DC System
DC System
1 Wrtsil
DC System
Chargers
Batteries
Nickel-Cadmium cells
2 Wrtsil
DC System
3 Wrtsil
DC System
Battery
110V 75Ah/ 10h
Battery
Main switch
4 Wrtsil
DC System
5 Wrtsil
DC System
6 Wrtsil
DC System
Factory set configuration
Operation actions
Normally, all actions related to operation are carried out automatically.
Manual actions are required only during preventive maintenance and
when replacing a faulty rectifier.
In principle, the preventive maintenance covers only inspection and
adjustment of output and alarm levels.
load ability
over voltage protection
current limit
no load alarm
mains fault alarm
8 Wrtsil
DC System
9 Wrtsil
DC System
10 Wrtsil
DC System
11 Wrtsil
DC System
12 Wrtsil
DC System
13 Wrtsil
DC System
14 Wrtsil
DC System
Internal faults in the rectifier cannot be repaired on site, thus the entire
rectifier module is replaced.
The following instructions are intended to help trace possible faults
outside the rectifier, and to ensure that the rectifier really is
malfunctioning. Fault tracing is based on the indicator lights of the
rectifier.
The rectifier will not start and the PWR indicator lamp is turned off:
Check that the mains cable is connected, mains switch turned on and
mains power operating.
If no other indicator lamps are active and above mentioned factors have
been checked, the rectifier is faulty.
15 Wrtsil
DC System
16 Wrtsil
DC System
Standard sizes
Nickel-Cadmium cells
17 Wrtsil
DC System
19 Wrtsil
DC System
1.2 Assembly
For assembly operations, use insulated tools.
It is recommended to protect yourself by wearing insulating gloves,
and to remove any metal object such as watches or any other items
of jewellery, especially in case of installation in a cabinet.
Moderately lubricate the inserts and connections using silicone
grease. The use of petroleum-based lubricant is not recommended.
The connections should be tightened by means of a torque wrench,
set to the following:
M5 connections: 2,5 +/- 1 Nm
M6 connections: 7 +/- 1 Nm
M8 connections: 11 +/- 1 Nm
M12 connections: 25 +/- 1 Nm
Check the overall battery voltage: it should be consistent with the
number of series connected cells.
20 Wrtsil
DC System
1.3 Commissioning
The charging voltage should be adjusted in accordance with the
specification of the batteries.
The safety system: fuses, circuit-breakers and voltage relays for
battery isolation, are all tested independently.
If a contractual endurance test is required, it is recommended initially,
to maintain the batteries under floating voltage for 4 to 5 days. This
will make up for the losses induced by storage, and improve the
equalization of the cells or monoblocks (for 3 month storage period at
20 C).
21 Wrtsil
DC System
23 Wrtsil
DC System
3. Charging Conditions
The constant-voltage charging mode with limited current is the most
appropriate to preserve a very long service life to the batteries.
The table below give an informative value of the time required to
recharge a battery under 2,27 V/cell or 2,40 V/cell at 20 C (2,25
V/cell or 2,38 V/cell at 25 C) according to its state of discharge and
to the initial current limit.
A recharge with current values higher than those mentioned does not
save much time, and could damage the battery.
The recharges performed at voltages higher than 2,27 V/cell shall be
limited in time.
24 Wrtsil
DC System
25 Wrtsil