Bus Protection
Bus Protection
Bus Protection
Mike Kockott
March, 2015
History of Bus Protection
Circulating current differential (1900s)
Boundary of the protected zone defined by the current measuring points (CTs)
ZA ZB
Ideally, for balanced conditions (no in-zone fault), currents will balance, i.e. current
into the zone = current out of the zone
For in-zone fault, currents no longer balance, i.e. current into the zone current
out of the zone
Measurement Principle
Traditionally, bus differential relays measure the secondary currents of
magnetic core CTs
non-linear devices
needs to be taken into account in the measurement design of bus differential
relays
Remanence
random parameter that can improve or reduce ability to transform primary current
Secondary dc transient
occurs on interruption of primary current
takes the form of an exponentially decaying dc current
caused by discharge of stored energy
Magnetic Core CTs (Non-Linear Phenomena)
The non-linear phenomena of magnetic core CTs have the tendency to cause
unwanted operation of bus differential relays
so each type of bus differential relay (high impedance, numerical, etc.) must have
the means to overcome this non-linear behaviour in its measurement design
High Impedance
All CT secondary circuits are galvanically connected
it is this galvanic connection
between the CT circuits that
is used to overcome the non-
linear phenomena
RL
RL RL
High Impedance
How does it work
a high resistance RHIGH is
placed in series with the
operating element to limit the
level of false differential
current through the RL
differential branch (during
through flow conditions) RL RL
RHIGH is the effective total
resistance of the relay loop
RL is the total lead resistance RHIGH Metrosil
of the CT loop
I>
High Impedance
External (through flow) fault
no CT saturation
RL
RL RL
RHIGH Metrosil
I>
High Impedance
External (through flow) fault
full CT saturation
the maximum differential
branch current for an
external fault with a fully
saturated CT is: RL
(RL+RCT)max
Idiffmax = Iunbmax* R +(R
HIGH L+RCT)max RL RL
to ensure stability (no
unwanted operation), Idiffmax
for an external fault with a RHIGH Metrosil RCT
fully saturated CT must be
less than the set I> pickup
requires the maximum
resistance of the saturated I>
CT loop (RL+RCT) to be low
High Impedance
Criteria to be met:
CT requirements
all CTs must have the same ratio and magnetising characteristics
Gives operating times of less than one cycle for internal faults
Percentage Restrained
iOUT
iD
iIN
For stability, the differential current < set % of incoming (stabilising) current
Rl
e.g. for x% setting Rl+Rd must be < set x (pu), i.e. the total CT secondary loop
resistance must be less than a required value
Percentage Restrained
Stability (no unwanted operation) for external faults, even with fully saturated
CT, is guaranteed for differential current below the characteristic
Idiff Operate
Idiff > x*Iin
operate
Stable
stable
Idiff x*Iin
Rl
Iin x> Rl+Rd
Percentage Restrained
Short comings
unable to detect open CT
requires interposing (auxiliary) CTs to match main CT ratios (percentage restraint,
not possible for high impedance)
double bus (single circuit breaker)
requires switching in CT circuits
requires bistable (flip-flop) relays to replicate disconnector status for zone
selection, trip output selection
ZA
A A
ZA
1
B
B
ZB ZB
1
Earlier Generations
5
ZB
all x to ZA 1 2 3 4
all y to CZ
RL RL
R R
CT not E E
CT
L RCT L
saturated saturated
A A
Y Y
Numerical
the analog inputs are galvanically isolated
the secondary circuit loop resistance is no longer the important factor
the critical factor now is the time available to make the measurement, i.e. the time
to saturation [the CTs must be able to correctly reproduce the current for a
minimum time before saturation of the CT begins]
for practical protection class CTs, time to saturation, even under extremely heavy
CT saturation, is around 2 ms the design criterion used for the numerical
algorithm
Numerical
Review: measured signal relationships
Zone operating condition Incoming current iin Outgoing current iout Relationship
between
iin, iout, & id
Normal through load Load current to the Load current from the iin = iout
differential zone differential zone id 0
External fault without CT Fault current to the Fault current from the iin = iout
saturation differential zone differential zone id 0
External fault with CT Fault current to the Fault current from the iin >> iout
saturation differential zone differential zone id iin
Internal fault Fault current to the Outfeed current from the iin >> iout
differential zone differential zone id iin
Numerical
Internal fault Iin
Iout
Id
Id
critical criterion the
External fault with CT saturation Iin time available to make
Iout the measurement
[initial correct
reproduction of the
Id current before CT
saturation occurred]
Numerical
External fault with CT
saturation
Numerical
differential Trip
relay
IC
Numerical
Internal fault
Numerical
differential Trip
relay
Numerical
Short comings of earlier generations now overcome
detection of open CT circuit without requiring check zone
no need for dedicated CT cores with identical secondary windings (ref high
impedance)
no interposing CTs required any CT ratio difference can be accommodated
(practical limit is typically around 10:1)
double bus (single circuit breaker)
no switching in CT circuits (software zone selection and allocation)
no requirement for additional bistable (flip-flop) relays to create the
disconnector status replica internally achieved replica now generated within
the software based on the zone selection inputs
no need for additional tripping relays tripping logic based on internal software
zone selection replica
Numerical
Numerical
Features
zone differential protection
check zone
Numerical
Features
zone selection
disconnector auxiliary contacts connected to binary inputs
zone selection takes place in software based on binary input status
zone interconnection (i.e. load transfer) [two zones must merge as one]
automatic (e.g. for double bus, single breaker, using the already required zone
selection binary inputs)
externally driven (other applications) by connecting the applicable switchgear
auxiliary contact to a binary input
two zones (disconnector open), no selection (fixed to zone), one zone for
interconnection (disconnector closed)
1 circuit breaker
.. .
ZB
two zones, selection (disconnector closed on either ZA or ZB), one overall zone for
interconnection (disconnectors of the same object closed on both ZA and ZB)
Numerical
Double bus (single circuit breaker)
disconnector status fed to numerical IED via binary inputs zone selection made in
software
A IED
1.0 T
ZA
X ZA
A 0.0 F
B
B
1.0 T
ZB
X ZB
0.0 F
1
A/D conversion
1 Multiplication by CT ratio
Take account of star-point direction
Numerical
Double bus (single circuit breaker)
check zone required to ensure stable operation for
incorrect disconnector auxiliary contact status
Selection of which CT
currents to include in ZA is ZA-DIFF
made using disconnector &
auxiliary contacts ZA-OCT & ZA-TRIP
Selection of which CT
currents to include in ZB is ZB-DIFF
made using disconnector &
auxiliary contacts ZB-OCT & ZB-TRIP
No selection of which CT
currents to include in the CZ
is made using disconnector
CZ-DIFF
auxiliary contacts
for numerical IEDs with open CT detection, there is no need for the check zone
to be supplied from separate CT cores to the main zones
Numerical
Single bus
1 circuit breaker
ZA
ZA
Open = logic1
ZB
5 x0 87B
ZB
1 2 3 4
Numerical
Zone interconnection
ZA
6
5
ZB
1 2 3 4
ZA
6
5
ZB
1 2 3 4
ZA
6
5
ZB
1 2 3 4
1 2 3 4 5 6
1 2 3 4 5 6
no zone interconnection
no zone interconnection
ZA ZB
ZA
.. .
no zone interconnection
ZB
ZA ZB
trigger zone
disconnector status entered via OR
interconnection
BI
Numerical
End fault protection
CTs object side of the CBs
when an object CB is open, stop the measuring boundary at the open CB contacts
to remove the over-trip zone, and activate fast 50 protection to trip the remote end
Open = logic1
x0 87B
under-trip zone
Open = logic1
Further Numerical Technology Benefits over Earlier Types
Ability to communicate, built-in self-supervision
Built-in disturbance recorder, event recorder
Built-in independent 50BF breaker failure protection for every circuit breaker
Built-in multi-step independent 51 backup overcurrent protection for every
bay
LHMI operator interface, also showing critical overview information
etc.