Control valves shall normally be sized in accordance with ANSI/ISA S75.01 for the rates
of flow and pressure drops at design conditions. The vendor shall be responsible for
sizing all control valves and shall submit calculations for approval, prior to
manufacture.
In general, an equal percentage control valve characteristic will be expected.
However, a linear characteristic shall be used where two control valves are operating
in split-range service or where the control valve pressure drop remains substantially
constant over the range of 10% to 100% of flow capacity.