Pws 002863
Pws 002863
Ovation Controller
Model OCR1100
Features
Secure, reliable and mission-critical control
capability providing bumpless automatic failover
between redundant controllers.
Fast processor for increased productivity
One-step data acquisition functionality through the
definition of the I/O database
Small footprint with low power requirements and
fanless operation
Interfaces to Ovation and WDPF I/O, both local and
remote
Integral interface to digital busses through Ovation
I/O modules
Integrated virtual I/O capability for third-party OEM
systems over Ethernet protocols.
Non-volatile storage of application software, point
Redundant Ovation controller model OCR1100 shown with four
database, configuration information, and operating local Ovation I/O modules installed on two I/O branches.
tuning constants
Integrated sequence of events capability with 1
millisecond resolution
Meets IEC 61131-3 standards
Achilles Level 1 certified
Page - 1
PWS_002863 [27]
Ovation Controller Model OCR1100 Data Sheet
Process point sensor/limit checking In addition to the higher resolution time tags,
Process point alarm processing sequence-of-events points may be used in control
schemes like any other I/O point, including limit
Process point conversion to engineering units
checking and alarming.
Process point database storage
Local and remote I/O interface Alarm Processing
Process point tagout
The OCR1100 processes limits and alarms based on
each process points database definition. These
Standard Functions functions are performed regardless of whether the
point is scanned for input to a control loop or for data
acquisition separate from control functions. The alarm
Control Execution status of each point in the controller is updated with
The Ovation OCR1100 controller, with an Intel-based each scan. The status may indicate whether a point
processor, is capable of simultaneously executing as value has:
many as five process control tasks at loop speeds Exceeded the range of the sensor
ranging from 10 milliseconds to 30 seconds. Each Exceeded the user-defined limits
control task is comprised of the I/O process point input Changed state
scan, control scheme execution and an output scan. Passed an incremental limit
Two of the control tasks use predefined loops speeds
of one-second and 100 milliseconds. The other three
control tasks can have user-selectable loop speeds. Alarm reporting can be delayed on a per-point basis by
Individual control sheets assigned to an available task a user-specified period.
coordinate the control execution loop time with the
appropriate control function. Advanced diagnostics When coupled with a workstation, the Ovation
visible on Ovation HMI graphics indicate control task OCR1100 controller has the capability to report six
loop times for configured, average, worst case and independent alarm thresholds defined as:
standard deviation. Four high limits
User-defined high limit
Control Scheme Highest plus incremental limits
Page - 2
PWS_002863 [27]
Ovation Controller Model OCR1100 Data Sheet
Page - 3
PWS_002863 [27]
Ovation Controller Model OCR1100 Data Sheet
malfunction. A full range of events can trigger provides some basic routing functions and offers
automatic failover, including: general resource management within the controller.
Control processor failure
Network controller failure Hardware
I/O interface failure
The Ovation OCR1100 controller is built to open
Removal of power from the control processor industry standards using Intel processors and
Control processor reset CompactPCI bus technology. Newer technologies can
be easily incorporated while protecting the initial
Once control is passed to the backup processor, the Ovation controller software investment.
failed processor may be powered down, repaired and
powered back up with no harmful effects on the This foundation provides the portability such that
executing control strategy. Ovation controller software can be run on other
available platforms and operating systems. The
Upon restart, the repaired processor will detect that its Ovation virtual controller used in Ovation simulator
partner is in control and assume the backup role. The systems runs the standard Windows operating system
processor in control will detect the presence of the on standard PC hardware and does not require actual
backup processor and adjust for redundant operation. I/O interfaces.
Page - 4
PWS_002863 [27]
Ovation Controller Model OCR1100 Data Sheet
Like the controller, the I/O system continues to evolve, 61131 directly relates to the standard programming
including support for increased channel capacity languages recommended to conform to this standard.
modules. Refer to the controller hardware manual and
the I/O reference manual for additional details on the The IEC 61131 standard specifies the syntax and
available models, capacities, module capabilities and semantics of a unified suite of programming
termination types. languages, including the software model and a
structuring language. The standard can be
summarized and described under two main categories:
Ovation Controller Cabinets Common Elements and Programming Languages.
Ovation controllers and I/O modules are all DIN rail Refer to the Ovation Compliance to IEC 61131-3 data
mountable, providing the flexibility to match controller sheet for detailed information Ovations adherence to
layouts with process requirements for various this international standard.
locations, environments and space availability. The
normal configuration is to mount DIN rail items on
plates which can then be installed in existing or new
Achilles Certified
cabinet enclosures. Top and bottom entry for I/O Achilles Communications Certification provides an
cables is available to meet required specifications. industry-leading benchmark for the secure
development of the applications, devices and systems
A variety of controller and I/O cabinet configurations found in critical infrastructure. The certification process
are available. The basic controller cabinet houses a is designed to assess the network robustness of
chassis for single or redundant controllers and two I/O industrial devices and certify that they meet a
branches on the front of the plate. Mounted on the rear comprehensive set of requirements. It provides device
of the plate is a redundant power supply, power manufacturers with an independently verified result to
distribution module and two additional I/O branches for communicate their product security to customers, while
a total of 32 I/O modules since each I/O branch can providing the operators of control systems with the
hold up to eight I/O modules. most complete, accurate and trustworthy information
possible about the network resilience of their deployed
Expansion cabinets house up to an additional 32 I/O products.
modules in four branches and a transition panel for
connection to the controllers. It can also provide The Ovation OCR1100 controller complies with the
additional space for mounting redundant power requirements set forth by Achilles Level 1 certification.
supplies (when required), and a power distribution
module.
Summary
Ovations standard cabinet structure is front and rear The Ovation system is renowned for delivering
access, but can be provided with front access only. precision control with outstanding performance. That
Other custom or OEM cabinet enclosures are precision begins with the Ovation controller that
optionally available to accommodate specific provides full-redundancy to assure the reliability and
requirements for plate sizes, cabinet sizes, security necessary for even the most demanding
construction materials, environmental ratings, cabinet application. The Ovation controller executes simple or
interior and exterior accessories, termination options complex modulating and sequential control strategies,
and marshaling cabinets. performing data acquisition functions and incorporating
full bumpless redundancy for mission critical
IEC 61131-3 Compliant applications. The controller provides the capabilities to
control a variety of applications in an adaptable,
The International Electrotechnical Committee of the flexible and cost-effective manner. With industry-
ISO organization created a set of standards to achieve standard hardware and software platforms, the
uniform mechanisms to configure and program control controller is easy to upgrade throughout a plant
systems from different vendors. Part 3 of the IEC lifecycle. These features make the Ovation controller
one of the most powerful in the industry.
Page - 5
PWS_002863 [27]
Ovation Controller Model OCR1100 Data Sheet
Item Capability
Two of the 5 tasks are predefined @ 1 s and @ 100 ms. The other three tasks are
Control task loop execution time user definable, with each task individually defined to execute at a rate between 10
ms. and 30 seconds in increments of 10 ms.
4 x 10/100 Mb Ethernet
NIC ports
Three options: (i) 4 x RJ45, (ii) 1 x RJ45 + 3 SFP Fiber or (iii) 4 x RJ45
0 - 60 C; 32 - 140 F
Temperature
0 - 50 C; 32 - 122 F
(Refer to (i) and (ii) above)
0 - 60 C; 32 - 140 F
Humidity 0 - 95% RH
Size 20 w x 8 h x 7 d
OCR1100 only
BootROM OCR1100 only
OCR400 replacement / OCR1100
Page - 6
PWS_002863 [27]
Ovation Controller Model OCR1100 Data Sheet
Item Capability
(h x w x d) (h x w x d)
Size 79 x 24 x 24 in 79 x 24 x 24 in
2006.6 x 609.6 x 609.6 mm 2006.6 x 609.6 x 609.6 mm
426.25 lbs. 396.25 lbs.
Weight (fully configured)
191.81 kg. 178.31 kg.
0-50 C; 32-122 F
(i) 4x RJ45 ports
Operating ambient temperature
0-60 C; 32-140 F
(Refer to NIC Ports above)
0-40 C; 32-104 F
(ii) 1 RJ45, 3x SFP ports
Storage ambient temperature -40 to 70 C; -40-158 F -40 to 70 C; -40-158 F
0 - 95% 0 - 95%
Operating humidity
Non-condensing Non-condensing
0 - 95% 0 - 95%
Storage humidity
Non-condensing Non-condensing
Redundant controllers, Space for spare equipment,
Capacity 32 I/O modules, 32 I/O modules,
2 power supplies 2 power supplies
2017 Emerson. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Ovation is a mark of one of the Emerson Automation Solutions family
of business units. All other marks are the property of their respective owners. The contents of this publication are presented for information purposes only, and while effort has been made
to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All
sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without
notice.
Page - 7
PWS_002863 [27]