Chapter 2
Chapter 2
Design
2-1 Installation...............................................................................11
2-1-1 Dimensions.......................................................................................11
2-1-2 Installation Conditions......................................................................13
2-1-3 Removing and Mounting the Covers................................................14
2-2 Wiring ...................................................................................... 16
2-2-1 Terminal Block..................................................................................16
2-2-2 Standard Connections......................................................................22
2-2-3 Wiring around the Main Circuit.........................................................23
2-2-4 Wiring Control Circuit Terminals.......................................................35
2-2-5 Conforming to EC Directive..............................................................38
10
Design Chapter 2
2.1 Installation
2-1-1 Dimensions
11
Design Chapter 2
A4007 140 Approx. 1.5
A4015 156 Approx. 1.5
A4022 156 Approx. 1.5
12
Design Chapter 2
VAC 2.9
Caution Be sure to install the product in the correct direction and provide
specified clearances between the Inverter and control panel or with
other devices. Not doing so may result in fire or malfunction.
Caution Do not allow foreign objects to enter inside the product. Doing may
result in fire or malfunction.
Caution Do not apply any strong impact. Doing may result in damage to the
product or malfunction
Direction
Install the Inverter on a vertical surface so that the characters on the nameplate
are oriented upward.
Dimensions
When installing the Inverter, always provide the following clearances to allow
normal heat dissipation from the Inverter.
W = 30 mm 100 mm Air
min. min.
Invert
Invert Invert Side
er
er er
W W W
100 mm Air
min.
13
Design Chapter 2
14
Design Chapter 2
After the front cover is removed, press the left and right sides of the terminal
cover in the arrow 1 directions and lift the terminal cover in the arrow 2 direction
as shown in the following illustration.
Note None of the following 200-V models have a terminal cover. Instead, the front
cover is used as a terminal cover.3G3MV-A2001 (0.1 kW), 3G3MV-A2002 (0.2
kW), 3G3MV-2004 (0.4 kW), 3G3MV-A2007 (0.75kW), 3G3MV-AB001 (0.1 kW),
3G3MV-AB002 (0.2 kW), and 3G3MV-AB004 (0.4 kW)
15
Design Chapter 2
2-2 Wiring
WARNING Wiring must be performed only after confirming that the power
supply has been turned OFF. Not doing so may result in electrical
shock.
WARNING Be sure to confirm operation only after wiring the emergency stop
circuit. Not doing so may result in injury.
Caution Install external breakers and take other safety measures against
short-circuiting in external wiring. Not doing so may result in fire.
Caution Confirm that the rated input voltage of the Inverter is the same as
the AC power supply voltage. An incorrect power supply may result
in fire, injury, or malfunction.
Caution Connect the Braking Resistor and Braking Resistor Unit as specified
in the manual. Not doing so may result in fire.
Caution Be sure to write correctly and securely. Not doing so may result in
injury or damage to the product.
Caution Be sure to firmly tighten the screws on the terminal block. Not doing
so may result in fire, injury, or damage to the product.
To wire the terminal block of the Inverter, remove the front cover, terminal
cover (unless the Inverter is a 200-V model), and bottom cover from the
Inverter. There is a label under the front cover indicating the arrangement
of main circuit terminals. Be sure to remove the label after wiring the
terminals. The output terminal of the motor has a label as well. Remove the
label before wiring the motor terminal.
16
Design Chapter 2
17
Design Chapter 2
Name Description
Symbo
l
R/L1 Power supply 3G3MV-A2 : 3-phase 200 to 230 VAC
S/L2 input terminals 3G3MV-AB : Single-phase 200 to 240 VAC (see
note 1)
T/L3 3G3MV-A4 : 3-phase 380 to 460 VAC
U/T1 Motor output 3-phase power supply output for driving motors.
terminals (see note 2)
V/T2 3G3MV-A2 and 3G3MV-AB : 3-phase 200 to
230 VAC
W/T3 3G3MV-A4 : 3-phase 380 to 460 VAC
B1 Braking Resistor Terminals for attaching an external Braking Resistor
connection or a Braking Resistor Unit. (Connect to detect
B2 terminals overvoltage during braking.)
+1 Connection Connect the DC reactor for suppressing harmonics
terminals+1 and to terminals+1 and +2.
+2 +2: When driving the Inverter with DC power, input
DC reactor the DC power to terminals +1 and -.
connection (Terminal +1 is a positive terminal.)
- terminals
+1 and -:
DC power supply
input terminals
Ground terminal Be sure to ground the terminal under the following
conditions.
3G3MV-A2 : Ground at a resistance of 100 or
less.
3G3MV-AB : Ground at a resistance of 100 or
less.
3G3MV-A4 : Ground at a resistance of 10 or
less.
To conform to EC Directives, connect to the neutral
point of the power supply.
Note Be sure to connect the ground terminal
directly to the
motor frame ground.
Note 1. Connect single-phase input to both the R/L1 terminal and the S/L2 terminal.
Note 2. The maximum voltage at the output sides corresponds to the power supply
voltage for Inverter input.
18
Design Chapter 2
19
Design Chapter 2
20
Design Section 2
Switches SW1 and SW2, both of which are located above the control circuit
terminals, are used for input method selection. Remove the front cover and
optional cover to use these switches.
21
Design Section 2
Selecting RS-422/485 Termination Resistance
Termination resistance can be selected by setting pin 1 of the SW2 to ON. The
default setting for the pin is OFF.
SW2
Communications Pin 1
method setting
RS-422 Set to ON
RS-485 Set to ON only if the Unit is the end
Slave
S+
S-
R+
R-
By using pin 2 of SW2, voltage input or current input can be selected as the input
method for frequency reference. The default setting is for current input.
Parameter settings are required together with the selection of the frequency
reference input method.
Note Do not set pin 2 to ON for current input while voltage input is ON, otherwise the
resistor in their input circuit may burn out.
22
Design Section 2
Note Connect single-phase 200VAC to terminals R/L1 and S/L2 of the 3G3MV-
AB .
Note Set parameter 052 to forward/reverse rotation command 0 for 3-wire sequence
input.
23
Design Section 2
For the main circuit and ground, always use 600-V polyvinyl chloride (PVC) cables.
If any is long and may cause voltage drops, increase the wire size according to the
cable length.
24
Design Section 2
25
Design Section 2
size breaker
(mm) capacito
r (A)
A4001 R/L1, S/L2, T/L3, B1, B2, M4 1.2 2 to 5.5 2 5
-, +1, +2, U/T1, V/T2,
W/T3
Choose an MCCB with a capacity of 1.5 to 2 times the Inverters rated current. For
the MCCBs time characteristics, be sure to consider Inverte the Inverters overload
Powe
protection (oneMCCB r
minute at 150% of the rated output current).
r
If the MCCB is to be used in common among multiple Inverters,
R/L1 or other devices,
set up asuppl
sequence such that the power supply will be turned OFF by a fault output,
3-phase/y in the following S/L
as shown diagram.
single- 2
T/L3
phase
200 VAC *
3-phase
400VAC MB
OFF ON Fault output
MC (NC)
26
Design Section 2
For the special-purpose breaker for Inverter, choose a ground fault interrupter with
a sensitivity amperage of at least 10 mA per Inverter.
When using a general leakage breaker, choose a ground fault interrupter with a
sensitivity amperage of 200 mA or more per Inverter and with an operating
time of 0.1 s or more.
If the power supply of the main circuit is to be shut off because of the
sequence, a magnetic contactor can be used instead of a molded-case
circuit breaker.
When a magnetic contactor is installed on the primary side of the main
circuit to stop a load forcibly, however, the regenerative braking does not
work and the load coasts to a stop.
A load can be started and stopped by opening and closing the magnetic contactor
on the primary side. Frequently opening and closing the magnetic contactor,
however, may cause the Inverter to break down.
When the Inverter is operated with the Digital Operator, automatic operation
cannot be performed after recovery from a power interruption.
When using the Braking Resistor Unit, be sure to arrange a sequence in which the
thermal relay of the Unit turns the magnetic contactor OFF.
27
Design Section 2
Installing an AC Reactor
Install a Noise Filter to eliminate noise transmitted between the power line
and the Inverter.
Wiring Example 1
Power supply MCCB 3G3IV-PHF 3G3MV
Noise SYSDRIVE M
Filter
MCCB
Programma
ble
Controller
Other controllers
Wiring Example 2
28
Design Section 2
Note Do not use any general-purpose noise filter. No general-purpose noise filter can
effectively suppress noise generated from the Inverter
Connect output terminal U/T1, V/T2, and W/T3 to motor lead wires U, V,
and W.
Check that the motor rotates forward command. Switch over any two of the
output terminals to each other and reconnect if the motor rotates in
reverse with the forward command.
Never connect a power supply to output terminals U/T1, V/T2, and W/T3.
If voltage is applied to the output terminals, the internal circuit of the
Inverter will be damaged.
If the output terminals are touched with bare hands or the output wires
come into contact with the Inverter casing, an electric shock or grounding
will occur. This is extremely hazardous.
Also, be careful not to shock the output wires.
29
Design Section 2
Connect a Noise Filter to the output side of the Inverter to reduce radio
noise and induction noise.
SYSDRIVE Noise M
Filter
Radio Noise : Electromagnetic waves from the Inverter and cables cause
the broadcasting radio
receive to make noise.
30
Design Section 2
30 cm min.
Signal line
Controll
er
Radio noise is generated from the Inverter as well as the input and output
lines. To reduce radio noise, install Noise Filter on both input and output
sides, and also install the Inverter in a totally enclosed steel box.
The cable between the Inverter and the motor should be as short as
possible.
Steel box
If the cable between the Inverter and the motor is long, the high-frequency
leakage current will increase, causing the Inverter output current to
increase as well. This may affect peripheral devices.
To prevent this, adjust the carrier frequency (set in n080) as shown in the
table below.
For details, refer to the parameter settings.
31
Design Section 2
Carrier 10 kHz max. 5 kHz max. 2.5 kHz max.
frequency
Ground Wiring
Always use the ground terminal of the 200-V Inverter with a ground resistance of
100 or less.
Similarly, always use the ground terminal of the 400-V Inverter with a ground
resistance of 10 or less.
Do not share the ground wire with other devices such as welding machines or
power tools.
Always use a ground wire that complies with technical standards on electrical
equipment and minimize the length of the ground wire.
Leakage current flows through the Inverter. Therefore, if the distance between the
ground electrode and the ground terminal is too long, the potential on the ground
terminal of the Inverter will become unstable.
When using more than one Inverter, be careful not to loop the ground wire.
32
Design Section 2
The Ministry of International Trade and Industry provided some guidelines
in September 1994 for the suppression of harmonics from electrical
household appliances and electrical equipment in Japan. Since then, the
problem has been drawing considerable attention.
Refer to the following information for the definition of harmonics (i.e.,
harmonic currents with voltages) and countermeasures against the
generation of harmonics from the Inverter.
Harmonics
Definition
Harmonics consist of electric power produced from AC power and
alternating at frequencies that are integral multiples of the frequency of the AC
power.
The following frequencies are harmonics of a 60- or 50-Hz commercial
power supply.
Second harmonic: 120 (100) Hz
Third harmonic: 180 (150) Hz
33
Design Section 2
DC voltage is obtained by converting AC voltage into a pulsating one-side
voltage with rectifiers and smoothing the pulsating one-side voltage with
capacitors. Such AC current, however, contains harmonics.
Inverter
The Inverter as well as normal electric machines has an input current
containing harmonics because the Inverter converts AC into DC. The output
current of the Inverter is comparatively high. Therefore, the ratio of
harmonics in the output current of the Inverter is higher than that of any
other electric machine.
Voltage
Time
Voltage Rectified
Time
Voltage Smoothed
Time
Current
DC/AC Reactor
The DC reactor and the AC reactor suppress harmonics and currents that
change suddenly and greatly.
The DC reactor suppresses harmonics better than the AC reactor. The DC
reactor used with the AC reactor suppresses harmonics more effectively.
The input power factor of the Inverter is improved by suppressing the
harmonics of the input current of the Inverter
Connection
Connect the DC reactor to the internal DC power supply of the Inverter
after shutting OFF the power supply to the Inverter and making sure that
the change indicator of the Inverter turns OFF.
Do not touch the internal circuitry of the Inverter in operation, otherwise an
electric shock or burn injury may occur.
Wiring Method
[With DC Reactor]
34
Design Section 2
DC
reactor
(optional
Power MCCB )
suppl
R/L1 U/T1
y
S/L V/T2 M
2
3-phase 200 T/L3 W/T3
VAC,
SYSDRIVE
single-phase
3G3MV
200 VAC, or
3-phase 400
VAC
Reactor Effects
Harmonics are effectively suppressed when the DC reactor is used with the
AC reactor as shown in the following table.
35
Design Section 2
capacity of the Inverter. In this case, use a Braking Resistor or a Braking
Resistor Unit.
Note 1. When using a Braking Resistor, install a thermal relay to monitor the
temperature of the resistor.
Note 2. When using a Braking Resistor or a Braking Resistor Unit, be sure to include a
sequence whereby the power supply for the Inverter will be turned OFF in
the case of abnormal overheating. Not doing so may result in burning.
Braking Resistor: Use the output of the thermal relay used to monitor the
temperature of the
thermometer.
Braking Resistor Unit: Use the error contact output of the Braking Resistor Unit.
36
Design Section 2
37
Design Section 2
38
Design Section 2
39
Design Section 2
40
Design Section 2
41
Design Section 2
When using a Braking Resistor, be sure to set n902 (deceleration stall prevention
selection) to 1 (without deceleration stall prevent).
Invert
Powe MCCB XA er
r R/L1
suppl S/L2
y
T/L3
3-phase, 200 VAC (single- B1 B
phase) 2
Braking
200 VAC/3-phase 200 VAC)
(P (B) Resistor/Braki
XB OFF ON ) ng
XA (1 x (2 Resistor Unit
) )
SA
XB
SA
Note Do not use resistance less than the minimum connection resistance value.
Doing so may damage the Inverter.
42
Design Section 2
Inverter Braking Braking Resistor
3G3MV- Resistor Unit Minimum
(3% usage rate (10% usage rate Connecti
ED) ED) on
3G3IV- 3G3IV-
resistanc
e
A4002 PERF150WJ715 PLKEB40P7 (750, 70 750
A4004 (750) W)
A4007 510
A4015 PERF150WJ401 PLKEB41P5 (400, 260 240
(400) W)
A4022 PERF150WJ301 PLKEB42P2 (250, 260 200
(300) W)
A4037 PERF150WJ401 PLKEB43P7 (150, 390 100
(400) X 2 W)
Note Do not use resistances less than than the minimum connection resistance
value.
Doing so may damage the Inverter.
Wire the control input terminals (S1 to S7 and SC), the multi- function
contact output terminals (MA, MB, and MC) and the multi-function
photocoupler output terminals (P1, P2, PC) as described below.
Wire Used
Note When using the following solderless terminal, make sure that the wire size is
1.0
0.5 mm.
dia
43
2.6 (Size:
Design Section 2
Wiring Method
1. Loosen the terminal screws with a thin-slotted screwdriver.
Note 1. Always separate the control signal line from the main circuit cables and
other power cables.
Note 2. Do not solder the wires to the control circuit terminals. The wires may not
contact well with the
control circuit terminals if the wires are soldered.
Note 3. The end of each wire connected to the control circuit terminals must be
stripped for
approximately 5.5 mm.
Thin-slotted Control
screwdriver circuit
terminal
block
Wires Used
44
Design Section 2
Use shielded, twisted-pair wires for wiring in order to prevent the Inverter
from mal-functioning due to noise.
Note Make sure that the wire size is 0.5 mm when using the following solderless
terminal.
1.0
dia
2.6 (Size:
dia mm)
Wiring Method
The wiring method for the frequency reference input terminals is the same as that
of the
control I/O terminals.
Always separate the control signal line from the main circuit cables and other
power cables.
Connect the shield to the ground terminal of the Inverter. Do not connect the
shield to the load.
Cover the shield with tape so that the shield will not come into contact with other
signal wires or
machines.
45
Design Section 2
The following description provides the wiring method of the Inverter to
meet DC Directive requirements. If the following requirements are not
satisfied, the whole equipment incorporating the Inverter will need further
confirmation.
Standard Connection
Conforming to EC Directives
46
Design Section 2
Make sure that the Inverter and Noise Filter are grounded together.
Always connect the power input terminals (R/L1, S/l2, and T/L3) and power supply
via a dedicated
Noise Filter.
Reduce the length of the ground wire as much as possible.
Locate the Noise Filter as close as possible to the Inverter. Make sure that the
cable length between
the Noise Filter and the Inverter does not exceed 40 cm.
The following Noise Filter are available.
??? Please provide information on rasumi sei in the following three tables.
Product Model
Manufacturer
Clamp Filter ZCAT3035-1330 TDK
47
Design Section 2
Cable
Ground clamp
plate
Cabl
e
Shiel
d
Conforming to LVD
Always connect the Inverter and power supply via molded case circuit breaker
(MCCB) suitable to the Inverter for protecting the Inverter from damage that may
result from short-circuiting.
Use one MCCB per Inverter.
Select a suitable MCCB from the following table.
200-V Models
48
Design Section 2
400-V Models
Note To satisfy LVD requirements, the Inverter must be protected with a line breaker
in case a short- circuiting accident occurs. When using a single line breaker to be
shared with other Inverters or devices, make sure that the Inverters and devices
will be fully protected if there is a one-point short-circuit, otherwise the Inverters
and devices may be damaged.
The frequency reference power supply (FS) of the Inverter is of basic insulation
construction. When connecting the Inverter to peripheral devices, be sure to
increase the degree of insulation.
49