Climatic Loading
Conductor & Earth Wire
V= 56 (m/sec) Conductor
V= 61.6 (m/sec) Earth Wire(V*1.1)
q0= 0.5*0.12*V2 Condcutor
= 188.16 (kg/m2)
q0= 0.5*0.12*V2 Earth Wire
= 227.67 (kg/m2)
(H/10)1/n n=5
H= Conductor average height and earthwire height
Hc= 41.2 (m)
He= 43.45 (m)
c 1.33
e 1.34
Cf= Force coefficient
Condcutor Diameter 29.56 mm
Earth Wire Diameter 12 mm
Numper of conductor per phase 4
Dia. Nos Dia. Nos Dia. Nos.
Construction of Conductor: Al 4.9 18 4.9 12 ST 3.2 7
Conductor Diameter/Total Diamater
= 0.174
Cf= 1.05 (0.1666< Conductor Diameter/Total Diamater)
1 (0.1666> Conductor Diameter/Total Diamater>0.125)
0.95 (0.125>Conductor Diameter/Total Diamater)
K1= 1 (1=Land portion. 1.15=River Crossing portion)
Fc= 236
Fe= 320
CD= 0.9
Insulator
H= Insulator average heigh
Hc= 41.2 (m)
c 1.33
K1= 1 (1=Land portion. 1.15=River Crossing portion)
Cf= 1.4
Fi= 350
Design Load Calculation for Tower Type 2DLQ [ Unit : N ]
Case -1,: Normal Condition ( 0 Wind Condition
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) +200kg 0.6900 x 760 x 9.80665 + 1961 7,104
V2 =(Arrester Wire weight) x (Vertical Span)+200kg 0.6900 x 760 x 9.80665 + 1961 7,104
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0000 x 760 x 4 x 9.80665 59,624
+ (Insulator strings weight)+200kg 358 x 9.80665 + 1961 5,472
V3 (Total) 65,096
-7- EDL-GMP-TL-110-101
Design Load Calculation for Tower Type 2DLQ [ Unit : N ]
Case -4 : Broken Condition (Transverse Wind Condition)
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.6900 x 570 x 9.80665 3,857
V2 =(Arrester Wire weight) x (Vertical Span) 0.6900 x 570 x 9.80665 3,857
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0000 x 570 x 4 x 9.80665 44,718
+ (Insulator Strings weight) 358 x 9.80665 3,511
V3 (Total) 48,229
-8- EDL-GMP-TL-110-101
Design Load Calculation for Tower Type 2DLQ [ Unit : N ]
-7- EDL-GMP-TL-110-101
Design Load Calculation for Tower Type 2DLQ [ Unit : N ]
Case -7 : Construction and Maintenance
Vertical Loads (Dead Weight Loads)
V1 =(OPGW weight) x (Vertical Span) 0.6900 x 988 x 9.80665 + 1961 8,646
V2 =(Arrester Wire weight) x (Vertical Span) 0.6900 x 988 x 9.80665 + 1961 8,646
V3 = (Conductor weight) x (Vertical Span) x (No. of Cond.) 2.0000 x 988 x 4 x 9.80665 77,512
+ (Insulator Strings weight) 358 x 9.80665 + 1961 5,472
V3 (Total) 82,984
-8- EDL-GMP-TL-110-101
( 3.179 ( 3.179 ) ( 3.179 ) ( 3.179 ) ( 3.179 ) ( 3.179 )
7.104 7.104 7.104 7.104 7.104 7.104
DW
DW
PGCB-230kV Hatahzari - Sikalbaha
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design
Design Load
Load Diagram
Diagram for
for Tower
Tower Type
Type 2DLQ
2DLQ (1/6)
(1/6)
( 0.880 ) ( 3.179 ) ( 3.179 ) ( 3.179 )
3.857 7.104 7.104 7.104
DW
Case 7 Case 8
PGCB-230kV Hatahzari - Sikalbaha
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design
Design Load
Load Diagram
Diagram for
for Tower
Tower Type
Type 2DLQ
2DLQ (3/6)
(3/6)
0.000 0.000 0.000 0.000 0.000 0.000
DW
PGCB-230kV Hatahzari - Sikalbaha
Case 9 Case 10
High Intensity Condition High Intensity Condition
45 Wind 90 Wind
O.L.F=2.0 O.L.F=2.0
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower Design
Design Load
Load Diagram
Diagram for
for Tower
Tower Type
Type 2DLQ
2DLQ (4/6)
(4/6)
( 3.179 ) ( 3.179 ) ( 3.179 ) ( 3.179 ) ( 3.179 ) ( 3.179 )
8.646 8.646 8.646 8.646 8.646 8.646
DW
DW
DW
Case 11 Case 12 Case 13
PGCB-230kV Hatahzari - Sikalbaha
Note
All Loads are in kN
All longitudinal loads are in the same direction
Factor of safety are not included
DW : Dead weight of tower
Design
Design Load
Load Diagram
Diagram for
for Tower
Tower Type
Type 2DLQ
2DLQ (5/6)
(5/6)
LOAD CASE SYMBOL
Case 6 NORMAL CONDITION (TRANSVERSE WIND =90o) SINGLE CIRCUIT (LEFT ARM)
Case 7 NORMAL CONDITION (OBLIQUE WIND =60o) SINGLE CIRCUIT (LEFT ARM)
Case 8 NORMAL CONDITION (LONGITUDINAL WIND =0o) SINGLE CIRCUIT (LEFT ARM)
Case 9 BROKEN WIRE CONDITION (TRANSVERSE WIND =90 o) SINGLE CIRCUIT (LEFT ARM)
9-1 ONE EARTHWIRE + ONE TOP CONDUCTOR
9-2 ONE EARTHWIRE + ONE MIDDLE CONDUCTOR
9-3 ONE EARTHWIRE + ONE BOTTOM CONDUCTOR
9-4 ONE TOP CONDUCTOR + ONE MIDDLE CONDUCTOR
9-5 ONE TOP CONDUCTOR + ONE BOTTOM CONDUCTOR
9-6 ONE TOP MIDDLE CONDUCTOR + ONE BOTTOM CONDUCTOR
Case 10 BROKEN WIRE CONDITION (LONGITUDINAL WIND =0 o) SINGLE CIRCUIT (LEFT ARM)
10-1 ONE EARTHWIRE + ONE TOP CONDUCTOR
10-2 ONE EARTHWIRE + ONE MIDDLE CONDUCTOR
10-3 ONE EARTHWIRE + ONE BOTTOM CONDUCTOR
10-4 ONE TOP CONDUCTOR + ONE MIDDLE CONDUCTOR
10-5 ONE TOP CONDUCTOR + ONE BOTTOM CONDUCTOR
10-6 ONE TOP MIDDLE CONDUCTOR + ONE BOTTOM CONDUCTOR
Case 11 NORMAL CONDITION (TRANSVERSE WIND =90o) SINGLE CIRCUIT (RIGHT ARM)
Case 12 NORMAL CONDITION (OBLIQUE WIND =60o) SINGLE CIRCUIT (RIGHT ARM)
Case 13 NORMAL CONDITION (LONGITUDINAL WIND =0o) SINGLE CIRCUIT (RIGHT ARM)
Case 14 BROKEN WIRE CONDITION (TRANSVERSE WIND =90 o) SINGLE CIRCUIT (RIGHT ARM)
14-1 ONE EARTHWIRE + ONE TOP CONDUCTOR
14-2 ONE EARTHWIRE + ONE MIDDLE CONDUCTOR
14-3 ONE EARTHWIRE + ONE BOTTOM CONDUCTOR
14-4 ONE TOP CONDUCTOR + ONE MIDDLE CONDUCTOR
14-5 ONE TOP CONDUCTOR + ONE BOTTOM CONDUCTOR
14-6 ONE TOP MIDDLE CONDUCTOR + ONE BOTTOM CONDUCTOR
Case 15 BROKEN WIRE CONDITION (LONGITUDINAL WIND =0 o) SINGLE CIRCUIT (RIGHT ARM)
15-1 ONE EARTHWIRE + ONE TOP CONDUCTOR
15-2 ONE EARTHWIRE + ONE MIDDLE CONDUCTOR
15-3 ONE EARTHWIRE + ONE BOTTOM CONDUCTOR
15-4 ONE TOP CONDUCTOR + ONE MIDDLE CONDUCTOR