Stage 1 2 Vessel 2 2 Ele/ves 3 3,2 55 m3/hr 60 Feed 8.3 8.3 59.99 Conc 3.3 3.3 4.99 Perm 5 5 Rec 3.6 0.6

This document compares two reverse osmosis (RO) schemes and provides design details for various RO system components. Scheme 1 has 2 vessels with 3 elements in the first and 3,2 elements in the second, treating 60 cubic meters per hour of feed water. Scheme 2 has 2 vessels with 55 elements each, treating 59.99 cubic meters per hour. Design details are also provided for high pressure pumps, permeate recovery rates, and total dissolved solids concentrations for the feed and concentrate streams. Vessel sizing calculations, pump power calculations, and the design of an aluminum removal filter are summarized. A cost estimate is also included for an RO system from a particular vendor.

Uploaded by

Rajesh Nare
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views

Stage 1 2 Vessel 2 2 Ele/ves 3 3,2 55 m3/hr 60 Feed 8.3 8.3 59.99 Conc 3.3 3.3 4.99 Perm 5 5 Rec 3.6 0.6

This document compares two reverse osmosis (RO) schemes and provides design details for various RO system components. Scheme 1 has 2 vessels with 3 elements in the first and 3,2 elements in the second, treating 60 cubic meters per hour of feed water. Scheme 2 has 2 vessels with 55 elements each, treating 59.99 cubic meters per hour. Design details are also provided for high pressure pumps, permeate recovery rates, and total dissolved solids concentrations for the feed and concentrate streams. Vessel sizing calculations, pump power calculations, and the design of an aluminum removal filter are summarized. A cost estimate is also included for an RO system from a particular vendor.

Uploaded by

Rajesh Nare
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

RO Scheme comparision

stage 1 2
vessel 2 2
ele/ves 3 3,2 55
Flow m3/hr 60
Feed 8.3 8.3 59.99
conc 3.3 3.3 4.99
perm 5 5
rec 3.6 0.6

HPP
m3/hr 11.9 8.9
bar 11 13.1

TDS ppm
Feed 1000 1000
conc 2478 2485
perm 14 9.9
rec 2478
5
6
5.99
0.99
5.040404
3.427475 1 m3/hr
58.42747 filtratio 0.5 m3
backwash 1.5 m3/hr
0.0125 m3
0.025
Vessel size selection

Flow rate 1.3 m3/hr

Design velocity 24 m/hr

Vessel CS area 0.05416667 m2

Dia 0.3 m
262.7 mm
10.3 inch
pump power calculation

flow rate 10 m3/hr


rated differential head 13.5 m
density of liquid 1000 kg/m3
efficiency of pump 75 %

power 0.4905 kW
Aluminium removal filter

Resin quantity 400 lit


Salt for regeneration(120-140 gpl) 56 kg

Resin bed depth to be provided 1m


dia of vessel 0.7 m
713.8 mm
Free board 50 %
200 lit
0.2 m3
FB height 0.5 m
Supporting media 0.2 m
Total height 1.7 m
dia 0.7 m
aventura starlite
1 vessel 3072 31735 24348
2 media 400 lit 124000
3 destributor 3690
4 frontal piping 5000
5 air vent, drain, sampling, PG 1500
6 miscellaneous 1000
159538
mark up 15 187691.8
nigotiation 5 197570.3
198000