Current Transformer Test Circuitficate
Current Transformer Test Circuitficate
% Burden Phase Current Err. Burden Phase Current Err. P.D. Test
S/N Core Primary Secondary % VA Err. %F VA Err. %F 43.2 kV ( pC ) 24.9 kV ( pC )
13/9288 1S1-1S2 300 5
1 2,50 6 0,21 10 12 -0,01 19 7
5 " 5 0,19 " 9 -0,02
20 " 3 0,16 " 4 0,01
100 " 2 0,16 " 6 -0,08
120 " 2 0,15 " 6 -0,06
1S1-1S3 600 5
1 5,00 2 0,09 20 5 0,01
5 " 2 0,08 " 3 0,01 CAPACTVE VOLTAGE
20 " 1 0,07 " 1 0,02 4,3 kV
100 " 1 0,08 " 1 0,04
120 " 1 0,08 " 1 0,02
2S1-2S2 300 5
100 10 4 0,61
120 " 4 0,61
2S1-2S3 600 5
100 20 2 0,30
120 " 2 0,30
100
120
Test Date : 10.06.2013 Tester : Soner TUTKUN Approval
Making deliveries of goods is ratified with test certificate according to agreement about quality control ,quarentee condition and product responsibility.
F69 / 00 / 26.03.2010
CURRENT TRANSFORMER TEST CERTIFICATE
Ratio : Type : Client : ABB ELK. P.F. Test ( 60 sec. )
300-600 / 5 - 5 A CTB 30-A Prim --> Earth Prim--> Prim Sec-->Earth Sec-->Sec.
Project Order No : 70 kV - 3 kV 3 kV
Fab.Nr. 13/9289 IEC 60044-1/2003 Customer Protect No Customer Order No
Ith 16 k A (1s) Idyn : kV 36/70/170 1YTU120108L0514 OK OK OK OK
F ( Hz ) 50 Is Cl E
ACC. Over
Core Primary Sec. VA Class Cur. Fact.
1S1-1S2 300 5 10 0,2s Fs5
1S1-1S3 600 5 20 0,2s Fs5
2S1-2S2 300 5 10 5P 10
2S1-2S3 600 5 20 5P 10
% Burden Phase Current Err. Burden Phase Current Err. P.D. Test
S/N Core Primary Secondary % VA Err. %F VA Err. %F 43.2 kV ( pC ) 24.9 kV ( pC )
13/9289 1S1-1S2 300 5
1 2,50 2 0,20 10 20 -0,21 19 8
5 " 9 0,16 " 10 -0,17
20 " 5 0,12 " 7 -0,10
100 " 3 0,13 " 4 -0,04
120 " 3 0,13 " 4 -0,04
1S1-1S3 600 5
1 5,00 4 0,06 20 8 -0,11
5 " 3 0,04 " 3 -0,07 CAPACTVE VOLTAGE
20 " 1 0,06 " 0 0,00 3,9 kV
100 " 0 0,07 " 1 -0,01
120 " 0 0,07 " 1 -0,01
2S1-2S2 300 5
100 10 6 0,63
120 " 6 0,63
2S1-2S3 600 5
100 20 3 0,33
120 " 3 0,33
100
120
Test Date : 10.06.2013 Tester : Soner TUTKUN Approval
Making deliveries of goods is ratified with test certificate according to agreement about quality control ,quarentee condition and product responsibility.
F69 / 00 / 26.03.2010
CURRENT TRANSFORMER TEST CERTIFICATE
Ratio : Type : Client : ABB ELK. P.F. Test ( 60 sec. )
300-600 / 5 - 5 A CTB 30-A Prim --> Earth Prim--> Prim Sec-->Earth Sec-->Sec.
Project Order No : 70 kV - 3 kV 3 kV
Fab.Nr. 13/9290 IEC 60044-1/2003 Customer Protect No Customer Order No
Ith 16 k A (1s) Idyn : kV 36/70/170 1YTU120108L0514 OK OK OK OK
F ( Hz ) 50 Is Cl E
ACC. Over
Core Primary Sec. VA Class Cur. Fact.
1S1-1S2 300 5 10 0,2s Fs5
1S1-1S3 600 5 20 0,2s Fs5
2S1-2S2 300 5 10 5P 10
2S1-2S3 600 5 20 5P 10
% Burden Phase Current Err. Burden Phase Current Err. P.D. Test
S/N Core Primary Secondary % VA Err. %F VA Err. %F 43.2 kV ( pC ) 24.9 kV ( pC )
13/9290 1S1-1S2 300 5
1 2,50 9 0,19 10 13 -0,06 17 6
5 " 7 0,15 " 8 -0,05
20 " 4 0,13 " 2 0,01
100 " 1 0,15 " 2 0,08
120 " 1 0,15 " 3 0,08
1S1-1S3 600 5
1 5,00 3 0,08 20 6 -0,01
5 " 2 0,07 " 4 -0,02 CAPACTVE VOLTAGE
20 " 1 0,07 " 1 0,01 4,1 kV
100 " 1 0,08 " 1 0,03
120 " 1 0,08 " 1 0,02
2S1-2S2 300 5
100 10 3 0,66
120 " 3 0,66
2S1-2S3 600 5
100 20 1 0,32
120 " 1 0,32
100
120
Test Date : 10.06.2013 Tester : Soner TUTKUN Approval
Making deliveries of goods is ratified with test certificate according to agreement about quality control ,quarentee condition and product responsibility.
F69 / 00 / 26.03.2010
CURRENT TRANSFORMER TEST CERTIFICATE
Ratio : Type : Client : ABB ELK. P.F. Test ( 60 sec. )
300-600 / 5 - 5 A CTB 30-A Prim --> Earth Prim--> Prim Sec-->Earth Sec-->Sec.
Project Order No : 70 kV - 3 kV 3 kV
Fab.Nr. 13/9291 IEC 60044-1/2003 Customer Protect No Customer Order No
Ith 16 k A (1s) Idyn : kV 36/70/170 1YTU120108L0514 OK OK OK OK
F ( Hz ) 50 Is Cl E
ACC. Over
Core Primary Sec. VA Class Cur. Fact.
1S1-1S2 300 5 10 0,2s Fs5
1S1-1S3 600 5 20 0,2s Fs5
2S1-2S2 300 5 10 5P 10
2S1-2S3 600 5 20 5P 10
% Burden Phase Current Err. Burden Phase Current Err. P.D. Test
S/N Core Primary Secondary % VA Err. %F VA Err. %F 43.2 kV ( pC ) 24.9 kV ( pC )
13/9291 1S1-1S2 300 5
1 2,50 9 0,19 10 13 -0,04 22 5
5 " 7 0,18 " 9 -0,04
20 " 8 0,15 " 5 -0,01
100 " 6 0,11 " 7 -0,10
120 " 6 0,11 " 6 -0,10
1S1-1S3 600 5
1 5,00 2 0,08 20 5 -0,02
5 " 2 0,07 " 3 -0,02 CAPACTVE VOLTAGE
20 " 2 0,06 " 1 -0,01 3,9 kV
100 " 1 0,06 " 1 0,01
120 " 1 0,05 " 1 -0,01
2S1-2S2 300 5
100 10 2 0,70
120 " 2 0,70
2S1-2S3 600 5
100 20 1 0,34
120 " 1 0,34
100
120
Test Date : 10.06.2013 Tester : Soner TUTKUN Approval
Making deliveries of goods is ratified with test certificate according to agreement about quality control ,quarentee condition and product responsibility.
F69 / 00 / 26.03.2010
CURRENT TRANSFORMER TEST CERTIFICATE
Ratio : Type : Client : ABB ELK. P.F. Test ( 60 sec. )
300-600 / 5 - 5 A CTB 30-A Prim --> Earth Prim--> Prim Sec-->Earth Sec-->Sec.
Project Order No : 70 kV - 3 kV 3 kV
Fab.Nr. 13/9292 IEC 60044-1/2003 Customer Protect No Customer Order No
Ith 16 k A (1s) Idyn : kV 36/70/170 1YTU120108L0514 OK OK OK OK
F ( Hz ) 50 Is Cl E
ACC. Over
Core Primary Sec. VA Class Cur. Fact.
1S1-1S2 300 5 10 0,2s Fs5
1S1-1S3 600 5 20 0,2s Fs5
2S1-2S2 300 5 10 5P 10
2S1-2S3 600 5 20 5P 10
% Burden Phase Current Err. Burden Phase Current Err. P.D. Test
S/N Core Primary Secondary % VA Err. %F VA Err. %F 43.2 kV ( pC ) 24.9 kV ( pC )
13/9292 1S1-1S2 300 5
1 2,50 7 0,21 10 2 -0,07 19 5
5 " 5 0,16 " 7 -0,06
20 " 3 0,15 " 4 -0,02
100 " 2 0,15 " 2 0,05
120 " 1 0,15 " 2 0,05
1S1-1S3 600 5
1 5,00 4 0,09 20 2 -0,01
5 " 3 0,08 " 5 -0,03 CAPACTVE VOLTAGE
20 " 1 0,07 " 2 0,00 3,6 kV
100 " 0 0,07 " 2 -0,01
120 " 0 0,07 " 2 -0,01
2S1-2S2 300 5
100 10 4 0,60
120 " 4 0,60
2S1-2S3 600 5
100 20 1 0,31
120 " 1 0,31
100
120
Test Date : 10.06.2013 Tester : Soner TUTKUN Approval
Making deliveries of goods is ratified with test certificate according to agreement about quality control ,quarentee condition and product responsibility.
F69 / 00 / 26.03.2010
CURRENT TRANSFORMER TEST CERTIFICATE
Ratio : Type : Client : ABB ELK. P.F. Test ( 60 sec. )
300-600 / 5 - 5 A CTB 30-A Prim --> Earth Prim--> Prim Sec-->Earth Sec-->Sec.
Project Order No : 70 kV - 3 kV 3 kV
Fab.Nr. 13/9293 IEC 60044-1/2003 Customer Protect No Customer Order No
Ith 16 k A (1s) Idyn : kV 36/70/170 1YTU120108L0514 OK OK OK OK
F ( Hz ) 50 Is Cl E
ACC. Over
Core Primary Sec. VA Class Cur. Fact.
1S1-1S2 300 5 10 0,2s Fs5
1S1-1S3 600 5 20 0,2s Fs5
2S1-2S2 300 5 10 5P 10
2S1-2S3 600 5 20 5P 10
% Burden Phase Current Err. Burden Phase Current Err. P.D. Test
S/N Core Primary Secondary % VA Err. %F VA Err. %F 43.2 kV ( pC ) 24.9 kV ( pC )
13/9293 1S1-1S2 300 5
1 2,50 9 0,14 10 8 -0,26 25 6
5 " 5 0,13 " 4 -0,11
20 " 3 0,11 " 1 -0,01
100 " 1 0,15 " 2 0,03
120 " 1 0,15 " 2 0,02
1S1-1S3 600 5
1 5,00 3 0,04 20 10 -0,10
5 " 3 0,04 " 4 -0,08 CAPACTVE VOLTAGE
20 " 2 0,05 " 2 -0,02 4,4 kV
100 " 1 0,07 " 1 0,03
120 " 1 0,07 " 1 0,03
2S1-2S2 300 5
100 10 2 0,67
120 " 2 0,67
2S1-2S3 600 5
100 20 1 0,33
120 " 1 0,33
100
120
Test Date : 10.06.2013 Tester : Soner TUTKUN Approval
Making deliveries of goods is ratified with test certificate according to agreement about quality control ,quarentee condition and product responsibility.
F69 / 00 / 26.03.2010
MAGNETIZATION CURVE
Type : CTB 30-A Rated voltage ( kV ) : 36 Current Voltage
100
10
1
1 10 100 1000 10000
Date 10.06.2013
MAGNETIZATION CURVE
Type : CTB 30-A Rated voltage ( kV ) : 36 Current Voltage
100
10
1
1 10 100 1000 10000
Date 10.06.2013