Free Cooling Guide
Free Cooling Guide
C O O L I N G I N T E G R AT I O N I N LO W -
ENERGY HOUSES
01 | 2013
Table of contents
1. Introduction to the concept of free cooling ...3 6. Free cooling in combination with
The need for cooling in low-energy houses.............4 different heat sources ....................................19
Comfort and energy efciency the best t
7. Choosing and dimensioning the radiant
for low-energy houses ............................................4
emitter system ................................................20
Investing for the future the design of a
Capacity of different radiant emitter systems ........20
low-energy house ...................................................5
Radiant oor constructions and capacity ..............22
2. Cooling loads in residential buildings .............6 Radiant ceiling constructions and capacity ...........24
Factors inuencing the sensible cooling load ..........6 Capacity diagrams .................................................24
Factors inuencing the latent cooling load .............7 Regulation and control..........................................26
The effect of shading ..............................................7 The self-regulating effect in underoor heating ..27
Room variation .......................................................8 Functional description of Uponor Control
Duration of the cooling load ..................................8 System .................................................................27
Required cooling capacity .......................................9 Component overview ............................................29
3. The ISO 7730 guidelines .................................10 8. Uponor Pump and exchanger group (EPG6)
Optimal temperature conditions............................10 for ground sourced free cooling.....................29
Draught rate .........................................................11 Dimensions ...........................................................30
Radiant asymmetry ...............................................11 Pump diagram.......................................................30
Surface temperatures ............................................12 Control principle ...................................................31
Vertical air temperature difference ........................12 Installation examples.............................................33
Operation of Uponor Climate Controller C-46 .......36
4. Capacity and limitations of radiant
Operation mode of Uponor Climate
emitter systems ..............................................13
Controller C-46 .....................................................36
Heat ux density...................................................13
Dew point management parameters and
Thermal transfer coefcient ..................................13
settings .................................................................37
Dew point limitations ............................................13
Heating and cooling change-over:
Theoretical capacities of embedded
external signal .......................................................38
radiant cooling ......................................................14
Heating and cooling change-over:
5. Ground heat exchangers .................................15 Uponor Climate Controller C-46 ............................38
Ground conditions ................................................15
Ground heat exchangers .......................................16
Ground temperature prole...................................17
Primary supply temperatures.................................17
Dimensioning of ground heat exchangers
for free cooling .....................................................17
Free cooling is a term generally used when low external lower compared to the outside air. The radiant system
temperatures are used for cooling purposes in buildings. operates with large surfaces, which means it can utilize
This guide presents a free cooling concept based on the temperatures from the ground directly for cooling
a ground coupled heat exchanger combined with a purposes. The result is that free cooling can be provided
radiant heating and cooling system. A ground coupled with only cost being the electricity required for running
heat exchanger can for example be horizontal collectors, the circulation pumps in the brine and water systems.
vertical boreholes or energy cages. A radiant system No heat pump is required.
means that the oors, ceilings or walls have embedded
In the heating season the system is operated using a
pipes in which water is circulated for heating and
heat pump. As the ground temperature during winter
cooling of the building. Under oor heating and cooling
is higher compared to the outside air temperature,
is the most well know example of a radiant system.
the result is improved heat pump efciency (COP)
A radiant system combined with a ground coupled heat compared to an air based heat pump. In addition, the
exchanger is highly energy efcient and has several radiant emitter a system (under oor heating) operates
advantages. In the summer period, the ground coupled at moderate water temperatures in large surfaces which
heat exchanger provides cooling temperatures that are further improves the heat pump COP.
Comfort and energy efciency Furthermore, radiant systems are able to heat at a
low supply temperature and cool at a high supply
the best t for low-energy
temperature. This ts perfectly to the typical operating
houses temperatures of a ground coupled heat exchanger.
Furthermore, the connected heat pump will be able
Using shading will help to reduce the cooling demand. to run more efciently and thereby consume less
However, this forces occupants to actively pull down the electricity. In addition, a radiant system provides no
shades e.g. when leaving the house. Also, shading will draught problems and provides an optimal temperature
block daylight which increases electricity consumption distribution inside a room. Last but not least, radiant
on articial light, and shading will block the view which systems provide complete freedom in terms of interior
may not be in the interest of the home occupant. design, as no physical space is occupied inside the room.
In fact many architects state that energy efciency
and comfort may conict when dening comfort in a Even more important when looking at the lifetime and
broader sense, such as the freedom to design window property value of a house, such systems have very low
sizes, spaciousness with increased ceiling height, maintenance need and a lifetime that almost follows
daylight requirements and the occupants tendency to the lifetime of the building itself. In todays uncertain
utilise open doors and windows. All such requirements environment of future energy prices, free cooling and
put increased demands on the HVAC applications. ground coupled heat pumps provides a high stability
on the future energy costs of the building in question.
Ground heat exchangers combined with radiant systems It will most certainly meet todays and future building
is the only all-in-one solution, with the ability to regulations even in a scenario where future property
provide both heating and cooling. Such systems are taxation would be linked to energy efciency. Hence, it
more cost efcient and simpler to install than having is an investment that helps to maintain and differentiate
to deal with a separate heating and cooling systems. the future property value.
25
20
Energy class
15
The design cooling load (or heat gain) is the amount Factors inuencing the sensible
of energy to be removed from a house by the
HVAC equipment, to maintain the house at indoor
cooling load
design temperature when worst case outdoor design
temperature is being experienced. As can be seen Windows or doors
from the gure above, heat gains can come from Direct and indirect sunshine through windows,
external sources, e.g. solar radiation and inltration skylights or glass doors heating up the room
and from internal sources, e.g. occupants and electrical
equipment. Exterior walls
Two important factors when calculating the cooling load Partitions (that separate spaces of different
of a house are: temperatures)
(Sensible) Total
Air sensible
CONDITIONED
Ventilation (Latent)
S PA C E
Cooling
Lighting (Sensible) Load
Total
Internal heat gain
(Sensible) latent
Equipment
(Latent)
(Sensible)
People
(Latent)
Internal gains in residential buildings are limited to the Without shading; cooling loads up to 60 W/m2.
people normally occupying the space and household
equipment. In national building regulations, the load
for internal gains in ordinary residential buildings is
often mentioned (3-5 W/m2). In residential buildings,
the cooling load primarily comes from external heat
gains, and mostly from solar gains through windows
and doors, transmission through wall and roof, and
inltration through the building envelope/ventilation.
The gure below shows that about 2/3 of the cooling
load comes from the solar radiation.
10%
52% 13%
15%
Shading factor 85%; cooling loads up to 25 W/m2.
37 37
36 No window opening, no HRV by-pass 36 No window opening, no HRV by-pass
35 Open windows, no HRV by-pass 35 Open windows, no HRV by-pass
34 34
33 Open windows, with HRV by-pass 33 Open windows, with HRV by-pass
Temperature [C]
Temperature [C]
Shading factor 50%; over-temperature up to 1 100 hours per year. Shading factor 85%; over-temperature up to 800 hours per year.
The simulations show that without active cooling building regulations across Europe have already started
there will be a signicant amount of time with over- to implement maximum duration periods of over-
temperature (assuming that the maximum temperature temperature. In Denmark, the requirement in the 2015
allowed is 26 C). All the cases also show that standard is that a temperature above 26 C is only
with radiant oor cooling, it is possible to keep the allowed for maximum 100 h during the year and above
temperature below 26 C all year round. National 27 C for maximum 25 h during the year.
5000 5000
Cooling Cooling
4500 4500
Heating Heating
4000 4000
3500
Capacity [W]
3500
Capacity [W]
3000 3000
2500 2500
2000 2000
1500 1500
1000 1000
500 500
0 0
January
February
March
April
May
June
July
August
September
October
November
December
January
February
March
April
May
June
July
August
September
October
November
December
Low energy building, no shading. Low energy building, shading in-between windows.
Window opening and HRV by-pass are used during cooling season Window opening and HRV by-pass are used during cooling season
5000
4500 Cooling
Heating
4000
3500
Capacity [W]
3000
2500
2000
1500
1000
500
0
January
February
March
April
May
June
July
August
September
October
November
December
+3 Hot 1.2
Dissatised [%]
+2 Warm
+1 Slightly warm
Basic clothing Basic clothing
0 Neutral insulation: 1.0 insulation: 0.5
-1 Slightly cold
-2 Cool
Operative temperature [C]
-3 Cold
Seven-point thermal sensation scale Operative temperature for winter and summer clothing
0.4
Maximum air velocity, 0.5 m from wall [m/s]
0.3
0.25
0.2
0 9 18 27 36 45 54 63 [F] 0,5
80
60 0
40 Warm ceiling Cool wall 2 4 6 8 10
Dissatised [%]
difference
The comfort categories are divided into A, B and C
depending upon the difference between the air
temperature at oor level and at a height equivalent to
a seated person. As can be seen below, the temperature
difference must be under 2C in order to reach
category A.
18 20 22 24 26
Vertical air temperature difference a [C]
Category C Ideal heating Underoor heating
Radiant ceiling heating External wall radiator heating
A <2
B <3 Vertical temperature prole with different emitter systems
C <4
a) 1,1 and 0,1 m above oor
Heat ux density 10
Cooling
21 Room temp. 25 C
20 Room temp. 24 C
19 Room temp. 23 C
18
17
16
15
14
13
12
11
10
9
8
40 45 50 55 60 65 70 75 80
Temperature [C]
35 Cooling
humidity of 50%. At the dew point, condensation
will occur on the emitter surface. In order to avoid 30
Cooling
160
Distribution pipes and manifolds
140
In any cooling system where you have distribution pipes
120
or manifolds you have to be aware of that these parts
100
of the system also have a risk of condensation because
they sometime operates below the dew point. Insulation 80
avoid condensation. 40
20
Design temperature
0
Floor Parimeter Ceiling Wall
The design supply water temperature of the system
depends on the type of surface used, the design indoor Maximum heating a cooling capacities
conditions (temperature and relative humidity) and the
cooling loads to be removed. It should be calculated to In theory, the highest heating capacity can be achieved
obtain the maximum cooling effect possible from the from the wall. Since space is limited due to windows
system. and other things hanging on the wall, the real heating
capacity from walls is signicantly reduced. Hence, the
The capacity and mean water temperature for radiant
biggest capacity can be achieved by heating from the
oor cooling depends on the oor construction, pipe
oor, and cooling from the ceiling. In practice, either
pitch and surface material. To have the highest possible
a oor system or a ceiling system is installed and used
capacity of the system you should design your oor
for both heating and cooling. A oor system should
construction so the surface temperature is equal to the
be chosen if the heating demand is dominant and a
minimum temperature of 20 C.
ceiling system should be chosen if the cooling demand
The capacity and mean water temperature for radiant is dominant.
cooling from the ceiling is calculated, or can be read
directly, in the capacity diagram of the cooling panels.
To have the highest possible capacity of the system you
should design as close to the dew point as possible.
Ground conditions
When planning the use of ground heat exchangers, on being in contact with ground water. Hence the depth
the ground conditions are of fundamental importance. of ground water levels has an important impact on the
Determining the ground properties, with respect to performance of a vertical ground heat exchanger.
the water content, the soil characteristics (i.e. thermal
In addition to the water concentration, different ground
conductivity), density, specic and latent thermal
types have different thermal conductivity. For example
capacity as well as evaluating the different heat and
rock has a higher thermal conductivity than soil, so
substance transport processes, are basic pre-requisites
ground conditions with granite or limestone will give a
to determine and dene the capacity of a ground heat
better performing ground heat exchanger than sand or
exchanger. The dimensioning has a signicant impact
clay.
on the energy efciency of the heat pump system.
Heat pumps with a high capacity have unnecessary
Thermal conductivity
high power consumption when combined with a poorly
Soil type (W/m K)
dimensioned heat source.
Clay/silt, dry 0.5
With a higher water concentration in the ground, you Clay/silt, waterlogged 1.8
get a better system capacity. Horisontal collectors are
Sand, dry 0.4
hence depending on the grounds ability to prevent rain
water from mitigating downwards due to gravitation. Sand, moist 1.4
The smaller the corn size in the soil, the better the Sand, waterlogged 2.4
ground can prevent rain water from gravitation. Hence Limestone 2.7
clay will provide a better performing ground heat Granite 3.2
exchanger than sand. Vertical collectors are depending
Source: VDI 4640
*) Energy cage; normal height is 2.0 m, and Horisontal collectors Energy cage Vertical collectors
XL height 2.6. Required depth is 4 m.
When calculation the pressure loss in the collector the In the diagram below, the pressure loss in the
ow is divided equally up in the number of loops. For ground collector should be maximum 34 kPa at the
vertical collectors the total pressure loss is normally dimensioning conditions, and the ground collector
very low hence the pressure is equalized and it is only should be dimensioned so that the pressure loss in each
the pressure loss in the feeding pipe has an inuence. loop is less than 34 kPa.
For horisontal collectors and partly energy cages
Pump diagram
the pressure loss has to be calculated in order to be
Available pressure for the primary circuit.
sure that the pump will be able to circulate the water
through the collector and the cooling exchanger
Pressure loss [kPa]
including manifolds and valves.
50
Example: 4 kW installations
40
Liquid Monoethylenglycol
10
The illustrations below shows a ground heat exchanger As one can see from the grey connection lines the pump
combined with a radiant system in heating mode and and exchanger group is not active in heating mode.
cooling mode. In this example a ground sourced heat Similarly, the connection lines from the heat pump (or
pump is providing heating to domestic hot water any other heat source) to the emitter systems are in-
(DHW), space heating, and for heating up the incoming active in cooling mode.
ventilation air. This could of course be utilized with If a boiler or district heating system is used as heating
other heat sources such as boilers or district heating. source, the ground heat exchanger will only work during
Free cooling is provided through a special pump and cooling (also known as a bivalent system). If a ground
exchanger group (see chapter 8) that supplies cold source heat pump is used as heat source, the ground
water/brine from the ground heat exchanger directly to ground heat exchanger will work both during heating
the radiant emitter system and possibly the incoming and during cooling (also known as a monovalent
ventilation air. In cooling mode, the heat pump will only system).
be active for domestic hot water generation.
Heating mode, the free cooling is deactivated Cooling mode, the free cooling is activated
Embedded emitters are the key to any radiant system. the oor has the highest heating efciency, but with a
In order to have an energy efcient and comfortable lower cooling efciency.
solution, the emitter system has to be designed to
Another important factor is the supply water
the construction but also to the task it has to solve.
temperature. Radiant emitter systems operate on a
There are many types of constructions for oor, wall
relatively low temperature for heating, and a relatively
and ceilings. Uponor offers emitters that can meet the
high temperature for cooling. A radiant system should
requirements of all types of installations. All emitters
be designed for the lowest possible temperature for
are able to provide heating and cooling. However, some
heating and the highest possible temperature for
emitters are more efciently than others. The most
cooling. This secures a heating/cooling system with
efcient cooling system is placed in the ceiling, but the
high energy efciency and optimal conditions for the
heating efciency is lower whereas an emitter system in
heating and cooling supply.
CN
pipes
40
m 15.5 C, m 18.5 C,
10 mm tiles 10 mm tiles
Wet oor
42 40 33 24
installation
Installation
integrated in 42 40 33 24
construction
Installation on the
28 20 27 19
joists
Dry oor
28 20 27 19
installation
Installation
24 17 18 14
between the joists
Cooling effect Cooling effect Cooling effect Cooling effect Cooling effect Cooling effect
Wall Installation q [W/m2] q [W/m2] q [W/m2] q [W/m2] q [W/m2] q [W/m2]
installation principle m 15.5 C m 18.5 C m 15.5 C m 18.5 C m 15.5 C m 18.5 C
Dry wall
45 32
installation
Wet wall
60 45
installation
Stud wall
42 34
installation
Ceiling Cooling effect Cooling effect Cooling effect Cooling effect Cooling effect Cooling effect
Installation
installation q [W/m2] q [W/m2] q [W/m2] q [W/m2] q [W/m2] q [W/m2]
principle
m 15.5 C m 18.5 C m 15.5 C m 18.5 C m 15.5 C m 18.5 C
Wet ceiling
75 55
installation
Dry ceiling
59 42
installation
Suspended
ceiling 97 67
installation
Capacity diagrams
Uponor offers a wide range of embedded emitter 3. Pipe pitch, i.e. centre distance between the pipes T
systems adapted to different kinds of constructions in [cm]
the oor, wall or ceiling. Whenever the choice of system
4. Difference between room temperature and mean
has been selected, detailed diagrams can be used in
water temperature c. = i - c [K]
order to make the planning of the capacity. The diagram
and example on next page shows a oor construction 5. Recommended minimum surface temperature
with the cooling and heating output of the emitter (20 C)
system.
6. Difference between room temperature and surface
temperature v - r, m [K]
Dimensioning diagram for cooling
If three of the parameters above are known, the
Analogue to dimensioning for heating, the following
remaining parameters can be calculated using the
parameters must be considered:
diagram to the right.
1. Cooling effect of the radiant area qc [W/m2]
2. Thermal resistance in the surface construction RB
[m2 K/W]
=
80 T 30 H
80
60 60
10 K
8K
40 40
6K
20 =4K 20
=
C
i C
0 0
30 5 20 T 15 T 10
T T2 T T qH H,N
Thermal resistance RB [m2 K/W]
0,05
cm W/m2 K
0,10
Heating 10
15
20
98,6
96,3
93,0
15,9
18,1
20,3
25 87,3 22,0
30 81,3 23,6
0,15 0
20 15 T 10
25
T T
T
0,05
C,N
Cooling T
cm
10
qC
W/m2
34,8
K
8 0,10
15 39,8 8
20 27,5 8
25 24,5 8
0,15
Note: The required cooling effect can only be achieved to avoid condensation, a supply water controller such as
if the median surface temperature and the dimensioned Uponor Climate Controller C-46 is needed.
supply temperature are above the dew-point. In order
In low-energy buildings there will in particular be high In addition, room by room regulation provides the
variations in the individual room heating and cooling possibility to shut down cooling in a specic room, such
loads (see gure 5.2). This means that lack of individual as a bathroom or a room without cooling loads.
Room 1
Living room Kitchen
18C
21C 21C
Room 2
Bedroom Bath 1 Room 3 Entrance Bath 2
18C
21C 22C 21C 20C 22C
Typical desired temperature (set points) in a single family house. Typical variation between individual room heat demands in a
low-energy house.
23 Thermostat set
point 20 C
22
b Uponor DEM
Lost energy when
technology
21 using Uponor DEM technology
a Lower
b heating = 13.9 W/m2 temperature -
Time
20
a heating = 19.1 W/m2
19 Typical behaviour in a heavy oor construction, where Uponor
Time
DEM technology ensures that a minimum of energy is lost to the
construction. Compared with traditional on/off regulation, saving
Self-regulating effect. UFH/C outputs for different temperatures gures between 3-8% can be obtained.
between room and oor surface.
I-76
C-46
C-46
C-56
C-56
230 V AC C-56
230 V AC
M
T-75
24 V DC
M
230 V AC M
Simple zone control, the central controller provides a regulated supply Individual room control, the central controller provides a regulated
temperature based on the outdoor/indoor temperature. supply water temperature based on the outdoor/indoor temperature and
the room thermostat controls the room temperature by using actuators.
The Uponor Pump and exchanger group, EPG6, system and interact with the Uponor Control
is designed for a separate cooling supply and System used to control the emitter system.
temperature control for ground source free Uponor Climate Controller C-46 is also able to
cooling. The EPG6 is pre-mounted and ready control the temperature according to the dew
to install in the installations. Together with point, in order to prevent condensation.
the Uponor ground collectors it is ready
The primary side of the system is driven by
to provide free cooling for radiant emitter
a circulation pump, to circulate the uid
systems.
in the brine circuit and a 3-way mixing
The EPG6 can be integrated in HVAC valve for controlling the primary ow, in
installations for applications a separate supply order to maintain the correct temperature
of cooling needs to be provided through a on the secondary side. The exchanger that
heat exchanger (e.g. from a ground collector). exchanges the brine from the ground circuit
The EPG 6 is controlled by Uponor Climate with the water in the emitter system is
Controller C-46, which is able to adjust the designed for a capacity up to 6 kW.
secondary temperature supplied to the emitter
Secondary circlet,
to emitter system
5
7
8
Component overview
3 Primary side
4
The primary side of the system (ground collector) is
connected to the EPG6 and will work as the heat sink.
2 The mixing valve (1) will adjust the ow of the primary
10
9 side and is controlled by the Uponor Climate Controller
C-46 (10), which opens and closes the valve to the
adjusted supply temperature on the secondary side
1 measured by the supply sensor (7). The primary pump
(2) will circulate the uid in the brine circuit through
11 the exchanger (4) and will shut down when there is no
request from the secondary control system. The lling
Primary side, ground collector and air valve (3) is used to ll up the primary system
or other cooling supply
with brine. Connection to an expansion tank and safety
valves can be done on the connection valve (9).
1 3 way mixing valve Kvs 7 m3/h
2 Primary circulation pump Grundfos Alpha 2L 26-60
3 Filling and air valve G
Secondary side
4 Heat exchanger 6 kW SWEP ESTH x 40/1P-SC-S 4 x The secondary ball valves (5 and 6) are shutting down
5 Ball valve with integrated check valve and thermometer Rp 1
the secondary side of the system, and have a ball
6 Ball valve with integrated thermometer Rp 1
valve (5) including a check valve to prevent backow
7 Sensor pocket (supply)
8 Blind piece 180 mm G 1 for secondary circulation pump in the system. The blind piece (8) can be replaced
9 Filling valve G by a circulation pump, if no other pump is used for
10 Uponor Climate Controller C-46 the secondary side. The secondary pump has to be
11 Primary connection Rp 1 connected to the Uponor Climate Controller C-46 (10).
580
Rp 1 Rp 1
125
Pump diagram
Available pressure for the primary circuit
50
40
Pressure loss [kPa]
30
CP2
20
CP1
10
0
0 0.5 1 1.5 2 2.5 3
3
Flow rate [m /h]
C-56 I-76
The system diagram illustrates a Uponor free cooling A diverting valve (7) is used to switch the ow direction
installation using a ground collector and Uponor EPG6 in the hydraulic system between heating and cooling
in combination with a brine to water heat pump for (diverting valve to open when cooling is activated).
space heating and domestic hot water.
When switching between heating and cooling, the heat
The EPG6 (3) is connected to a Uponor ground collector pump must be in a position where it only produces
(1) on the primary side of the free cooling installation. If domestic hot water (typically summer mode can be
more than one ground loop is installed, a manifold can used).
be used to connect the ground loops.
The Uponor Climate Controller C-46 can send an
The secondary side of the EPG6 is connected to the external signal to the heat pump when switching
heating pipe system before the manifold of the radiant between heating and cooling or it can be done
system (4). manually with a relay switch. Contact the heat pump
manufacturer in order to check the possibilities.
6
TW
7 3
3 Uponor EPG6 with Uponor Climate Controller C-46 8 Non return valve
The system diagram illustrates a Uponor free cooling When switching between heating and cooling, the boiler
installation using a ground collector and Uponor EPG6 must be in a position where it only produces domestic
in combination with a gas/oil boiler for space heating hot water (typically summer mode can be used).
and domestic hot water.
The Uponor Climate Controller C-46 can send an
The EPG6 (3) is connected to a Uponor ground external signal to the boiler when switching between
collector (1) on the primary side of the free cooling heating and cooling or it can be done manually with a
installation. If more than one ground loop is installed, a relay switch. Contact the boiler manufacturer in order to
manifold can be used to connect the ground loops. check the possibilities.
The secondary side of the EPG6 is connected to the In the example below, a solar collector is supporting the
heating pipe system before the manifold of the radiant boiler for space heating and domestic hot water but is
system (4). not interacting with the cooling system.
A diverting valve (7) is used to switch the ow direction
in the hydraulic system between heating and cooling
(diverting valve to open when cooling is activated).
8
2
5
M
The system diagram illustrates a Uponor free cooling Please note that a circulation pump (180 mm) has to be
installation using a ground collector and Uponor EPG6 added to the EPG6 in order to circulate the secondary
as a stand-alone system. circuit. There is a blind piece on the EPG6 that can be
replaced with a pump.
The EPG6 (3) is connected to a Uponor ground
collector (1) on the primary side of the free cooling The activation of the EPG6 cooling module can be
installation using the same supply line as to the heat done automatically through the Uponor Climate
pump. If more than one ground loop is installed, a Controller C-46 included in the EPG6 or through
manifold can be used to connect the ground loops. another external signal through the climate controller.
The secondary side of the EPG6 is connected to the
heating pipe system before the manifold of the radiant
system (4).
Operating mode
Heating
Heating and cooling
Cooling
Uponor > Main menu > Control settings > Advanced control > Operation
Wizard great installation guide mode. Note that the startup wizard will start when changing mode.
When Uponor Climate Controller C-46 is started for
the very rst time, it guides the installer to make the Heating min./max. supply Uponor
necessary primary settings of the system. Wizard helps Climate Controller C-46
you step by step through the installation process. On
In the case of combined heating and cooling system,
the display, the installer can read all about the set-up
where you can change between heating and cooling,
and what to do next. The installation wizard is also
the climate controller C-46 must always be set to
started after changing or resetting the operation mode.
Heating and cooling mode, even when the climate
controller is not used as primary controller for heating.
Quick menu gives easy access to basic settings
In this case the heating setting in the climate controller
Made for end-users: The quick menu consists of a series must be neutralized as follows:
of screens easily accessible from the Uponor screen.
These screens display readings for daily use. If the
Uponor Climate Controller C-46 is set to installer access Min./max supply
level, it is also possible to modify some parameters.
Min Max
Main menu all informations and settings on the 5.0 C 8.0 C
whole
The main menu and all its sub-menus are used for
displaying any accessible information, parameter Uponor > Main menu > Control settings > Heating > Min./max supply
OK, also covered in startup wizard.
settings, and selecting operating modes that are
accessible in the system.
Operating mode Uponor > Main menu > Control settings > Cooling > Dew point
1
2A
24VAC/DC
G H I J K L
Change-over between heating and cooling can also
C-56
0-10V
+ - N L
230 V ~
automatically using the indoor-outdoor temperature
24 V 2A
L
N
50 Hz
controlled switch-over, or a manual command. When
230 V ~
Contact closing output from the best source or from manual switch. The
supplier of the heat source will be able to give guidelines of which signal
is available.
Reset
1 2 3 4 5 6 7 8 9 10 11 12
V ~ 50 Hz
+ - N L
0-10V 230 V ~
24 V 2A
L
N
50 Hz
Bus master
Bus slave
No bus 2
230 V
Uponor > Main menu > Control settings > H/C switchover 1 Heat pump 4
3
2 Pump
3 Diverting valve
4 Actuator 24 V
5 Relay (e.g. Uponor 1000517)
The heat source must be able to receive potential free signal, i e sense a
dry contact closure. The supplier of the heat source will be able to give
guidelines of which signal is available
Bus master
Indoor and outdoor 1 2 3 4 5 6
Reset
7 8 9 10 11 12
Supply water temp.
General purpose input 2A
24VAC/DC
C-56
Uponor > Main menu > Control settings > H/C switchover > Bus master 230 V 5 6
Uponor > Main menu > General settings > General purpose output >
Mode
Uponor Corporation
www.uponor.com
Uponor reserves the right to make changes, without prior notication, to the specication of
incorporated components in line with its policy of continuous improvement and development.