement facilities and condition
based maintenance options will provide design engineers new options to enhance their
clients system to maximise uptime.
In closing, it is important that state that where detailed MCCB specifications exist, it is
important to make sure that they are up to date with current legislation and are truly
generic in nature. Several of the leading MCCB manufacturers can offer appraisals on
circuit breaker specification documents to ensure full compliance and openness.
10. References and Acknowledgement
2. BS EN 60204-1
Safety of machinery. Electrical equipment of machines. General requirements
3. BS:7671 2008
Requirements for Electrical Installation (IEE Wiring Regulations 17th Edition)