Overcurrent Protection Device Basis
Overcurrent Protection Device Basis
Selective Coordination
Enforcement:
Overcurrent Protective
Device Basics
by Tim Crnko
(AHJ), evaluating whether a system is selectively coor-
Merely having a higher ampere overcurrent protective dinated does not require as much knowledge or work.
device (OCPD) feeding a lower ampere overcurrent However, it does require specic information which can
protective device does not assure a circuit is selectively
coordinated. Designing a selectively coordinated sys- that must be provided for evaluation purposes depends
tem takes a knowledgeable person who is capable at the on the method used to achieve selective coordination.
task and who has the necessary data available to select
the proper devices. As an authority having jurisdiction interpretation for fuse or circuit breaker circuits used
IAEI NEWS July . August 2010 Reprinted by permission of IAEI News www.iaei.org
SELECTIVE COORDINATION ENFORCEMENT
2 www.iaei.org Reprinted by permission of IAEI News July . August 2010 IAEI NEWS
SELECTIVE COORDINATION ENFORCEMENT
Figure 3: Example to Evaluate Fuse Selective Coordination type of fuses. One fuse type may require only a 2:1 amp
1-600A
Class J - 2:1 2:1 8:1
Time-Delay
1-600A
Class RK1 - 2:1 2:1 8:1
Time-Delay
1-600A
Class RK5 - 1.5:1 1.5:1 2:1
Time-Delay
IAEI NEWS July . August 2010 Reprinted by permission of IAEI News www.iaei.org 3
rating ratio between a line-side fuse and a load-side fuse. (Time-current curves typically are not published for
If dierent types of fuses from the same manufacturer times less than 0.01 seconds.) It is simpler and more
are used line-side and load-side, then the ratio might be comprehensive to use the Fuse Selectivity Ampere Rat-
dierent, such as 3:1, 4:1, or 8:1. As with any method or ing Ratios method illustrated previously rather than
table, be sure to read any applicable notes or footnotes. interpreting time-current curves.
Each fuse manufacturer publishes a selectivity ratio In this example, use the fuse time-current curves in
SELECTIVE COORDINATION ENFORCEMENT
table specic to only their brands. Table 1 is for illustra- gure 4 to analyze selective coordination for the circuit
tive purposes and should not be used in actual studies. path with the three fuses shown. Examining gure 4,
there is no overlap of the fuses time-current curves.
Analysis for Figure 3 using Table 1 However, this does not mean that the fuses are selective-
Investigate the circuit for fuses 1, 2, and 3 in gure 3 us- ly coordinated for the full range of overcurrents up to
ing the Selectivity Amp Rating Ratio Table method. their interrupting rating. What can be interpreted from
gure 4 is that the 90-A Class RK5 time-delay fuse is
1. Check fuse 1 with fuse 2 coordinated with the 200-A Class J time-delay fuse up
t For the actual fuses, the line-side to load-side amp to 2500 A and is coordinated with the 800-A Class L
rating ratio is 400 A:100 A = 4:1 time-delay fuse up to 12,000 A. Also, the 200-A Class
t Both fuse 1 and fuse 2 are Class J time-delay and J time-delay fuse is coordinated with the 800-A Class L
Table 1 shows a ratio of 2:1 or greater is necessary. fuse up to 12,000 A.
and fuse 2 (4:1) is equal or greater than 2:1 (Table 1), Conclusion: If this specic system has available short-
fuse 1 will selectively coordinate with fuse 2 for any circuit currents for X of 2,500 A or less and X of 12,000
1 2
overcurrent up to 200 kA. A or less; then, this circuit is selectively coordinated.
2. Check fuse 1 with fuse 3 not selectively coordinated for higher fault currents; it just
tActual amp ratio is 800 A:100 A = 8:1 means we cannot draw that conclusion by interpreting
t2:1 or greater is necessary (Table 1). the time-current curve method. To illustrate this point,
t Fuse 1 selectively coordinates with fuse 3 up to 200 use the fuse selectivity amp rating ratio method and Ta-
kA.
ble 1 to check gure 4 for fault currents up to 200 kA for
3. Check fuse 2 with fuse 3 X1and X 2
tActual amp rating ratio is 800 A:400 A = 2:1 delay fuse line-side of a load-side Class K5 time-delay fuse
t2:1 or greater is necessary (Table 1). is 8:1. In the circuit for gure 4, the actual fuse ratio is
t Fuse 2 will selectively coordinate with fuse 3 for any 200 A:90 A = 2.2:1. So, using the ratio method, these
overcurrent up to 200 kA. two fuses would not be selectively coordinated up to 200
kA. However, gure 4 does show these two fuses are se-
Conclusion: lectively coordinated up to 2,500 A. Now investigate the
for any overcurrent up to 200 kA; therefore, X1 and X2
could be any value of available short-circuit currents up to required by Table 1 for Class L time-delay fuse line-side
200 kA. Using this method, there is no need to do a short- of a load-side Class J time-delay fuse is 2:1. In the circuit
circuit current study if a quick assessment shows the short- for gure 4, the actual fuse ratio is 800 A:200 A = 4:1.
circuit currents in the system will be 200 kA or less. So, using the ratio method, these two fuses are selectively
Example b: Fuse Selectivity Time-Current Curves it is quicker and simpler to just use the fuse selectivity am-
Use this method only for the portion of the curve that is pere ratio method rather than plotting the time-current
curves and interpreting.
industry time-current curve has a vertical time axis
from 0.01 seconds up to 300 seconds or 1000 seconds. Selective Coordination Basics
However, fuses when operating in their current-lim- for Circuit Breakers
iting range, clear in less than 0.01 seconds. Depend- -
ing on the fuse type, amp rating, and available fault tion using circuit breakers (CBs) are also relatively sim-
current, the clearing time can be less than 0.01 sec.
4 www.iaei.org Reprinted by permission of IAEI News July . August 2010 IAEI NEWS
SELECTIVE COORDINATION ENFORCEMENT
of gure 6 is as follows:
a and b.
IAEI NEWS July . August 2010 Reprinted by permission of IAEI News www.iaei.org 5
SELECTIVE COORDINATION ENFORCEMENT
Figure 7. 600-A CB is set on IT=10X instantaneous trip, resulting in its being able to
Conclusion: If the available short-circuit current selectively coordinate up to a higher available short-circuit current versus figure
at X1 is less than 1800 A and at X 2 less than 5200 6 example.
6 www.iaei.org Reprinted by permission of IAEI News July . August 2010 IAEI NEWS
SELECTIVE COORDINATION ENFORCEMENT
IAEI NEWS July . August 2010 Reprinted by permission of IAEI News www.iaei.org 7
SELECTIVE COORDINATION ENFORCEMENT
Type F
15A 5.0 kA 10.0 kA 12.0 kA
40A 4.2 kA 8.3 kA 12.0 kA
100A 4.0 kA 7.0 kA 12.0 kA
225A 4.0 kA 7.0 kA 12.0 kA
8 www.iaei.org Reprinted by permission of IAEI News July . August 2010 IAEI NEWS
SELECTIVE COORDINATION ENFORCEMENT
Conclusion:
Figure 11. 20-A CB selectively coordinates with 200-A fuse up to 2200 A. with the 100-A CB if X1
CB will selectively coordinate with the 400-A CB if X 2
nation for the full range of overcurrents is required
is less than 3200 A.
and that sucient documentation must be submitted.
Plan reviewers or inspectors do not have to be experts
on coordination to enforce the mandatory require-
IAEI NEWS July . August 2010 Reprinted by permission of IAEI News www.iaei.org 9
SELECTIVE COORDINATION ENFORCEMENT
10 www.iaei.org Reprinted by permission of IAEI News July . August 2010 IAEI NEWS