Distribution System Short Circuit Analysis
Distribution System Short Circuit Analysis
-
W. H. Kersting IEEE Fellow W.H. Phillips
New Mexico State University W. H. Power Consultants
P. 0. Box 3-0 P. 0. Box 3903
Las Cruces, NM 88003 Las Cruces, NM 88003
ABSTRACT
-
Figure 1 Radial System Model
In Figure 1, ZTOT is a three-phase impedance matrix that matrix which is reduced to a 3 x 3 matrix using the &on
represents the total equivalent impedance between the fault reduction technique [2]. For single-phase and two-phase line
bus and the system equivalent generator. This impedance will sections, the 3 x 3 impedance matrix will be characterized by
include the total line impedance from the faulted bus back to a row and column of zeros occupying the position of the
the substation plus the substation transformer impedance plus missing phase or phases.
the system equivalent impedance as determined at the high
voltage bus of the substation.
310
All of the necessary data for computing the total impedance Equation 11 in expended form is:
from the faulted bus back to the low voltage bus of the
substation is input by section and automatically stored in an
ordered form after the system graph is built. The sum of the
substation transformer and system impedance is input
separately.
In Figure 1, the voltages Ea, E,, and E, are the equivalent (12)
system voltages and are usually assumed to be 1.0 per unit.
The impedances, &, represent the impedance in the fault. In Equation 12 let:
This value is supplied by the user.
ya = yaa + Yab yac (13)
Kirchhoffs voltage law can be applied in matrix form to the
Yb = Yba + Ybb + Ybc
Y, = Y, + Y* + Y,
With the terms defined in Equations 13, Equation 12
becomes:
Three-phase Faults
1, + 1, + I, =0
31 1
Equations 15 and 17 therefore define the four necessary Equations 19 and 22 provide the four unknowns necessary to
unknowns so that Equations 16 (derived from Equations 14) solve Equation U) for a b-c fault. In general, for a fault
can be used to solve for the three unknown line currents. between phase i and phase j with phase k unfaulted, Equations
24 and 25 are used.
v, = v, = v, = vxe= 0 (18)
Equation 18 defines the necessary four unknowns for this fault
condition.
I, = 0
1, + IC 0
-
I, = 0 = IP, Y,v, - YaVv (20) Line-to-line-tomound Faults (assume b-c-g)
1, = m b - Y & v a * Y b v q v, = v, = vq = 0 (27)
Adding the last two equations and then rearranging terms Equations 14 are used to get:
yields two equations in matrix forms:
I, = 0 = IP, Y,v, - (28)
Therefore:
v, = IPJY, (29)
where: v, = vq = 0 (32)
y = [(Yk?YW) (Y*ya
+ Yc) r (23)
Ib
1, = IC= 0
=0 =w b Ybbvbx Yhvbx
312
Solving these two equations for V, and V, gives: Substation
-Three-phase short circuit MVA and angle at the high
voltage terminals of the substation transformer.
(34) -Substation transformer ratings and impedance.
-Substation transformer output voltages.
where:
Load Types
-Spot and distributed loads.
-All wye connected.
-All constant kW,kVAr.
Line Types
- Three-phase overhead.
- Single-phase overhead (a-n, b-n and c-n).
Voltage Regulators - single-phase regulators wye
connected.
-
Figure 3 34 Bus Circuit Diagram
313
TABLE 2
PHASE NEUTRAL
CONF COND COND SPACING
ID PHASINGACSR ACSR ID
Table 2 gives the Overhead Line Configuration Codes for this The Radial Distribution Analysis Package short circuit routine
system. e the results of a short circuit study
oped in this paper and the IEEE 34
S H O R T C I R C U I T
IEE
Thi
THE FAULT STUDY Is RUN,WITH THE FOLLO
Voltage (Per unit): 1
s): 2.510+j20. 1
si): 2.480+j19.840 CO1
40.00 CRI
THE FOLLOWING BUSES WIL >IN THE FAULT OUTPUT (IGNORING ZERO
800 806 808 0 816 822 854
832 888 858 864 836 838 834
314
The positive and zero sequence impedances in ohms of the short circuit current. The usual application of the method of
transformer plus equivalent high voltage system as measured symmetrical components would not have allowed for the
at the low voltage terminals of the transformer are required determination of the phase-b to ground faults currents.
input data. The values shown are determined from the given
data for the sample system as follows: CONCLUSIONS
Transformer: Base Z = 24.g2/2.5 = 248.00 ohms Because a distribution feeder is composed of many single-
phase laterals and is inherently unbalanced both in loading
Z + = Zo = (0.01 +jO.O8) * 248.00 ohms and construction, it is necessary to use a different method of
= 2.48 + j19.84 ohms short circuit analysis than the usual application of
symmetrical components. This paper has developed a general
System: '
2 = (24.92/1800)/85 ohms method for the computation of the short circuit currents for
= 0.03 + j0.3431 ohms all possible types of faults on an unbalanced three-phase radial
distribution system. The method has been incorporated into
The equivalent positive sequence impedance is the sum of a personal computer package of programs (RDAP). RDAP
the transformer plus system positive sequence impedances was used to perform a short circuit study using the program
with the final value shown in Figure 4. The equivalent and the IEEE 34 Bus Radial Distribution Feeder and some
zero sequence impedance is only the transformer impedance of the results listed.
since the transformer is grounded wye on the 24.9 kV side
and therefore the system zero sequence impedance is not REFERENCES
"seen" from the low side transformer terminals. The value of
fault resistance of 40 ohms was selected because it is a 1. Carson, John R., "Wave Propagation in Overhead Wires
standard value used by many electric cooperatives. with Ground Return", Bell System Technical Journal,
New York, Vol. 5, 1926.
The short circuit routine allows the user to either have the 2. G. Kron, Tensor Adysii of Nelvmrks, John Wiley &
short circuit currents determined at every bus in the system Sons, New York, 1939.
or to select buses of interest. The latter is used here with the 3. W.H. Kersting, W.H. Phillips, "Modeling and Analysis of
selected buses listed in Figure 4. These buses were selected Rural Electric Distribution Feeders", IEEE Rural
for fuse coordinations purposes. Electric Power Conference, Orlando, Florida, April 1990.
4. "Radial Distribution Test Feeders", IEEE Distribution
Table 3 lists the currents for short circuits at Buses 854 and Planning Working Group Report. Presented at the 1990
856. The lateral tap at Bus 854 going to Bus 856 is a single- IEEE PES Summer Power Meeting, Minneapolis, MN
phase consisting only of phase-b and neutral. As shown in 5. "Specifications and Drawings for 14.4m.9 kV Line
Table 3, a phase-b to ground short circuit is the only possible Construction, REA Form 803, Rural Electrification Ad.
TABLE 3
Short Circuit Output Report
- S H 0 R T C I R C U I T S T U D I E S - DATE: 5- 4-1990 AT 15: 3:57 HOURS
IEEE 34 BUS REA DISTRIBUTION FEEDER
BUS/FAULT (EQV SYST > V:1.00 PU; 2-P: 2.5+j20.2 OHMS; 2 - 0 : 2.5+519.8 OHMS)
----------- Phase A Amps ----
Phase B Amps Phase C Amps ----
Ground Amps -----
BUS 854 FR=40. FR=4 0. FR=40. FR=40 .
Fault
L-G 187.0 132.8 186.9 133.0 187.0 132.9
A-B 200.5 130.2 200.5 130.2
A-B-G 204.4 133.3 225.6 152.2 154.8 117.7
A-C 200.5 130.2 200.5 130.2
A-C-G 225.3 151.9 204.6 133.5 156.4 118.4
B-C 196.4 129.1 196.4 129.1
B-C-G 203.2 134.2 219.9 149.8 159.5 119.8
A-B-C 233.2 150.8 231.4 151.0 225.3 147.9
-----------
A-B-C-G 231.7 150.1
Phase A Amps -
232.5 151.7
Phase B Amps
225.7 147.9
Phase C Amps
4.5
---- 2.3
Ground Amps -----
BUS 856 FR=40. FR=40 . FR=40. FR=40.
Fault
B-G 159.2 117.7
31 5